Description of display
LED display lamp
Function or operation method
(1) POWER/MODE
Green
• Turns on when the power supply is ON (Including
when error occurs).
• Indicate the MODE by the number of flashes when
the installation function is active.
(2) ERROR
Red
Flashes at high-speed when there is an error.
(3) MONITOR
A
Red
• Displays the location and contents of errors when
there is an error. (Refer to Chapter 14-3.
• Displays when check run is activated. (Refer to
B
Red
C
Red
D
Red
E
Red
F
Red
Switch
Function or operation method
Factory setting
SW1
Push
• For the test run start and stop.
• For the pump down start and stop.
—
SW2
Push
• For when check run function is activated.
• For displaying the check run.
• For resetting the Automatic wiring correction memory.
—
SET1-1
DIP
For selecting cooling or heating during test operation.
OFF
SET1-2
DIP
For switching SW1 operation.
OFF
SET1-3
DIP
(Prohibited)
OFF (Do not change)
SET1-4
DIP
(Prohibited)
OFF (Do not change)
SET2-1
DIP
• For selecting outdoor unit low noise operation function.
• To use this function, the Central remote controller
(option) is necessary.
OFF
SET2-2
DIP
(Prohibited)
OFF (Do not change)
SET2-3
DIP
Changing the current limit
OFF
SET2-4
DIP
SET3-1
DIP
(Prohibited)
OFF (Do not change)
SET3-2
DIP
(Prohibited)
OFF (Do not change)
SET3-3
DIP
(Prohibited)
OFF (Do not change)
SET3-4
DIP
(Prohibited)
OFF (Do not change)
Be sure to disconnect the power supply or turn off the breaker before changing the DIP switch
setting.
- 401 -
OUTDOOR UNIT
AOYG45LBLA6
Summary of Contents for agyg09lvca
Page 8: ......
Page 54: ... Models ASYG18LFCA ASYG24LFCA and ASYG24LFCC 46 MULTI TYPE 5 6 ROOMS TYPE ...
Page 55: ...4 5 Floor Ceiling type Models ABYG14LVTA and ABYG18LVTB 47 MULTI TYPE 5 6 ROOMS TYPE ...
Page 56: ...4 6 Floor type Models AGYG09LVCA AGYG12LVCA and AGYG14LVCA 48 MULTI TYPE 5 6 ROOMS TYPE ...
Page 281: ...Part 2 OUTDOOR UNIT 5 ROOMS TYPE MULTI TYPE AOYG36LBLA5 ...
Page 289: ...5 Wiring diagram 5 1 Model AOYG36LBLA5 281 OUTDOOR UNIT AOYG36LBLA5 ...
Page 352: ... 344 OUTDOOR UNIT AOYG36LBLA5 ...
Page 353: ...Part 3 OUTDOOR UNIT 6 ROOMS TYPE MULTI TYPE AOYG45LBLA6 ...
Page 360: ...5 Wiring diagram 5 1 Model AOYG45LBLA6 352 OUTDOOR UNIT AOYG45LBLA6 ...