![Fujitsu AOHG07KGCA Service Manual Download Page 139](http://html.mh-extra.com/html/fujitsu/aohg07kgca/aohg07kgca_service-manual_2344036139.webp)
2-2. External output
Use an external output cable with appropriate external dimension, depending on the number of ca-
bles to be installed.
¢
Indoor unit
• A twisted pair cable should be used. Maximum length of cable is 25 m.
• Output voltage: High DC 12 V ±2 V, Low 0 V.
• Permissible current: 50 mA
• For details, refer to
"Setting of external input and output"
•
When indicator, etc. are connected directly
Example:
Function setting number 60 is set to "00"
1
2
CN47
LED
PCB
Resistor
Connected device
+
-
•
When connecting with a device equipped with a power supply
Example:
Function setting number 60 is set to "00"
1
2
Connected device
CN47
PCB
Connected device
Relay
(Operation status)
-
+
2-2. External output
- (05-13) -
2. External input and output
FI
EL
D
W
O
R
K
IN
G
FI
EL
D
W
O
R
K
IN
G
Summary of Contents for AOHG07KGCA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 3 11 SR_CH01_AS069EG_01 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 3 11 SR_CH02_AS069EG_01 ...
Page 33: ...3 TROUBLESHOOTING 2022 03 25 SR_CH03_AS069EG_01 ...
Page 36: ......
Page 89: ...4 CONTROL AND FUNCTIONS 2022 03 25 SR_CH04_AS069EG_01 ...
Page 91: ...8 6 High temperature and high pressure release control heating mode 04 32 CONTENTS continued ...
Page 92: ......
Page 125: ...5 FILED WORKING 2022 03 25 SR_CH05_AS069EG_01 ...