![Fujitsu AOHG07KGCA Service Manual Download Page 84](http://html.mh-extra.com/html/fujitsu/aohg07kgca/aohg07kgca_service-manual_2344036084.webp)
4-5. Outdoor unit fan motor
Check point 1. Check rotation of fan
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
If fan or bearing is abnormal, replace it.
Check point 2. Check resistance of outdoor fan motor
Refer to below. Circuit-test “Vm” and “GND” terminal
NOTE:
Vm: DC voltage, GND: Earth terminal
If they are short-circuited (below 300 kΩ), replace outdoor fan motor and controller PCB.
Pin number
(wire color)
Terminal function
(symbol)
1 (Red)
DC voltage (Vm)
2
No function
3
No function
4 (Black)
Earth terminal (GND)
5 (→hite)
Control voltage (Vcc)
6 (↔ellow)
Speed command (Vsp)
7 (Blue)
Feed back (FG)
4-5. Outdoor unit fan motor