1-6. Setting the Indoor room temperature sensor switching function
(Only for Wired remote controller)
The following settings are needed when use the control by Wired remote controller temperature sensor.
( Factory setting)
Setting Description
Function Number
Setting Value
No
Yes
42
00
01
If setting value is “00”,
room temperature is controlled by the indoor unit temperature sensor.
If setting value is “01”,
room temperature is controlled by either indoor unit temperature sensor or remote control unit sensor.
1-7. Setting the Remote controller signal code
Change the indoor unit Signal Code, depending on the remote controllers.
( Factory setting)
Setting Description
Function Number
Setting Value
A
B
C
D
44
00
01
02
03
1-8. Setting the External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
( Factory setting)
Setting Description
Function Number
Setting Value
Operation /Stop mode
(Setting forbidden)
Forced stop mode
46
00
01
02