background image

En-14

7.3.1. Button name and function

TIMER indicator lamp (Orange)

MANUAL AUTO button

OPERATION indicator lamp (Green)

FILTER indicator lamp (Red)

7.3.2. Checking the function settings

Press and hold the “MANUAL AUTO” button on the indoor unit for 3 seconds to check 
the function settings. It is necessary to disconnect the power in order to return to normal 
operation mode.

(1) Indoor unit and refrigerant address indication

Indication pattern

Indicator name

Indication pattern

Indoor unit 

address

Refrigerant address

OPERATION indicator lamp (Green)

ON

Flash (1.0s ON/1.0s OFF)

TIMER indicator lamp (Orange)

Address: tens place (0.5s ON/0.5s OFF)

FILTER indicator lamp (Red)

Address: ones place (0.5s ON/0.5s OFF)

•  Indoor unit address example

(Example) ADDRESS : 24

OPERATION 

indicator 

lamp (Green)

TIMER 

indicator 

lamp (Orange)
FILTER 

indicator 

lamp (Red)

10 sec

1 cycle 12 sec

8 sec

ON

OFF

0.5s 0.5s 0.5s 0.5s 0.5s 0.5s 0.5s 0.5s

0.5s 0.5s 0.5s 0.5s

ON

OFF

ON

OFF

ON

•  Indoor unit address example Refrigerant address example
(Example) ADDRESS : 30 

OPERATION 

indicator 

lamp (Green)

TIMER 

indicator 

lamp (Orange)

FILTER 

indicator 

lamp (Red)

9 sec

1 cycle 12 sec

ON

OFF

1.0s

1.0s

1.0s

1.0s

1.0s

1.0s

1.0s

0.5s 0.5s 0.5s 0.5s 0.5s 0.5s

ON

OFF

ON

OFF

OFF

• Setting details

Function number

Item

Setting number

01

Indoor unit address

00 to 63

02

Refrigeration address

00 to 99

For use with a remote controller, set all rotary switches to 0, and refer to “7.1. Setting the 
address” for details.
All switches are set to 0 at the factory.

(2) Others

Indication pattern

Indicator Name

Indication pattern

OPERATION indicator lamp (Green)

Function number; tens place (0.5s ON/0.5s OFF)

TIMER indicator lamp (Orange)

Function number; ones place (0.5s ON/0.5s OFF)

FILTER indicator lamp (Red)

Setting number: (0 to 9) (0.5s ON/0.5s OFF)

(Example) Function : 31, Setting number : 2

OPERATION 

indicator 

lamp (Green)

TIMER 

indicator 

lamp (Orange)

FILTER 

indicator 

lamp (Red)

11 sec

10 sec

9 sec

1 cycle 12 sec

ON

OFF

0.5s 0.5s

0.5s

0.5s

0.5s

0.5s

0.5s

0.5s

0.5s

0.5s 0.5s 0.5s

ON

OFF

ON

OFF

8.  FRESH-AIR INTAKE

(1)  Open up the knockout hole for the fresh-air intake (If using half-concealed installa-

tion, open up the top knockout hole instead.)

For half concealed 
installation

Indoor unit

 

CAUTION

When removing the cabinet (iron plate), be careful not to damage the indoor unit 
internal parts and surrounding area (outer case).

When processing the cabinet (iron plate), be careful not to injure yourself with burrs, 
etc.

(2)  Fasten the round 

fl

 ange (optional) to the fresh-air intake (If using half-concealed in-

stallation, attach to the top.)

Round duct (Option parts)

[After completing “3.3. Installing the unit”…]

(3)  Connect the duct to the round 

fl

 ange.

(4)  Seal with a band and vinyl tape, etc. so that air does not leak from the connection.

Duct

9367702091-02_IM.indb   En-14

9367702091-02_IM.indb   En-14

12/29/2011   8:57:48 AM

12/29/2011   8:57:48 AM

Summary of Contents for Airstage ABUA30RLAV

Page 1: ...E INTERIOR Tipo teto For authorized service personnel only Uniquement réservé aux techniciens agréés Sólo para personal de mantenimiento autorizado Apenas para técnicos de assistência autorizados PART NO 9367702091 02 Português Español Français English ABUA30RLAV ABUA36RLAV 9367702091 02_IM indb cover1 9367702091 02_IM indb cover1 12 29 2011 8 57 26 AM 12 29 2011 8 57 26 AM ...

Page 2: ...er OFF at the main circuit breaker panel before opening the unit to check or repair electrical parts and wiring Keep your fingers and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced After installation explain correct operation to the customer using the operating manual D...

Page 3: ...conventional R22 vacuum pump can be used by installing a vacuum pump adapter Be sure that the pump oil does not backflow into the system Use one capable for vacuum suction of 5 Torr 755 mmHg 100 7 kPa Gas leakage detector Special gas leakage detector for R410A refrigerant 1 2 3 Accessories WARNING For installation purposes be sure to use the parts supplied by the manufacturer or other prescribed p...

Page 4: ...t on a place having a sufficient strength so that it withstands against the weight of the indoor unit 2 The inlet and outlet ports should not be obstructed the air should be able to blow all over the room 3 Leave the space required to service the air conditioner 4 Install the unit where connection to the outdoor unit is easy 5 Install the unit where the connection pipe can be easily installed 6 In...

Page 5: ...32 in 10 to 15 mm 3 3 6 Installing the indoor unit 1 Lift unit so that suspension bolts pass through the suspension fittings at the sides 4 places and slide the unit back Ceiling Wall 3 3 3 Location of ceiling suspension bolts Fig A 1 3 16 30 Suspension bolt pitch 5 ft 3 in 1 600 1 3 16 30 Dimensions Space required for Installation 13 32 10 5 29 32 150 11 13 16 300 INDOOR UNIT TOP VIEW Unit in mm ...

Page 6: ...nd both the gas and liquid pipes Failure to do so may cause water leaks Use heat insulation with heat resistance above 248 F 120 C Reverse cycle model only In addition if the humidity level at the installation location of the refrigerant piping is expected to exceed 70 install heat insulation around the refrigerant piping If the expected humidity level is 70 to 80 use heat insulation that is 19 32...

Page 7: ...re nut from the indoor unit pipe until immediately before connecting the connection pipe Do not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units 1 4 4 Installing heat insulation Install the heat insulation material after performing a refrigerant leak check see the Instal lation Manual for the outdoor unit for details COU...

Page 8: ...up Prohibited Prohibited 1 Install insulation for the drain pipe Assemble as described below Drain port Assemble Drain hose Accessories and Hose band Accessories to Drain port Hose band Accessories Drain hose Accessories Soft PVC side Drain hose Accessories 13 32 to 19 32 in 10 to 15 mm Hose Band Accessories Soft PVC side Ensure there is no space Drain pan Wrap the drain hose insulation around the...

Page 9: ...ct power supply cables to the transmission or remote controller terminals as this will damage the product Never bundle the power supply cable and transmission cable remote controller cable together Separate these cable by 1 31 32 in 50 mm or more Bundling these cables together will cause miss operation or breakdown When handling PCB static electricity charged in the body may cause malfunction of t...

Page 10: ...here is no stress placed on the terminals 4 Use an appropriate screwdriver to tighten the terminal screws Do not use a screwdriver that is too small otherwise the screw heads may be damaged and prevent the screws from being properly tightened 5 Do not tighten the terminal screws too much otherwise the screws may break 6 See the table for the terminal screw tightening torques 7 Please do not fix 2 ...

Page 11: ...ble line Input selection Use either one of these types of terminal according to the application Both types of terminals cannot be used simultaneously Voltage terminal CN6 When a power supply must be provided at the input device you want to connect use the voltage terminal CN6 1 2 3 Input device 1 Input device 2 Load resis tance Load resis tance 1 DC power supply 12 to 24 V Connected unit a a P C B...

Page 12: ...unit stops and Start Stop operation by a remote controller is restricted When forced stop function is used with forming a remote controller group connect the same equipment to each indoor unit within the group Selection method of functions Start Stop mode or Emergency stop mode Forced stop mode can be selected with function setting of indoor unit 2 External output terminals When picking up output ...

Page 13: ...n OFF the power before performing the field setting 1 7 1 Setting the address Manual address setting method The indoor unit address and the refrigerant circuit address can also be set up through the wireless remote controller CAUTION Use an insulated screwdriver to set the dip switches Rotary switch Example 0 Rotary switch Example 0 Setting Setting range Type of switch Indoor unit address 0 to 63 ...

Page 14: ...to make sure no wiring mistakes were made before turning on the power Function details Function Function number Setting number Default Details Filter indicator interval 11 00 Default Adjust the filter cleaning interval notification If the notification is too early change to setting 01 If the notification is too late change to setting 02 01 Longer 02 Shorter Filter indicator action 13 00 Enable Ena...

Page 15: ...on address 00 to 99 For use with a remote controller set all rotary switches to 0 and refer to 7 1 Setting the address for details All switches are set to 0 at the factory 2 Others Indication pattern Indicator Name Indication pattern OPERATION indicator lamp Green Function number tens place 0 5s ON 0 5s OFF TIMER indicator lamp Orange Function number ones place 0 5s ON 0 5s OFF FILTER indicator la...

Page 16: ... refrigerant pipes No cooling No heating Has heat insulation work been completed Water leakage Does water drain eas ily from the indoor units Water leakage Is the voltage of the power source the same as that indicated on the label on the indoor unit No operation heat or burn damage Are the wires and pipes all connected completely No operation heat or burn damage Is the indoor unit earthed grounded...

Reviews: