- 29 -
W
A
LL
MOU
N
TED
ASTG30, 34
KMTA
Error status
The output is ON when an error is generated for the indoor unit.
Indoor unit fan operation status
Function
setting /
Rotary SW on
External input and
output PCB
External output
Output
signal
Command
60-09 / B
Output of indoor unit
CN3
Low
→
High
Error
High
→
Low
Normal
60-00 / 1
External input and output
PCB
CN311
Off
→
On
Error
On
→
Off
Normal
Function
setting /
Rotary SW on External
input and output PCB
External output
Output
signal
Command
60-10 / C
Output of indoor unit
CN3
Low
→
High
Fan run
High
→
Low
Fan stop
60-00 / 1
External input and output
PCB
CN312
Off
→
On
Fan run
On
→
Off
Fan stop
Output signal
Condition
On
The indoor unit fan is operating.
Low
→
High
Off
The fan is stopped or during cold air prevention.
High
→
Low
During thermostat off when in dry mode operation.
Error
Normal
High
Low
CN3
On
Off
CN310―312
Indoor unit
Fan run
Fan stop
High
Low
CN3
On
Off
CN311―312
Indoor unit
Summary of Contents for AOTG30KMTA
Page 5: ...Part 1 INDOOR UNIT WALL MOUNTED TYPE ASTG30KMTA ASTG34KMTA ...
Page 15: ... 11 WALL MOUNTED ASTG30 34KMTA 5 Wiring diagram ...
Page 21: ... 17 WALL MOUNTED ASTG30 34KMTA 8 2 Sound level check point 0 8 m 1 m Microphone Microphone ...
Page 44: ... 40 WALL MOUNTED ASTG30 34KMTA ...
Page 45: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOTG30KMTA AOTG34KMTA ...
Page 56: ... 52 OUTDOOR UNIT AOTG30 34KMTA 3 Refrigerant circuit 3 1 Model AOTG30KMTA ...
Page 57: ... 53 OUTDOOR UNIT AOTG30 34KMTA 3 2 Model AOTG34KMTA ...
Page 58: ... 54 OUTDOOR UNIT AOTG30 34KMTA 4 Wiring diagrams 4 1 Model AOTG30KMTA ...
Page 59: ... 55 OUTDOOR UNIT AOTG30 34KMTA 4 2 Model AOTG34KMTA ...