![Fujitsu AOHG07KGCA Service Manual Download Page 144](http://html.mh-extra.com/html/fujitsu/aohg07kgca/aohg07kgca_service-manual_2344036144.webp)
NOTES:
• →hen the forced stop is triggered, indoor unit stops and Operation/Stop operation by the remote
controller is restricted.
• →hen forced stop function is used with forming a remote controller group, connect the same
equipment to each indoor unit within the group.
¢
Operation/Stop mode 2
•
In the case of “Edge” input
Function
setting
External input and
output PCB
External input
Input signal
Command
Rotary
switch
SW302
46-03
—
Input of indoor unit
CN46
Off On
Operation
(R.C. enabled)
On Off
Stop
(R.C. disabled)
1
Edge
External input and
output PCB
CN313
Off On
Operation
(R.C. enabled)
On Off
Stop
(R.C. disabled)
On
CN313
Off
On
Indoor unit operation
Off
Remote contoller
On
On
Off
•
In the case of “Pulse” input
Function
setting
External input and
output PCB
External input
Input signal
Command
Rotary
switch
SW302
46-03
1
Pulse
External input and
output PCB
CN313
Pulse
Operation
(R.C. enabled)
CN314
Stop
(R.C. disabled)
On
On
Off
On
Off
Remote controller
On
Off
Indoor unit operation
CN313
CN314
Off
On
2-4. Details of control input function
- (05-18) -
2. External input and output
FI
EL
D
W
O
R
K
IN
G
FI
EL
D
W
O
R
K
IN
G
Summary of Contents for AOHG07KGCA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 3 11 SR_CH01_AS069EG_01 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 3 11 SR_CH02_AS069EG_01 ...
Page 33: ...3 TROUBLESHOOTING 2022 03 25 SR_CH03_AS069EG_01 ...
Page 36: ......
Page 89: ...4 CONTROL AND FUNCTIONS 2022 03 25 SR_CH04_AS069EG_01 ...
Page 91: ...8 6 High temperature and high pressure release control heating mode 04 32 CONTENTS continued ...
Page 92: ......
Page 125: ...5 FILED WORKING 2022 03 25 SR_CH05_AS069EG_01 ...