background image

En-15

9.  FINISHING

(1)  Reattach cover A and B. Then fasten the control box back into its original position 

using the 4 tapping screws.

Cover A

Top of the Cover A

Top of the Cover B

Cover B

(2)  Attach the remote controller cable, transmission cable, power supply cable, RB unit 

cable (for Reverse cycle model) and cable clips. Make sure that they are positioned so 
that they will not interfere with opening and closing of the intake grille or with removal 
and installation of the air 

fi

 lters.

Cable clip Remote controller cable

Transmission cable

Power supply cable

(3)  Close the piping outlet with the closing material (putty etc.).
(4) Install 

the 

fi

 lter guide.

(5)  Install the intake grilles.
(6)  Install side covers A and B (if the unit is installed in a half-concealed orientation, only 

install side cover A).

(7)  Install the air 

fi

 lters.

10. TEST RUN

]1

10.1. Test run using PCB (Outdoor unit)

•  Refer to the Installation Manual for the outdoor unit if the PCB for the outdoor unit is to 

be used for the test run.

10.2. Test run using remote controller

•  Refer to the Installation Manual for the remote controller to perform the test run using 

the remote controller.

•  When the air conditioner is being test run, the OPERATION and TIMER indicator lamps 

fl

 ash slowly at the same time.

11. CHECK  LIST

]1

Pay special attention to the check items below when installing the indoor unit(s). 
After installation is complete, be sure to check the following check items again.

Check items

If not performed correctly

Check 

box

Has the indoor unit been 
installed correctly?

Vibration, noise, indoor unit may drop

Has there been a check for 
gas leaks (refrigerant pipes)?

No cooling, No heating

Has heat insulation work 
been completed?

Water leakage

Does water drain eas-
ily from the indoor units?

Water leakage

Is the voltage of the power 
source the same as that indicated 
on the label on the indoor unit?

No operation, heat or burn damage

Are the wires and pipes all 
connected completely?

No operation, heat or burn damage

Is the indoor unit earthed 
(grounded)?

Short circuit

Is the connection cable the 
speci

fi

 ed thickness?

No operation, heat or burn damage

Are the inlets and outlets 
free of any obstacles?

No cooling, No heating

Does start and stop air con-
ditioner operation by remote 
controller or external device?

No operation

After installation is completed, 
has the proper operation and han-
dling been explained to the user?

12. ERROR CODES

1

If you use a wired type remote controller, error codes will appear on the remote controller 
display. If you use a wireless remote controller the lamp on the photodetector unit will 
output error codes by way of blinking patterns. See the lamp blinking patterns and error 
codes in the table below.

Error display

Wired 

Remote 

Controller 

Error CODE

Error contents

OPERATION 

indicator 

lamp (green)

TIMER 

indicator 

lamp (orange)

FILTER 

indicator 

lamp (red)

 (1)

 (2)

Remote controller 
communication error

 (1)

 (4)

Anomalous network 
communications

 (1)

 (6)

Parallel communication 
error

 (3)

 (1)

Power frequency error

 (3)

 (2)

Model information error/
EEPROM accession 
error

 (4)

 (1)

Room temperature 
thermistor error

 (4)

 (2)

Indoor heat exchanger 
temperature thermistor 
error

 (5)

 (1)

Indoor fan motor error

 (5)

 (3)

Drainage error

 (9)

 (15)

Outdoor unit error

Display mode 

  :  0.5s ON / 0.5s OFF

 

 :  0.1s ON / 0.1s OFF

 

( )  :  Number of 

fl

 ashing

Wired Remote Controller Display

Error code

9367702091-02_IM.indb   En-15

9367702091-02_IM.indb   En-15

12/29/2011   8:57:49 AM

12/29/2011   8:57:49 AM

Summary of Contents for Airstage ABUA30RLAV

Page 1: ...E INTERIOR Tipo teto For authorized service personnel only Uniquement réservé aux techniciens agréés Sólo para personal de mantenimiento autorizado Apenas para técnicos de assistência autorizados PART NO 9367702091 02 Português Español Français English ABUA30RLAV ABUA36RLAV 9367702091 02_IM indb cover1 9367702091 02_IM indb cover1 12 29 2011 8 57 26 AM 12 29 2011 8 57 26 AM ...

Page 2: ...er OFF at the main circuit breaker panel before opening the unit to check or repair electrical parts and wiring Keep your fingers and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced After installation explain correct operation to the customer using the operating manual D...

Page 3: ...conventional R22 vacuum pump can be used by installing a vacuum pump adapter Be sure that the pump oil does not backflow into the system Use one capable for vacuum suction of 5 Torr 755 mmHg 100 7 kPa Gas leakage detector Special gas leakage detector for R410A refrigerant 1 2 3 Accessories WARNING For installation purposes be sure to use the parts supplied by the manufacturer or other prescribed p...

Page 4: ...t on a place having a sufficient strength so that it withstands against the weight of the indoor unit 2 The inlet and outlet ports should not be obstructed the air should be able to blow all over the room 3 Leave the space required to service the air conditioner 4 Install the unit where connection to the outdoor unit is easy 5 Install the unit where the connection pipe can be easily installed 6 In...

Page 5: ...32 in 10 to 15 mm 3 3 6 Installing the indoor unit 1 Lift unit so that suspension bolts pass through the suspension fittings at the sides 4 places and slide the unit back Ceiling Wall 3 3 3 Location of ceiling suspension bolts Fig A 1 3 16 30 Suspension bolt pitch 5 ft 3 in 1 600 1 3 16 30 Dimensions Space required for Installation 13 32 10 5 29 32 150 11 13 16 300 INDOOR UNIT TOP VIEW Unit in mm ...

Page 6: ...nd both the gas and liquid pipes Failure to do so may cause water leaks Use heat insulation with heat resistance above 248 F 120 C Reverse cycle model only In addition if the humidity level at the installation location of the refrigerant piping is expected to exceed 70 install heat insulation around the refrigerant piping If the expected humidity level is 70 to 80 use heat insulation that is 19 32...

Page 7: ...re nut from the indoor unit pipe until immediately before connecting the connection pipe Do not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units 1 4 4 Installing heat insulation Install the heat insulation material after performing a refrigerant leak check see the Instal lation Manual for the outdoor unit for details COU...

Page 8: ...up Prohibited Prohibited 1 Install insulation for the drain pipe Assemble as described below Drain port Assemble Drain hose Accessories and Hose band Accessories to Drain port Hose band Accessories Drain hose Accessories Soft PVC side Drain hose Accessories 13 32 to 19 32 in 10 to 15 mm Hose Band Accessories Soft PVC side Ensure there is no space Drain pan Wrap the drain hose insulation around the...

Page 9: ...ct power supply cables to the transmission or remote controller terminals as this will damage the product Never bundle the power supply cable and transmission cable remote controller cable together Separate these cable by 1 31 32 in 50 mm or more Bundling these cables together will cause miss operation or breakdown When handling PCB static electricity charged in the body may cause malfunction of t...

Page 10: ...here is no stress placed on the terminals 4 Use an appropriate screwdriver to tighten the terminal screws Do not use a screwdriver that is too small otherwise the screw heads may be damaged and prevent the screws from being properly tightened 5 Do not tighten the terminal screws too much otherwise the screws may break 6 See the table for the terminal screw tightening torques 7 Please do not fix 2 ...

Page 11: ...ble line Input selection Use either one of these types of terminal according to the application Both types of terminals cannot be used simultaneously Voltage terminal CN6 When a power supply must be provided at the input device you want to connect use the voltage terminal CN6 1 2 3 Input device 1 Input device 2 Load resis tance Load resis tance 1 DC power supply 12 to 24 V Connected unit a a P C B...

Page 12: ...unit stops and Start Stop operation by a remote controller is restricted When forced stop function is used with forming a remote controller group connect the same equipment to each indoor unit within the group Selection method of functions Start Stop mode or Emergency stop mode Forced stop mode can be selected with function setting of indoor unit 2 External output terminals When picking up output ...

Page 13: ...n OFF the power before performing the field setting 1 7 1 Setting the address Manual address setting method The indoor unit address and the refrigerant circuit address can also be set up through the wireless remote controller CAUTION Use an insulated screwdriver to set the dip switches Rotary switch Example 0 Rotary switch Example 0 Setting Setting range Type of switch Indoor unit address 0 to 63 ...

Page 14: ...to make sure no wiring mistakes were made before turning on the power Function details Function Function number Setting number Default Details Filter indicator interval 11 00 Default Adjust the filter cleaning interval notification If the notification is too early change to setting 01 If the notification is too late change to setting 02 01 Longer 02 Shorter Filter indicator action 13 00 Enable Ena...

Page 15: ...on address 00 to 99 For use with a remote controller set all rotary switches to 0 and refer to 7 1 Setting the address for details All switches are set to 0 at the factory 2 Others Indication pattern Indicator Name Indication pattern OPERATION indicator lamp Green Function number tens place 0 5s ON 0 5s OFF TIMER indicator lamp Orange Function number ones place 0 5s ON 0 5s OFF FILTER indicator la...

Page 16: ... refrigerant pipes No cooling No heating Has heat insulation work been completed Water leakage Does water drain eas ily from the indoor units Water leakage Is the voltage of the power source the same as that indicated on the label on the indoor unit No operation heat or burn damage Are the wires and pipes all connected completely No operation heat or burn damage Is the indoor unit earthed grounded...

Reviews: