- 28 -
W
A
LL
MOU
N
TED
ASTG30, 34
KMTA
Forced thermostat off function
Control output function
Operation/Stop status
The output is low when the unit is stopped.
Function
setting /
Rotary SW on
External input and
output PCB
External input
Input signal
Command
60-00 / 2
60-09 / B
60-10 / C
External input and output
PCB
CN313
Off
→
On
Thermostat
off
On
→
Off
Normal
operation
Function
setting /
Rotary SW on
External input and
output PCB
External output
Output
signal
Command
60-00 / 1, 2
Output of indoor unit
CN3
Low
→
High
Operation
High
→
Low
Stop
60-00 / 1
External input and output
PCB
CN310
Off
→
On
Operation
On
→
Off
Stop
On
Off
On
Off
Compressor
Room temp.
Set temp.
Input
Operation
Stop
High
Low
CN3
On
Off
CN310
Indoor unit