![Fujitsu AOHG07KGCA Service Manual Download Page 40](http://html.mh-extra.com/html/fujitsu/aohg07kgca/aohg07kgca_service-manual_2344036040.webp)
Check point 4. Check serial signal (Reverse transfer signal)
Check serial signal (Reverse transfer signal)
RED
WHITE
BLACK
BLACK
WHITE
GREEN
+
-
N
L
3
2
1
•
Check if indicated value swings between AC 90 V and AC 270 V at the outdoor unit terminal 1
—3.
•
If it is abnormal, check the parts below.
– Outdoor unit fan motor in
•
If outdoor fan motor is abnormal, replace outdoor unit fan motor and main PCB.
•
If the checked parts are normal, replace the main PCB.
End
Check point 1-2. Check external cause such as noise
•
Check the complete insulation of the grounding.
•
Check if there is any equipment that causes harmonic wave near the power cable (Neon light
bulb or any electronic equipment which causes harmonic wave).
End
2-1. E: 11. Serial communication error (Serial reverse transfer error) (Outdoor unit)
- (03-4) -
2. Troubleshooting with error code
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Summary of Contents for AOHG07KGCA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 3 11 SR_CH01_AS069EG_01 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 3 11 SR_CH02_AS069EG_01 ...
Page 33: ...3 TROUBLESHOOTING 2022 03 25 SR_CH03_AS069EG_01 ...
Page 36: ......
Page 89: ...4 CONTROL AND FUNCTIONS 2022 03 25 SR_CH04_AS069EG_01 ...
Page 91: ...8 6 High temperature and high pressure release control heating mode 04 32 CONTENTS continued ...
Page 92: ......
Page 125: ...5 FILED WORKING 2022 03 25 SR_CH05_AS069EG_01 ...