En-10
]1
6.4. Connection of wiring
(1) Remove the 2 tapping screws and pull the control box downward.
Indoor unit
Control box
Tapping screw
(2) Remove the cover A and B. And install the connection cable.
Cover A
Cover B
Control box
(3) After wiring is complete, clamp the power supply cable with the cable binder
(Accessories).
For U.S.A. and Canada
GND
Conduit (L1, L2 (N):
Power supply cable)
X1, X2:
Transmission
cable
Lock nut
Binder (Medium)
(Accessories)
Remote controller cable
Y1: Red,
Y2: White,
Y3: Black
For Others
X1, X2:
Transmission
cable
Remote controller cable
Y1: Red,
Y2: White,
Y3: Black
L1, L2 (N)
Power supply cable
Binder (Medium)
(Accessories)
GND
Grommet edging
(Accessories)
]1
6.5. External input and external output (Optional parts)
Controller PCB
Input No Voltage terminal (CN17)
Input Voltage terminal (CN6)
Output terminal (CN16)
(1) External input terminals
• Indoor unit can be Start/Stop or Emergency stop, Forced stop by using indoor unit PCB
CN6 or CN17.
Wiring methods and speci
fi
cations
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 492 ft. (150 m).
* Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
• The wire connection should be separate from the power cable line.
• Input selection
Use either one of these types of terminal according to the
application. (Both types of terminals cannot be used simultaneously.)
• Voltage terminal ([CN6])
When a power supply must be provided at the input device you want to connect, use the
voltage terminal ([CN6]).
1
2
3
+
+
-
-
-
In
pu
t d
ev
ic
e 1
In
pu
t d
ev
ic
e 2
Load resis-
tance
Load resis-
tance
*1
DC power supply
12 to 24 V
Connected unit
*a
*a
P.C.B
CN6
*b
*1 Make the power supply DC12 to 24V. Select a power supply capacity with an ample
surplus for the connected load.
Do not impress a voltage exceeding 24V across pins 1-2, and 1-3.
*a The allowable current is DC5 to 10mA. (Recommended: DC5mA)
Provide a load resistance such that the current becomes DC10mA or less.
Select very low current use contacts (usable at DC12V, DC1mA or less).
*b The polarity is [+] for pin 1 and [-] for pin 2 and 3.
Connect
correctly.
When connected to voltage terminals of multiple indoor units with a connected unit, be
sure to make a branch outside the indoor unit using a pull box, etc. as shown on below
example.
DC power
supply 12 to 24 V
Connected unit
Load
resistance
P.C.B
P.C.B
CN6
CN6
CN6
P.C.B
In
pu
t d
ev
ic
e 1
In
pu
t d
ev
ic
e 2
Indo
or
unit
Indo
or
unit
Indo
or
unit
Load
resistance
• No voltage terminal ([CN17])
When a power supply is unnecessary at the input device you want to connect, use the no
voltage terminal ([CN17]).
9367702091-02_IM.indb En-10
9367702091-02_IM.indb En-10
12/29/2011 8:57:45 AM
12/29/2011 8:57:45 AM