Trouble shooting 14
OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 :
Check Point 3 :
OK
OK
OK
OK
Discharge temp. thermistor error
Outdoor unit Main PCB
Discharge pipe temperature thermistor
When the discharge pipe temperature thermistor open or short-circuit
is detected at power ON or while running the compressor.
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check Thermistor resistance value
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
02-16
TH
E
R
M
IS
TO
R
(D
IS
C
H
A
R
G
E
)
TH
E
R
M
IS
TO
R
(P
IP
E
)
TH
E
R
M
IS
TO
R
(O
U
TD
O
O
R
)
B
LA
C
K
B
LA
C
K
CN70 CN71
1 2 3 4
1 2 3 4
1 2 3
1 2 3
B
R
O
W
N
Thermistor Characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Resistance Value (k )
Temperature(
°C)
Resistance Value (k )
Temperature(
°C)
-30 -20 -10 0 10 20 30 40 50
60 70 80 90 100 110 120
1013.1 531.6 292.9 168.6 100.9 62.5 40.0 26.3 17.8
12.3 8.7 6.3 4.6 3.4 2.6 2.0
Indicate or Display:
Outdoor Unit :
LED 0.1sec ON/ 0.1sec OFF
Indoor Unit : Operation lamp: 7 time Flash, Timer lamp: 1 time Flash
Economy lamp : Continuous flash.
ERROR CODE : [E : 71]
Summary of Contents for AOCG040LBTA
Page 3: ...R410A SLIM DUCT type INVERTER 1 DESCRIPTION OF EACH CONTROL OPERATION ...
Page 26: ...2 TROUBLE SHOOTING R410A SLIM DUCT type INVERTER ...
Page 59: ...3 APPENDING DATA SLIM DUCT type INVERTER R410A ...
Page 67: ...3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan Jun 2016 Printed in Japan ...