- 56 -
O
U
T
D
OOR UNIT
AOTG30, 34KMT
A
5. Capacity compensation rate for pipe length and height
difference
5-1. Model: AOTG30KMTA
NOTE:
Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5
7.5
10
20
30
40
50
Height difference H
(m)
Indoor unit is higher than
outdoor unit *1
30
-
-
-
-
0.926
0.916
0.906
20
-
-
-
0.953
0.942
0.931
0.920
10
-
-
0.979
0.968
0.958
0.946
0.936
7.5
-
0.988
0.983
0.972
0.961
0.951
0.939
5
0.992
0.992
0.987
0.976
0.965
0.954
0.943
0
1.000
1.000
0.995
0.984
0.973
0.962
0.951
Indoor unit is lower than
outdoor unit *2
-5
1.000
1.000
0.995
0.984
0.973
0.962
0.951
-7.5
-
1.000
0.995
0.984
0.973
0.962
0.951
-10
-
-
0.995
0.984
0.973
0.962
0.951
-20
-
-
-
0.984
0.973
0.962
0.951
-30
-
-
-
-
0.973
0.962
0.951
HEATING
Pipe length (m)
5
7.5
10
20
30
40
50
He
igh
t differ
ence
H (m)
Indoor unit is higher than
outdoor unit *1
30
-
-
-
-
0.931
0.914
0.899
20
-
-
-
0.954
0.931
0.914
0.899
10
-
-
0.990
0.954
0.931
0.914
0.899
7.5
-
1.000
0.990
0.954
0.931
0.914
0.899
5
1.000
1.000
0.990
0.954
0.931
0.914
0.899
0
1.000
1.000
0.990
0.954
0.931
0.914
0.899
Indoor unit is lower than
outdoor unit *2
-5
0.995
0.995
0.986
0.949
0.926
0.909
0.895
-7.5
-
0.993
0.983
0.946
0.924
0.907
0.892
-10
-
-
0.981
0.944
0.921
0.904
0.890
-20
-
-
-
0.935
0.912
0.895
0.881
-30
-
-
-
-
0.903
0.886
0.872
Height difference H
Indoor unit is higher than outdoor unit
*
1
Indoor unit is lower than outdoor unit
*
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
H
H
Summary of Contents for AOTG30KMTA
Page 5: ...Part 1 INDOOR UNIT WALL MOUNTED TYPE ASTG30KMTA ASTG34KMTA ...
Page 15: ... 11 WALL MOUNTED ASTG30 34KMTA 5 Wiring diagram ...
Page 21: ... 17 WALL MOUNTED ASTG30 34KMTA 8 2 Sound level check point 0 8 m 1 m Microphone Microphone ...
Page 44: ... 40 WALL MOUNTED ASTG30 34KMTA ...
Page 45: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOTG30KMTA AOTG34KMTA ...
Page 56: ... 52 OUTDOOR UNIT AOTG30 34KMTA 3 Refrigerant circuit 3 1 Model AOTG30KMTA ...
Page 57: ... 53 OUTDOOR UNIT AOTG30 34KMTA 3 2 Model AOTG34KMTA ...
Page 58: ... 54 OUTDOOR UNIT AOTG30 34KMTA 4 Wiring diagrams 4 1 Model AOTG30KMTA ...
Page 59: ... 55 OUTDOOR UNIT AOTG30 34KMTA 4 2 Model AOTG34KMTA ...