background image

3. Attach the remote controller.

When attaching to switch box:

a. Seal the wiring hole of the remote controller cable.
b. Put a remote controller cable through the hole of the rear case.

c. Fix the rear case by securing it with attached screws (2 places).

When attaching to the wall directly:

a. Seal the wiring hole of the remote controller cable.
b. Put a remote controller cable through the back hole of the rear case of the main body.

c. Fix the rear case by securing it with attached screws (2 places).

When routing the cable on-wall:

a. Cut off the cable guide of the front case with using a knife or a nipper.
b. Deburr the edge of the cable guide.

c. Fix the rear case by securing it with attached screws (2 places).

DESIGN & TECHNICAL MANUAL

- 182 -

MULTI TYPE

5, 6 ROOMS TYPE

Summary of Contents for agyg09lvca

Page 1: ...AP ARYG14LSLAP ARYG18LSLAP ARYG07LLTA ARYG09LLTA ARYG12LLTB ARYG14LLTB ARYG18LLTB ASYG07LMCA ASYG09LMCA ASYG12LMCA ASYG14LMCA ASYG07LMCE ASYG09LMCE ASYG12LMCE ASYG14LMCE ASYG07LUCA ASYG09LUCA ASYG12LUCA ASYG14LUCA ASYG18LFCA ASYG24LFCA ASYG24LFCC OUTDOOR ABYG14LVTA ABYG18LVTB AGYG09LVCA AGYG12LVCA AGYG14LVCA AOYG36LBLA5 AOYG45LBLA6 DR_MU006EF_03 2017 05 22 ...

Page 2: ...roduct specifications and design are subject to change without notice for future improvement For further details please check with our authorized dealer Copyright 2017 Fujitsu General Limited All rights reserved ...

Page 3: ... 30 3 5 Floor Ceiling type 38 3 6 Floor type 40 4 Wiring diagrams 41 4 1 Compact cassette type 41 4 2 Mini duct type 42 4 3 Slim duct type 43 4 4 Wall mounted type 44 4 5 Floor Ceiling type 47 4 6 Floor type 48 5 Air velocity and temperature distributions 49 5 1 Compact cassette type 49 5 2 Mini duct type 57 5 3 Slim duct type 67 5 4 Wall mounted type 77 5 5 Floor Ceiling type 85 5 6 Floor type 89...

Page 4: ...ller UTY LBTYM Optional part 167 13 5 Wired remote controller UTY RNNYM 170 13 6 Wired remote controller UTY RLRY 175 13 7 Wired remote controller UTY RVNYM Optional part 178 13 8 Wired remote controller UTY RNRYZ Optional part 187 13 9 Simple remote controller UTY RSNYM Optional part 190 13 10 Simple remote controller UTY RSRY and UTY RHRY Optional parts 195 14 Function settings 198 14 1 Compact ...

Page 5: ...5 5 Floor Ceiling type 261 15 6 Floor type 262 16 Optional parts 263 16 1 Controllers 263 16 2 Cassette grille 265 16 3 Others 266 17 Indoor unit installation precautions 270 17 1 Place where prohibited for use 270 17 2 Points to remember when installing 271 CONTENTS continued ...

Page 6: ...tion 320 8 1 Model AOYG36LBLA5 320 9 Airflow 321 9 1 Model AOYG36LBLA5 321 10 Operation noise sound pressure 322 10 1 Noise level curve 322 10 2 Sound level check point 322 11 Electrical characteristics 323 12 Safety devices 324 13 Function settings 325 13 1 Setting methods 325 13 2 Outdoor unit low noise operation function option 328 13 3 Changing the current limit function 328 14 Check and test ...

Page 7: ...tion 394 8 1 Model AOYG45LBLA6 394 9 Airflow 395 9 1 Model AOYG45LBLA6 395 10 Operation noise sound pressure 396 10 1 Noise level curve 396 10 2 Sound level check point 396 11 Electrical characteristics 397 12 Safety devices 398 13 Function settings 399 13 1 Setting methods 399 13 2 Outdoor unit low noise operation function option 402 13 3 Changing the current limit function 402 14 Check and test ...

Page 8: ......

Page 9: ...LSLAP ARYG18LSLAP SLIM DUCT TYPE ARYG07LLTA ARYG09LLTA ARYG12LLTB ARYG14LLTB ARYG18LLTB WALL MOUNTED TYPE ASYG07LUCA ASYG09LUCA ASYG12LUCA ASYG14LUCA ASYG07LMCA ASYG09LMCA ASYG12LMCA ASYG14LMCA ASYG07LMCE ASYG09LMCE ASYG12LMCE ASYG14LMCE ASYG18LFCA ASYG24LFCA ASYG24LFCC FLOOR CEILING TYPE ABYG14LVTA ABYG18LVTB FLOOR TYPE AGYG09LVCA AGYG12LVCA AGYG14LVCA ...

Page 10: ...P ARYG07LLTA ARYG09LLTA ARYG12LLTB ARYG14LLTB ARYG18LLTB ASYG07LMCA ASYG09LMCA ASYG12LMCA ASYG14LMCA ASYG07LMCE ASYG09LMCE ASYG12LMCE ASYG14LMCE ASYG07LUCA ASYG09LUCA ASYG12LUCA ASYG14LUCA ASYG18LFCA ASYG24LFCA ASYG24LFCC ABYG14LVTA ABYG18LVTB AGYG09LVCA AGYG12LVCA AGYG14LVCA Outdoor unit AOYG36LBLA5 AOYG45LBLA6 2 MULTI TYPE 5 6 ROOMS TYPE ...

Page 11: ...YG45LBLA6 Outdoor unit Slim duct Wall mounted ARYG07 09LLTA ARYG12 18LLTB LU LM ASYG07 14LMCA ASYG07 14LMCE ASYG07 14LUCA Btu class 07 09 12 14 18 07 09 12 14 kW class 2 0 2 5 3 5 4 0 5 0 2 0 2 5 3 5 4 0 AOYG36LBLA5 AOYG45LBLA6 Outdoor unit Wall mounted Floor Ceiling Floor LF ASYG18LFCA ASYG24LFCA ASYG24LFCC ABYG14LVTA ABYG18LVTB AGYG09 14LVCA Btu class 18 24 14 18 09 12 14 kW class 5 0 7 0 4 0 5 ...

Page 12: ... 45 37 9 18 24 51 38 12 12 12 36 39 12 12 14 38 40 12 12 18 42 41 12 12 24 48 42 12 14 14 40 43 12 14 18 44 44 12 14 24 50 45 12 18 18 48 46 12 18 24 54 47 14 14 14 42 48 14 14 18 46 49 14 14 24 52 50 14 18 18 50 51 18 18 18 54 52 7 7 7 7 28 53 7 7 7 9 30 54 7 7 7 12 33 55 7 7 7 14 35 56 7 7 7 18 39 57 7 7 7 24 45 58 7 7 9 9 32 59 7 7 9 12 35 60 7 7 9 14 37 61 7 7 9 18 41 62 7 7 9 24 47 63 7 7 12 ...

Page 13: ...7 18 46 119 7 7 7 7 24 52 120 7 7 7 9 9 39 121 7 7 7 9 12 42 122 7 7 7 9 14 44 123 7 7 7 9 18 48 124 7 7 7 9 24 54 125 7 7 7 12 12 45 126 7 7 7 12 14 47 127 7 7 7 12 18 51 128 7 7 7 14 14 49 129 7 7 7 14 18 53 130 7 7 9 9 9 41 131 7 7 9 9 12 44 132 7 7 9 9 14 46 133 7 7 9 9 18 50 134 7 7 9 12 12 47 135 7 7 9 12 14 49 136 7 7 9 12 18 53 137 7 7 9 14 14 51 138 7 7 12 12 12 50 139 7 7 12 12 14 52 140...

Page 14: ...6 40 14 14 24 52 41 14 18 18 50 42 14 18 24 56 43 14 24 24 62 44 18 18 18 54 45 18 18 24 60 46 7 7 7 14 35 47 7 7 7 18 39 48 7 7 7 24 45 49 7 7 9 12 35 50 7 7 9 14 37 51 7 7 9 18 41 52 7 7 9 24 47 53 7 7 12 12 38 54 7 7 12 14 40 55 7 7 12 18 44 56 7 7 12 24 50 57 7 7 14 14 42 58 7 7 14 18 46 59 7 7 14 24 52 60 7 7 18 18 50 61 7 7 18 24 56 62 7 7 24 24 62 63 7 9 9 9 34 64 7 9 9 12 37 65 7 9 9 14 39...

Page 15: ... 7 9 37 130 7 7 7 7 12 40 131 7 7 7 7 14 42 132 7 7 7 7 18 46 133 7 7 7 7 24 52 134 7 7 7 9 9 39 135 7 7 7 9 12 42 136 7 7 7 9 14 44 137 7 7 7 9 18 48 138 7 7 7 9 24 54 139 7 7 7 12 12 45 140 7 7 7 12 14 47 141 7 7 7 12 18 51 142 7 7 7 12 24 57 143 7 7 7 14 14 49 144 7 7 7 14 18 53 145 7 7 7 14 24 59 146 7 7 7 18 18 57 147 7 7 9 9 9 41 148 7 7 9 9 12 44 149 7 7 9 9 14 46 150 7 7 9 9 18 50 151 7 7 ...

Page 16: ... 14 49 218 7 7 7 7 7 18 53 219 7 7 7 7 7 24 59 220 7 7 7 7 9 9 46 221 7 7 7 7 9 12 49 222 7 7 7 7 9 14 51 223 7 7 7 7 9 18 55 224 7 7 7 7 9 24 61 225 7 7 7 7 12 12 52 226 7 7 7 7 12 14 54 227 7 7 7 7 12 18 58 228 7 7 7 7 14 14 56 229 7 7 7 7 14 18 60 230 7 7 7 9 9 9 48 231 7 7 7 9 9 12 51 232 7 7 7 9 9 14 53 233 7 7 7 9 9 18 57 234 7 7 7 9 12 12 54 235 7 7 7 9 12 14 56 236 7 7 7 9 12 18 60 237 7 7...

Page 17: ...Pipe type Copper tube Fin type Aluminum Dimensions H W D Net mm 245 570 570 Gross 265 730 625 Weight Net kg 15 Gross 18 Connection pipe Size Liquid mm in Ø6 35 Ø1 4 Gas Ø9 52 Ø3 8 Method Flare Operation range Cooling C 18 to 32 RH 80 or less Heating C 16 to 30 Drain hose Material Hard PVC Size mm Ø 25 I D Ø 32 O D Cassette grille Model name UTG UFYD W Material PS Color White Approximate color of M...

Page 18: ... Aluminum Dimensions H W D Net mm 245 570 570 Gross 265 730 625 Weight Net kg 15 Gross 18 Connection pipe Size Liquid mm in Ø6 35 Ø1 4 Gas Ø12 70 Ø1 2 Method Flare Operation range Cooling C 18 to 32 RH 80 or less Heating C 16 to 30 Drain hose Material Hard PVC Size mm Ø 25 I D Ø 32 O D Cassette grille Model name UTG UFYD W Material PS Color White Approximate color of Munsell N 9 25 Dimensions H W ...

Page 19: ...at exchanger type Dimensions H W D mm 336 490 26 6 Fin pitch mm 1 3 Rows Stages 2 16 Pipe type Copper tube Fin type Aluminum Enclosure Material Steel sheet Color Dimensions H W D Net mm 198 700 450 Gross 250 930 580 Weight Net kg 15 5 Gross 19 5 Connection pipe Size Liquid mm in Ø6 35 Ø1 4 Gas Ø9 52 Ø3 8 Method Flare Operation range Cooling C 18 to 32 RH 80 or less Heating C 16 to 30 Drain hose Ma...

Page 20: ... mm 1 3 Rows Stages 2 16 Pipe type Copper tube Fin type Aluminum Enclosure Material Steel sheet Color Dimensions H W D Net mm 198 700 450 198 900 450 Gross 250 930 580 250 1 130 580 Weight Net kg 15 5 18 5 Gross 19 5 23 0 Connection pipe Size Liquid mm in Ø6 35 Ø1 4 Gas Ø12 7 Ø1 2 Method Flare Operation range Cooling C 18 to 32 RH 80 or less Heating C 16 to 30 Drain hose Material Hard PVC Size mm ...

Page 21: ...294 500 26 6 294 500 39 9 Fin pitch mm 1 3 Rows Stages 2 14 3 14 Pipe type Copper tube Fin type Aluminum Enclosure Material Steel sheet Color Dimensions H W D Net mm 198 700 620 Gross 274 945 772 Weight Net kg 17 19 Gross 21 23 Connection pipe Size Liquid mm in Ø6 35 Ø1 4 Gas Ø9 52 Ø3 8 Method Flare Operation range Cooling C 18 to 32 RH 80 or less Heating C 16 to 30 Drain hose Material Hard PVC Si...

Page 22: ...3 14 Pipe type Copper tube Fin type Aluminum Enclosure Material Steel sheet Color Dimensions H W D Net mm 198 700 620 198 900 620 Gross 274 945 772 274 1 145 772 Weight Net kg 19 23 Gross 23 27 Connection pipe Size Liquid mm in Ø6 35 Ø1 4 Gas Ø12 70 Ø1 2 Method Flare Operation range Cooling C 18 to 32 RH 80 or less Heating C 16 to 30 Drain hose Material Hard PVC Size mm Ø 25 I D Ø 32 O D Remote co...

Page 23: ...nger type Dimensions H W D mm Main 320 690 20 Sub 84 690 13 3 Fin pitch mm Main 1 1 Sub 1 4 Rows Stages Main 2 20 Sub 1 4 Pipe type Copper tube Fin type Aluminum Enclosure Material Polystyrene Color White Approximate color of Munsell N 9 3 Dimensions H W D Net mm 282 870 185 Gross 247 920 373 Weight Net kg 9 5 Gross 12 Connection pipe Size Liquid mm in Ø6 35 Ø1 4 Gas Ø9 52 Ø3 8 Ø12 7 Ø1 2 Method F...

Page 24: ...ensions H W D mm Main 320 630 20 Sub 84 630 13 3 Fin pitch mm Main 1 1 Sub 1 4 Rows Stages Main 2 20 Sub 1 4 Pipe type Copper tube Fin type Aluminum Enclosure Material Polystyrene Color White Approximate color of Munsell N 9 25 Dimensions H W D Net mm 268 840 203 Gross 270 884 336 Weight Net kg 8 5 Gross 10 5 Connection pipe Size Liquid mm in Ø6 35 Ø1 4 Gas Ø9 52 Ø3 8 Ø12 7 Ø1 2 Method Flare Drain...

Page 25: ...ensions H W D mm Main 320 630 20 Sub 84 630 13 3 Fin pitch mm Main 1 1 Sub 1 4 Rows Stages Main 2 20 Sub 1 4 Pipe type Copper tube Fin type Aluminum Enclosure Material Polystyrene Color White Approximate color of Munsell N 9 25 Dimensions H W D Net mm 270 870 204 Gross 270 925 336 Weight Net kg 8 5 Gross 11 0 Connection pipe Size Liquid mm in Ø6 35 Ø1 4 Gas Ø9 52 Ø3 8 Ø12 7 Ø1 2 Method Flare Drain...

Page 26: ...4 Rows Stages Main 2 18 Sub 1 4 Main 2 18 Sub 1 4 1 4 Pipe type Copper tube Fin type Aluminum Enclosure Material Polystyrene Color White Approximate color of Munsell N 9 25 Dimensions H W D Net mm 320 998 238 Gross 329 1 090 420 Weight Net kg 14 Gross 18 Connection pipe Size Liquid mm in Ø6 35 Ø1 4 Gas Ø12 70 Ø1 2 Ø15 88 Ø5 8 Method Flare Drain hose Material PVC Size mm Ø12 I D Ø16 O D Operation r...

Page 27: ...er ceiling 36 Floor console 34 Under ceiling 37 Floor console QUIET 29 Under ceiling 32 Floor console 32 Under ceiling 35 Floor console Sound power level Cooling dB A 51 55 Heating 51 55 Heat exchanger type Dimensions H W D mm 252 800 26 6 252 800 39 9 Fin pitch mm 1 2 1 3 Rows Stages 2 12 3 12 Pipe type Copper tube Fin type Aluminum Enclosure Material ABS Color White Approximate color of Munsell ...

Page 28: ...e Dimensions H W D mm 378 550 26 6 Fin pitch mm 1 2 Rows Stages 2 18 Pipe type Copper tube Fin type Aluminum Enclosure Material Polystyrene Color White Approximate color of Munsell N 9 25 Dimensions H W D Net mm 600 740 200 Gross 700 820 310 Weight Net kg 14 Gross 17 Connection pipe Size Liquid mm in Ø6 35 Ø1 4 Gas Ø9 52 Ø3 8 Ø12 70 Ø1 2 Method Flare Drain hose Material PVC Size mm Ø13 8 I D Ø16 7...

Page 29: ...g bolt position 570 Indoor unit 580 to 660 Ceiling openings Cassette grille mounting state Top view 150 to 200 Min 450 Min 450 Service access Side view 215 123 58 114 146 108 102 245 30 40 99 Drain port Control box Ceiling Drain port Be sure to leave service access for future service at the designated position Bottom view 30 49 Side view Unit mm 21 MULTI TYPE 5 6 ROOMS TYPE ...

Page 30: ...ection setting 100 or more Unit mm NOTES When installing the indoor unit be careful about the maintenance space To set 3 direction optional Air outlet shutter plate UTR YDZB must be installed and the outlet direction need to be switched to 3 way by remote controller The ceiling height cannot be set in the 3 way outlet mode Therefore ceiling height setting change by function setting 20 is prohibite...

Page 31: ...LSLAP and ARYG14LSLAP Drain port 575 174 752 650 43 33 665 700 650 49 49 92 78 169 56 66 85 P 100 6 600 A 295 198 168 150 78 57 10 30 150 182 193 450 30 153 72 52 Rear view Top view Front view Bottom view Side view View A Unit mm 23 MULTI TYPE 5 6 ROOMS TYPE ...

Page 32: ...rt A Unit mm Rear view View A Top view Side view Front view Bottom view 775 174 153 72 52 295 30 49 85 952 850 P 100 8 800 49 92 78 169 56 66 10 30 150 182 193 450 850 43 33 864 900 198 168 150 78 57 24 MULTI TYPE 5 6 ROOMS TYPE ...

Page 33: ...o ceiling Floor 225 or more 5 or more 20 or more 300 or more Air When intaking air from bottom 100 or more Air Maintenance space requirement For future maintenance and service access provide sufficient maintenance space NOTE Do not place any wiring or illumination in the maintenance space as they will impede service Unit mm Top view Service access Air Air Control box 400 or more 100 or more 300 or...

Page 34: ...LLTB and ARYG14LLTB Rear view View A Top view Side view Front view Bottom view Drain port 51 574 174 71 152 100 x 6 600 82 48 650 734 30 377 167 119 89 78 55 47 10 620 371 264 144 69 650 664 700 43 20 198 168 151 78 55 Unit mm 26 MULTI TYPE 5 6 ROOMS TYPE ...

Page 35: ...w View A Top view Side view Front view Bottom view Drain port 51 774 174 71 152 87 56 850 934 100 x 8 800 30 377 167 119 89 78 55 47 10 620 371 264 144 69 850 864 900 43 20 198 168 151 78 55 Unit mm 27 MULTI TYPE 5 6 ROOMS TYPE ...

Page 36: ...re 20 or more 20 or more 300 or more Unit mm In wall concealed installations 10 or less 10 or less Left side Strong and durable floor Right side PIPE side Grille Inlet air Strong and durable floor 150 or more 150 or more 300 or more 100 or more 20 or more 20 or more Unit mm Left side Strong and durable floor Right side PIPE side Duct Grille Inlet air Strong and durable floor 150 or more 150 or mor...

Page 37: ...ice access provide sufficient maintenance space NOTE Do not place any wiring or illumination in the maintenance space as they will impede service Service access Unit mm Unit Control box Service space 300 or more 300 or more 100 or more 29 MULTI TYPE 5 6 ROOMS TYPE ...

Page 38: ...pe Models ASYG07LMCA ASYG09LMCA ASYG12LMCA and ASYG14LMCA Unit mm 268 268 34 216 209 74 840 203 840 410 310 430 165 144 178 233 321 315 295 Outline of unit 65 for pipe inlet 65 for pipe inlet 30 MULTI TYPE 5 6 ROOMS TYPE ...

Page 39: ... Installation space Unit mm 45 or more 1 800 or more 63 or more Outline of unit 25 or more 52 or more 130 or more 1 500 or more 70 or more 31 MULTI TYPE 5 6 ROOMS TYPE ...

Page 40: ...ASYG07LMCE ASYG09LMCE ASYG12LMCE and ASYG14LMCE Unit mm 270 270 34 218 209 74 870 204 870 426 310 444 165 144 178 233 321 315 295 Outline of unit 65 for pipe inlet 65 for pipe inlet 32 MULTI TYPE 5 6 ROOMS TYPE ...

Page 41: ...ce requirement Provide sufficient installation space for product safety Unit mm 45 or more 1 800 or more 63 or more Outline of unit 25 or more 52 or more 144 or more 1 500 or more 86 or more 33 MULTI TYPE 5 6 ROOMS TYPE ...

Page 42: ... Models ASYG07LUCA ASYG09LUCA ASYG12LUCA and ASYG14LUCA Unit mm 282 870 185 187 Installed state Outline of Unit Ø65 for pipe inlet Ø65 for pipe inlet 34 MULTI TYPE 5 6 ROOMS TYPE ...

Page 43: ... Installation space Unit mm 50 or more Outline of unit 160 or more 1 500 or more 1 800 or more 337 247 55 50 or more 160 or more 100 or more 120 or more 35 MULTI TYPE 5 6 ROOMS TYPE ...

Page 44: ... Models ASYG18LFCA ASYG24LFCA and ASYG24LFCC 998 238 320 998 Outline of unit 471 67 28 46 438 61 102 397 432 56 56 10 320 ø 8 0 ø 8 0 17 Unit mm 36 MULTI TYPE 5 6 ROOMS TYPE ...

Page 45: ...on space Provide sufficient installation space for product safety 63 or more 80 or more 53 or more 52 or more 80 or more Outline of unit 120 or more 1 500 or more 1 800 or more Unit mm 37 MULTI TYPE 5 6 ROOMS TYPE ...

Page 46: ...iew 100 hole 50 hole 125 100 655 530 45 65 500 245 990 65 Wall bracket Side of unit Unit mm 500 900 990 100 28 47 100 124 100 100 175 200 530 655 43 13 100 124 742 56 72 67 63 27 98 199 162 100 190 145 20 ø45 mm hole Use M10 screw bolt Hole for lifting bolt 38 MULTI TYPE 5 6 ROOMS TYPE ...

Page 47: ...allation space Left Right 300 or more 300 or more Ceiling Left Indoor unit Right 150 or more 300 or more Ceiling 20 or more 1 000 or more 2 300 or more Obstruction Floor Unit mm 39 MULTI TYPE 5 6 ROOMS TYPE ...

Page 48: ...e Models AGYG09LVCA AGYG12LVCA and AGYG14LVCA 600 200 Side view Front view 740 Unit mm Installation space 80 or more 50 or more 80 or more 100 or more 100 or below from the floor Unit mm 40 MULTI TYPE 5 6 ROOMS TYPE ...

Page 49: ...4 Wiring diagrams 4 1 Compact cassette type Models AUYG07LVLA AUYG09LVLA AUYG12LVLB AUYG14LVLB and AUYG18LVLB 41 MULTI TYPE 5 6 ROOMS TYPE ...

Page 50: ...4 2 Mini duct type Models ARYG07LSLAP ARYG09LSLAP ARYG12LSLAP ARYG14LSLAP and ARYG18LSLAP WLAN adapter Converter etc Option 42 MULTI TYPE 5 6 ROOMS TYPE ...

Page 51: ...5 1 2 3 4 5 6 1 2 3 4 5 6 CN104 CN101 1 2 3 4 5 6 7 8 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 1 2 4 5 6 7 8 GRAY GRAY GRAY GRAY GRAY GRAY GRAY GRAY GRAY GRAY GRAY CN4 CN1 1 2 3 4 5 6 7 8 1 2 3 1 2 3 1 2 3 4 5 6 7 8 CN10 CN103 CN3 CN13 CN14 CN6 BROWN RED RED RED YELLOW WHITE WHITE WHITE CN11 1 2 3 CN9 1 2 3 CN12 1 2 3 4 5 1 2 3 4 5 1 2 3 1 2 1 2 3 1 2 3 4 5 6 1 2 3 4 5 6 7 TERMINAL 1 2 3 M PRINTED CIRCUI...

Page 52: ...4 4 Wall mounted type Models ASYG07LUCA ASYG09LUCA ASYG12LUCA and ASYG14LUCA 44 MULTI TYPE 5 6 ROOMS TYPE ...

Page 53: ... Models ASYG07LMCA ASYG09LMCA ASYG12LMCA ASYG14LMCA ASYG07LMCE ASYG09LMCE ASYG12LMCE and ASYG14LMCE 45 MULTI TYPE 5 6 ROOMS TYPE ...

Page 54: ... Models ASYG18LFCA ASYG24LFCA and ASYG24LFCC 46 MULTI TYPE 5 6 ROOMS TYPE ...

Page 55: ...4 5 Floor Ceiling type Models ABYG14LVTA and ABYG18LVTB 47 MULTI TYPE 5 6 ROOMS TYPE ...

Page 56: ...4 6 Floor type Models AGYG09LVCA AGYG12LVCA and AGYG14LVCA 48 MULTI TYPE 5 6 ROOMS TYPE ...

Page 57: ...itions Fan speed Operation mode HIGH FAN Top view Vertical airflow direction louver up 2 0 2 0 2 0 2 0 1 0 1 0 1 0 1 0 0 5 0 5 0 5 0 5 0 25 0 25 0 25 0 25 Unit m s 4 3 2 1 0 1 2 3 4 4 3 2 1 0 1 2 3 4 m m Side view Vertical airflow direction louver up 2 0 1 0 0 5 0 5 0 25 0 25 4 3 2 1 0 1 2 3 4 m 0 1 2 2 7 m Unit m s 49 MULTI TYPE 5 6 ROOMS TYPE ...

Page 58: ... down 2 0 2 0 1 5 1 5 1 0 1 0 0 5 0 5 0 25 0 25 4 3 2 1 0 1 2 3 4 m 0 1 2 2 7 m 2 5 Unit m s Air temperature distribution Measuring conditions NOTE Reference data Fan speed Operation mode Outlet directions HIGH HEAT 4 way air outlet Side view Vertical airflow direction louver down 30 30 28 28 26 26 24 24 22 22 4 3 2 1 0 1 2 3 4 m 0 1 2 2 7 m 2 5 Unit C 50 MULTI TYPE 5 6 ROOMS TYPE ...

Page 59: ...p view Vertical airflow direction louver up 2 0 2 0 2 0 2 0 1 0 1 0 1 0 1 0 0 5 0 5 0 5 0 5 0 25 0 25 0 25 0 25 4 3 2 1 0 1 2 3 4 m Unit m s 4 3 2 1 0 1 2 3 4 m Side view Vertical airflow direction louver up 2 0 1 0 0 5 0 5 0 25 0 25 4 3 2 1 0 1 2 3 4 m 0 1 2 2 7 m Unit m s 51 MULTI TYPE 5 6 ROOMS TYPE ...

Page 60: ...uver down 1 5 1 5 1 0 1 0 0 5 0 5 0 25 0 25 0 1 2 2 7 m 2 5 4 3 2 1 0 1 2 3 4 m Unit m s Air temperature distribution Measuring conditions NOTE Reference data Fan speed Operation mode Outlet directions HIGH HEAT 4 way air outlet Side view Vertical airflow direction louver down 30 30 28 28 26 26 24 24 22 22 0 1 2 2 7 m 2 5 4 3 2 1 0 1 2 3 4 m Unit C 52 MULTI TYPE 5 6 ROOMS TYPE ...

Page 61: ...H FAN Top view Vertical airflow direction louver up 1 0 5 0 5 1 2 0 25 0 25 1 0 25 2 0 25 0 5 2 0 5 1 2 4 3 2 1 0 1 2 3 4 m Unit m s 4 3 2 1 0 1 2 3 4 m Side view Vertical airflow direction louver up 0 25 0 25 0 5 0 5 1 1 2 2 4 3 2 1 0 1 2 3 4 m 0 1 2 2 7 m Unit m s 53 MULTI TYPE 5 6 ROOMS TYPE ...

Page 62: ...w direction louver down 0 25 0 5 1 0 1 5 2 0 0 1 2 2 7 m 2 5 4 3 2 1 0 1 2 3 4 m Unit m s Air temperature distribution Measuring conditions NOTE Reference data Fan speed Operation mode Outlet directions HIGH HEAT 4 way air outlet Side view Vertical airflow direction louver down 22 24 26 28 30 0 1 2 2 7 m 2 5 4 3 2 1 0 1 2 3 4 m Unit C 54 MULTI TYPE 5 6 ROOMS TYPE ...

Page 63: ...p view Vertical airflow direction louver up 4 3 2 1 0 1 2 3 4 m Unit m s 4 3 2 1 0 1 2 3 4 m 2 0 2 0 2 0 2 0 1 0 1 0 1 0 1 0 0 5 0 5 0 5 0 5 0 25 0 25 0 25 0 25 Side view Vertical airflow direction louver up 4 3 2 1 0 1 2 3 4 m 0 1 2 2 7 m Unit m s 2 0 1 0 0 5 0 5 0 25 0 25 55 MULTI TYPE 5 6 ROOMS TYPE ...

Page 64: ...r down 0 1 2 2 7 m 2 5 4 3 2 1 0 1 2 3 4 m Unit m s 1 5 1 5 1 0 1 0 0 5 0 5 0 25 0 25 2 0 2 0 Air temperature distribution Measuring conditions NOTE Reference data Fan speed Operation mode Outlet directions HIGH HEAT 4 way air outlet Side view Vertical airflow direction louver down 0 1 2 2 7 m 2 5 4 3 2 1 0 1 2 3 4 Unit C 30 30 28 28 26 26 24 24 22 22 56 MULTI TYPE 5 6 ROOMS TYPE ...

Page 65: ...p Horizontal airflow direction louver Center 2 1 0 1 2 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 1 0 5 Top view Vertical airflow direction louver Up Horizontal airflow direction louver Left Right 2 1 0 1 2 m m Unit m s 0 1 2 3 4 5 6 7 5 4 3 8 9 10 5 4 3 2 1 0 5 2 1 0 5 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 2 1 0 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 ...

Page 66: ...ow direction louver Center 2 1 0 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 5 3 2 1 0 5 Air temperature distribution Measuring conditions Fan speed Operation mode HIGH HEAT Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 2 1 0 m Unit C m 0 1 2 3 4 5 6 7 8 9 2 5 3 10 30 28 26 24 22 58 MULTI TYPE 5 6 ROOMS TYPE ...

Page 67: ...tal airflow direction louver Center 2 1 0 1 2 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 1 0 5 Top view Vertical airflow direction louver Up Horizontal airflow direction louver Left Right 2 1 0 1 2 m m Unit m s 0 1 2 3 4 5 6 7 5 4 3 8 9 10 5 4 3 2 1 0 5 2 1 0 5 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 2 1 0 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 5 3 1 0 5...

Page 68: ...ow direction louver Center 2 1 0 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 5 3 2 1 0 5 Air temperature distribution Measuring conditions Fan speed Operation mode HIGH HEAT Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 2 1 0 m Unit C m 0 1 2 3 4 5 6 7 8 9 2 5 3 10 30 28 26 24 22 60 MULTI TYPE 5 6 ROOMS TYPE ...

Page 69: ...tal airflow direction louver Center 2 1 0 1 2 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 1 0 5 Top view Vertical airflow direction louver Up Horizontal airflow direction louver Left Right 2 1 0 1 2 m m Unit m s 0 1 2 3 4 5 6 7 5 4 3 8 9 10 5 4 3 2 1 0 5 2 1 0 5 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 2 1 0 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 5 3 1 0 5...

Page 70: ...ow direction louver Center 2 1 0 m m 0 1 2 3 4 5 6 7 8 9 10 2 5 3 2 1 0 5 Unit m s Air temperature distribution Measuring conditions Fan speed Operation mode HIGH HEAT Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 2 1 0 m Unit C m 0 1 2 3 4 5 6 7 8 9 2 5 3 10 30 28 26 24 22 62 MULTI TYPE 5 6 ROOMS TYPE ...

Page 71: ...tal airflow direction louver Center 2 1 0 1 2 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 1 0 5 Top view Vertical airflow direction louver Up Horizontal airflow direction louver Left Right 2 1 0 1 2 m m Unit m s 0 1 2 3 4 5 6 7 5 4 3 8 9 10 5 4 3 2 1 0 5 2 1 0 5 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 2 1 0 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 5 3 1 0 5...

Page 72: ...ow direction louver Center 2 1 0 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 5 3 2 1 0 5 Air temperature distribution Measuring conditions Fan speed Operation mode HIGH HEAT Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 2 1 0 m Unit C m 0 1 2 3 4 5 6 7 8 9 2 5 3 10 30 28 26 24 22 64 MULTI TYPE 5 6 ROOMS TYPE ...

Page 73: ...tal airflow direction louver Center 2 1 0 1 2 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 1 0 5 Top view Vertical airflow direction louver Up Horizontal airflow direction louver Left Right 2 1 0 1 2 m m Unit m s 0 1 2 3 4 5 6 7 5 4 3 8 9 10 5 4 3 2 1 0 5 2 1 0 5 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 2 1 0 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 5 3 1 0 5...

Page 74: ...ow direction louver Center 2 1 0 m m 0 1 2 3 4 5 6 7 8 9 10 2 5 3 Unit m s 2 1 0 5 Air temperature distribution Measuring conditions Fan speed Operation mode HIGH HEAT Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 2 1 0 m Unit C m 0 1 2 3 4 5 6 7 8 9 2 5 3 10 30 28 26 24 22 66 MULTI TYPE 5 6 ROOMS TYPE ...

Page 75: ... Horizontal airflow direction louver Center 2 1 0 1 2 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 1 0 5 Top view Vertical airflow direction louver Up Horizontal airflow direction louver Left Right 2 1 0 1 2 m m Unit m s 0 1 2 3 4 5 6 7 5 4 3 8 9 10 5 4 3 2 1 0 5 2 1 0 5 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 2 1 0 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 5...

Page 76: ...ow direction louver Center 2 1 0 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 5 3 2 1 0 5 Air temperature distribution Measuring conditions Fan speed Operation mode HIGH HEAT Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 2 1 0 m Unit C m 0 1 2 3 4 5 6 7 8 9 2 5 3 10 30 28 26 24 22 68 MULTI TYPE 5 6 ROOMS TYPE ...

Page 77: ...al airflow direction louver Center 2 1 0 1 2 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 1 0 5 Top view Vertical airflow direction louver Up Horizontal airflow direction louver Left Right 2 1 0 1 2 m m Unit m s 0 1 2 3 4 5 6 7 5 4 3 8 9 10 5 4 3 2 1 0 5 2 1 0 5 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 2 1 0 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 5 3 1 0 5 ...

Page 78: ...ow direction louver Center 2 1 0 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 5 3 2 1 0 5 Air temperature distribution Measuring conditions Fan speed Operation mode HIGH HEAT Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 2 1 0 m Unit C m 0 1 2 3 4 5 6 7 8 9 2 5 3 10 30 28 26 24 22 70 MULTI TYPE 5 6 ROOMS TYPE ...

Page 79: ...al airflow direction louver Center 2 1 0 1 2 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 1 0 5 Top view Vertical airflow direction louver Up Horizontal airflow direction louver Left Right 2 1 0 1 2 m m Unit m s 0 1 2 3 4 5 6 7 5 4 3 8 9 10 5 4 3 2 1 0 5 2 1 0 5 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 2 1 0 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 5 3 1 0 5 ...

Page 80: ...ow direction louver Center 2 1 0 m m 0 1 2 3 4 5 6 7 8 9 10 2 5 3 2 1 0 5 Unit m s Air temperature distribution Measuring conditions Fan speed Operation mode HIGH HEAT Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 2 1 0 m Unit C m 0 1 2 3 4 5 6 7 8 9 2 5 3 10 30 28 26 24 22 72 MULTI TYPE 5 6 ROOMS TYPE ...

Page 81: ...al airflow direction louver Center 2 1 0 1 2 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 1 0 5 Top view Vertical airflow direction louver Up Horizontal airflow direction louver Left Right 2 1 0 1 2 m m Unit m s 0 1 2 3 4 5 6 7 5 4 3 8 9 10 5 4 3 2 1 0 5 2 1 0 5 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 2 1 0 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 5 3 1 0 5 ...

Page 82: ...ow direction louver Center 2 1 0 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 5 3 2 1 0 5 Air temperature distribution Measuring conditions Fan speed Operation mode HIGH HEAT Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 2 1 0 m Unit C m 0 1 2 3 4 5 6 7 8 9 2 5 3 10 30 28 26 24 22 74 MULTI TYPE 5 6 ROOMS TYPE ...

Page 83: ...al airflow direction louver Center 2 1 0 1 2 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 1 0 5 Top view Vertical airflow direction louver Up Horizontal airflow direction louver Left Right 2 1 0 1 2 m m Unit m s 0 1 2 3 4 5 6 7 5 4 3 8 9 10 5 4 3 2 1 0 5 2 1 0 5 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 2 1 0 m Unit m s m 0 1 2 3 4 5 6 7 8 9 10 2 5 3 1 0 5 ...

Page 84: ...ow direction louver Center 2 1 0 m m 0 1 2 3 4 5 6 7 8 9 10 2 5 3 Unit m s 2 1 0 5 Air temperature distribution Measuring conditions Fan speed Operation mode HIGH HEAT Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 2 1 0 m Unit C m 0 1 2 3 4 5 6 7 8 9 2 5 3 10 30 28 26 24 22 76 MULTI TYPE 5 6 ROOMS TYPE ...

Page 85: ...irflow direction louver Up Horizontal airflow direction louver Left Right Unit m s m 0 1 2 3 4 5 6 7 8 m 0 1 1 2 2 3 3 0 75 0 5 0 25 0 75 1 0 1 0 0 5 0 25 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 3 2 1 0 Unit m s m m 0 1 2 3 4 5 6 7 8 0 75 1 0 0 5 0 25 Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 3 2 1 ...

Page 86: ...ction louver Up Horizontal airflow direction louver Left Right Unit m s m 0 1 2 3 4 5 6 7 8 m 0 1 1 2 2 3 3 0 75 0 5 0 25 0 75 1 0 1 0 0 5 0 25 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 3 2 1 0 Unit m s m m 0 1 2 3 4 5 6 7 8 0 75 1 0 0 5 0 25 Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 3 2 1 0 Unit m s ...

Page 87: ...ow direction louver Up Horizontal airflow direction louver Left Right Unit m s m 0 1 2 3 4 5 6 7 8 9 m 0 1 1 2 2 3 3 2 0 2 0 1 0 1 0 0 5 0 5 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center Unit m s 3 2 1 0 m m 0 1 2 3 4 5 6 7 8 9 2 0 1 0 0 5 Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center Unit m s 0 5 2 0 1 0 3 2...

Page 88: ...ow direction louver Up Horizontal airflow direction louver Left Right Unit m s m 0 1 2 3 4 5 6 7 8 9 m 0 1 1 2 2 3 3 2 0 2 0 1 0 1 0 0 5 0 5 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center Unit m s 3 2 1 0 m m 0 1 2 3 4 5 6 7 8 9 2 0 1 0 0 5 Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center Unit m s 3 2 1 0 m m 0 1...

Page 89: ...ow direction louver Up Horizontal airflow direction louver Left Right Unit m s m 0 1 2 3 4 5 6 7 8 9 m 0 1 1 2 2 3 3 2 0 2 0 1 0 1 0 0 5 0 5 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center Unit m s 3 2 1 0 m m 0 1 2 3 4 5 6 7 8 9 2 0 1 0 0 5 Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center Unit m s 3 2 1 0 m m 0 1...

Page 90: ...ow direction louver Up Horizontal airflow direction louver Left Right 1 0 1 0 0 5 0 5 2 0 2 0 Unit m s m 0 1 2 3 4 5 6 7 8 9 m 0 1 1 2 2 3 3 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 2 0 1 0 0 5 Unit m s 3 2 1 0 m m 0 1 2 3 4 5 6 7 8 9 Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 2 0 1 0 0 5 Unit m s 3 2...

Page 91: ...ection louver Up Horizontal airflow direction louver Left Right 2 0 2 0 1 0 1 0 0 5 0 5 Unit m s m 0 1 2 3 4 5 6 7 8 m 0 1 1 2 2 3 3 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 3 2 1 0 Unit m s m m 0 1 2 3 4 5 6 7 8 2 0 1 0 0 5 Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 2 0 1 0 0 5 3 2 1 0 Unit m s m m 0...

Page 92: ...low direction louver Up Horizontal airflow direction louver Left Right 2 0 2 0 1 0 1 0 0 5 0 5 Unit m s m 0 1 2 3 4 5 6 7 8 m 0 1 1 2 2 3 3 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 2 0 1 0 0 5 Unit m s m 0 1 2 3 4 5 6 7 8 m 0 1 2 3 Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 2 0 1 0 0 5 Unit m s m 0 1 ...

Page 93: ...0 25 0 5 0 5 1 0 1 0 2 0 2 0 10 m 0 1 2 3 4 5 6 7 8 9 Unit m s m 0 1 1 2 2 3 4 5 3 4 5 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 0 25 0 5 1 0 2 0 10 m 0 1 2 3 4 5 6 7 8 9 m 3 1 2 Unit m s Side view Vertical airflow direction louver Center Horizontal airflow direction louver Center 0 25 0 5 1 0 2 0 10 m 0 1 2 3 4 5 6 7 8 9 m 3 1 2 Unit m s Side view V...

Page 94: ... 5 1 0 1 0 2 0 2 0 10 m 0 1 2 3 4 5 6 7 8 9 Unit m s m 0 1 1 2 2 3 4 5 3 4 5 Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 0 25 0 5 1 0 2 0 10 m 0 1 2 3 4 5 6 7 8 9 m 3 1 2 Unit m s Side view Vertical airflow direction louver Center Horizontal airflow direction louver Center 0 25 0 5 1 0 2 0 Unit m s m 0 1 2 3 4 5 6 7 m 3 4 1 2 Side view Vertical airfl...

Page 95: ... 6 7 8 9 Unit m s m 0 1 1 2 2 3 4 5 3 4 5 0 25 0 25 0 5 0 5 1 0 1 0 2 0 2 0 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 10 m 0 1 2 3 4 5 6 7 8 9 m 3 1 2 Unit m s 0 25 0 5 1 0 2 0 Side view Vertical airflow direction louver Center Horizontal airflow direction louver Center 0 25 0 5 1 0 2 0 10 m 0 1 2 3 4 5 6 7 8 9 m 3 1 2 Unit m s Side view Vertical air...

Page 96: ... 5 1 0 1 0 2 0 2 0 10 m 0 1 2 3 4 5 6 7 8 9 Unit m s m 0 1 1 2 2 3 4 5 3 4 5 Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 0 25 0 5 1 0 2 0 10 m 0 1 2 3 4 5 6 7 8 9 m 3 1 2 Unit m s Side view Vertical airflow direction louver Center Horizontal airflow direction louver Center Unit m s m 0 1 2 3 4 5 6 7 m 3 4 1 2 0 25 0 5 1 0 2 0 Side view Vertical airfl...

Page 97: ...1 0 1 2 m m 1 2 3 4 Unit m s Top view Vertical airflow direction louver Up Horizontal airflow direction louver Left Right 1 0 0 5 1 0 0 5 Unit m s 2 1 0 1 2 m m 1 2 3 4 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 1 0 0 5 3 2 1 0 Unit m s m m 1 2 3 4 Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 1 0 0 5 3 2 ...

Page 98: ...imit Normal SP upper limit Quiet Normal SP Hi Normal SP Hi SP mode 00 SP mode 00 upper limit 60 50 40 30 20 10 0 300 External static pressure Pa Airflow m3 h 400 500 600 700 1 Available airflow rate range when Auto louver grille option is installed Fan speed HIGH Vertical airflow direction louver Up Available airflow rate range High level 1 Hi SP mode 00 Hi Normal SP Hi SP mode 02 Hi SP mode 03 90...

Page 99: ...air volume and capacity Cooling 300 400 500 700 600 Airflow m3 h 0 20 40 60 80 100 140 120 Capacity Capacity Heating 0 20 40 60 80 100 120 140 300 400 500 700 600 Capacity Airflow m3 h Capacity 91 MULTI TYPE 5 6 ROOMS TYPE ...

Page 100: ...er limit Quiet Normal SP Hi Normal SP Hi SP mode 00 SP mode 00 upper limit 1 Available airflow rate range when Auto louver grille option is installed Fan speed HIGH Vertical airflow direction louver Up 60 50 40 30 20 10 0 300 External static pressure Pa Airflow m3 h 400 500 600 700 Available airflow rate range High level 1 Hi SP mode 00 Hi Normal SP Hi SP mode 02 Hi SP mode 03 92 MULTI TYPE 5 6 RO...

Page 101: ...air volume and capacity Cooling 300 400 500 700 600 Airflow m3 h 0 20 40 60 80 100 140 120 Capacity Capacity Heating 0 20 40 60 80 100 120 140 300 400 500 700 600 Capacity Airflow m3 h Capacity 93 MULTI TYPE 5 6 ROOMS TYPE ...

Page 102: ...l SP Quiet Normal SP Quiet SP mode 00 SP mode 00 upper limit Hi SP mode 00 60 50 40 30 20 10 0 300 400 500 600 800 External static pressure Pa Airflow m3 h Available airflow rate range High level 1 700 1 Available airflow rate range when Auto louver grille option is installed Fan speed HIGH Vertical airflow direction louver Up Hi SP mode 03 Hi Normal SP Hi SP mode 02 Hi SP mode 00 94 MULTI TYPE 5 ...

Page 103: ...volume and capacity Cooling Capacity 800 500 400 700 600 Airflow m3 h 300 0 20 40 60 80 100 140 Capacity 120 Heating 300 500 600 800 700 Airflow m3 h 400 0 20 40 60 80 100 120 Capacity 140 Capacity 95 MULTI TYPE 5 6 ROOMS TYPE ...

Page 104: ... limit Quiet Nomal SP Hi SP mode 00 Quiet SP mode 00 80 70 60 50 40 30 20 10 0 External static pressure Pa 300 400 500 600 700 Airflow m3 h 800 900 1 Available airflow rate range when Auto louver grille option is installed Fan speed HIGH Vertical airflow direction louver Up Hi SP mode 01 Hi SP mode 05 Hi SP mode 04 Hi SP mode 03 Hi Normal SP Hi SP mode 02 Hi SP mode 00 Available airflow rate range...

Page 105: ...me and capacity Cooling 0 20 40 60 80 100 120 Capacity 140 500 600 700 900 800 Airflow m3 h 400 300 Capacity Heating 0 20 40 60 80 100 120 Capacity 140 500 600 700 900 800 Airflow m3 h 400 300 Capacity 97 MULTI TYPE 5 6 ROOMS TYPE ...

Page 106: ...mode 05 lower limit Quiet SP mode 05 Quiet SP mode 00 1 Available airflow rate range when Auto louver grille option is installed Fan speed HIGH Vertical airflow direction louver Up 80 70 60 50 40 30 20 10 0 External static pressure Pa 700 Airflow m3 h 900 1 000 1 100 800 600 500 400 300 Available airflow rate range High level 1 Hi SP mode 05 Hi SP mode 04 Hi SP mode 03 Hi Normal SP Hi SP mode 02 H...

Page 107: ...ity Cooling 0 20 40 60 80 100 120 Capacity 140 Airflow m3 h 700 900 1 000 1 100 800 300 400 500 600 Capacity Heating 0 20 40 60 80 100 120 Capacity 140 Airflow m3 h 700 900 1 000 1 100 800 300 400 500 600 Capacity 99 MULTI TYPE 5 6 ROOMS TYPE ...

Page 108: ...r limit Hi SP mode 00 Normal SP lower limited 110 100 90 80 70 60 50 40 30 20 10 0 300 External static pressure Pa Airflow m3 h 400 500 600 700 1 Available airflow rate range when Auto louver grille option is installed Fan speed HIGH Vertical airflow direction louver Up Hi SP mode 09 Hi SP mode 08 Hi SP mode 07 Hi SP mode 06 Hi SP mode 05 Hi SP mode 04 Hi SP mode 03 Hi Normal SP Hi SP mode 02 Hi S...

Page 109: ...of air volume and capacity Cooling 0 20 40 60 80 100 120 400 500 600 800 700 Capacity Capacity Airflow m3 h Heating 0 20 40 60 80 100 120 400 500 600 800 700 Capacity Capacity Airflow m3 h 101 MULTI TYPE 5 6 ROOMS TYPE ...

Page 110: ...w m3 h 800 Hi SP mode00 1 110 100 90 80 70 60 50 40 30 20 10 0 300 External static pressure Pa Airflow m3 h Hi SP mode 09 Hi SP mode 08 Hi SP mode 07 Hi SP mode 06 Hi SP mode 05 Hi SP mode 04 Hi SP mode 03 Hi Normal SP Hi SP mode 02 Hi SP mode 01 Hi SP mode 00 Available airflow rate range High level 1 400 500 600 800 700 1 Available airflow rate range when Auto louver grille option is installed Fa...

Page 111: ...of air volume and capacity Cooling 0 20 40 60 80 100 120 400 500 600 800 700 Capacity Capacity Airflow m3 h Heating 0 20 40 60 80 100 120 400 500 600 800 700 Capacity Capacity Airflow m3 h 103 MULTI TYPE 5 6 ROOMS TYPE ...

Page 112: ...w m3 h 800 Hi SP mode 00 110 100 90 80 70 60 50 40 30 20 10 0 300 400 500 600 800 External static pressure Pa Airflow m3 h Hi SP mode 09 Hi SP mode 08 Hi SP mode 07 Hi SP mode 06 Hi SP mode 05 Hi SP mode 04 Hi SP mode 03 Hi Normal SP Hi SP mode 02 Hi SP mode 01 Hi SP mode 00 Available airflow rate range High level 1 700 1 Available airflow rate range when Auto louver grille option is installed Fan...

Page 113: ...of air volume and capacity Cooling 0 20 40 60 80 100 120 900 500 600 800 700 Capacity Capacity Airflow m3 h Heating 900 0 20 40 60 80 100 120 500 600 800 700 Capacity Capacity Airflow m3 h 105 MULTI TYPE 5 6 ROOMS TYPE ...

Page 114: ... 000 Quiet Nomal SP 120 110 100 90 80 70 60 50 40 30 20 10 0 300 400 500 600 700 External static pressure Pa Airflow m3 h 800 900 1 000 120 1 Available airflow rate range when Auto louver grille option is installed Fan speed HIGH Vertical airflow direction louver Up Hi SP mode 09 Hi SP mode 08 Hi SP mode 07 Hi SP mode 06 Hi SP mode 05 Hi SP mode 04 Hi SP mode 03 Hi Normal SP Hi SP mode 02 Hi SP mo...

Page 115: ... air volume and capacity Cooling 0 20 40 60 80 100 120 1 000 600 700 900 800 Capacity Capacity Airflow m3 h Heating 0 20 40 60 80 100 120 1 000 600 700 900 800 Capacity Capacity Airflow m3 h 107 MULTI TYPE 5 6 ROOMS TYPE ...

Page 116: ... 000 1 100 1 200 800 600 110 100 90 80 70 60 50 40 30 20 10 0 External static pressure Pa Airflow m3 h Hi SP mode 09 Hi SP mode 08 Hi SP mode 07 Hi SP mode 06 Hi SP mode 05 Hi SP mode 04 Hi SP mode 03 Hi Normal SP Hi SP mode 02 Hi SP mode 01 Hi SP mode 00 Available airflow rate range High level 1 700 900 1 000 1 100 1 200 800 600 1 Available airflow rate range when Auto louver grille option is ins...

Page 117: ...ir volume and capacity Cooling 0 20 40 60 80 100 120 Capacity Capacity Airflow m3 h 700 900 1 000 1 100 800 Heating 0 20 40 60 80 100 120 Capacitty Capacity Airflow m3 h 700 900 1 000 1 100 800 109 MULTI TYPE 5 6 ROOMS TYPE ...

Page 118: ...t 390 108 230 AUYG12LVLB Cooling High 610 169 359 Med 530 147 312 Low 470 131 277 Quiet 410 114 241 Heating High 610 169 359 Med 530 147 312 Low 470 131 277 Quiet 410 114 241 AUYG14LVLB Cooling High 680 189 400 Med 580 161 341 Low 490 136 288 Quiet 410 114 241 Heating High 700 194 412 Med 620 172 365 Low 550 153 324 Quiet 430 119 253 AUYG18LVLB Cooling High 750 208 441 Med 610 169 359 Low 520 144 ...

Page 119: ...25 265 Low 400 111 235 Quiet 360 100 212 ARYG12LSLAP Cooling High 650 181 383 Med 490 136 288 Low 430 119 253 Quiet 360 100 212 Heating High 650 181 383 Med 490 136 288 Low 430 119 253 Quiet 360 100 212 ARYG14LSLAP Cooling High 800 222 471 Med 640 178 377 Low 530 147 312 Quiet 360 100 212 Heating High 800 222 471 Med 640 178 377 Low 530 147 312 Quiet 360 100 212 ARYG18LSLAP Cooling High 940 261 55...

Page 120: ...53 324 Low 500 139 294 Quiet 450 125 265 ARYG12LLTB Cooling High 650 181 383 Med 600 167 353 Low 550 153 324 Quiet 480 133 283 Heating High 650 181 383 Med 600 167 353 Low 550 153 324 Quiet 480 133 283 ARYG14LLTB Cooling High 800 222 471 Med 700 194 412 Low 600 167 353 Quiet 480 133 283 Heating High 800 222 471 Med 700 194 412 Low 600 167 353 Quiet 480 133 283 ARYG18LLTB Cooling High 940 261 553 M...

Page 121: ...353 Low 530 147 312 Quiet 330 92 194 Heating High 660 183 388 Med 600 167 353 Low 530 147 312 Quiet 330 92 194 ASYG14LUCA Cooling High 710 197 418 Med 640 178 376 Low 570 158 335 Quiet 390 108 229 Heating High 710 197 418 Med 640 178 376 Low 590 164 347 Quiet 430 119 253 ASYG07LMCA ASYG07LMCE Cooling High 560 156 330 Med 500 139 294 Low 430 119 253 Quiet 310 86 182 Heating High 560 156 330 Med 500...

Page 122: ...7 353 Low 530 147 312 Quiet 360 100 212 Heating High 730 203 430 Med 615 171 362 Low 560 156 330 Quiet 375 104 221 ASYG18LFCA Cooling High 900 250 530 Med 740 206 436 Low 620 172 365 Quiet 550 153 324 Heating High 900 250 530 Med 740 206 436 Low 620 172 365 Quiet 550 153 324 ASYG24LFCA ASYG24LFCC Cooling High 1 120 311 659 Med 900 250 530 Low 740 206 436 Quiet 620 172 365 Heating High 1 100 306 64...

Page 123: ... 500 139 294 7 6 Floor type Model Operation mode Fan speed Airflow m3 h l s CFM AGYG09LVCA Cooling High 530 147 312 Med 440 122 259 Low 360 100 212 Quiet 270 75 159 Heating High 530 147 312 Med 460 128 270 Low 380 106 224 Quiet 270 75 159 AGYG12LVCA Cooling High 600 167 353 Med 490 136 288 Low 380 106 224 Quiet 270 75 159 Heating High 600 167 353 Med 510 142 300 Low 410 114 241 Quiet 270 75 159 AG...

Page 124: ...250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 HIGH QUIET Model AUYG09LVLA Cooling Octave band sound pressure level dB 0 dB 0 00020 μbar Octave band center frequency Hz 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 HIGH QUIET Heating Octave band sound pressure lev...

Page 125: ...000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 HIGH QUIET Model AUYG14LVLB Cooling Octave band sound pressure level dB 0 dB 0 00020 μbar Octave band center frequency Hz 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 HIGH QUIET Heating Octave band sound pressure level dB 0 dB 0 00020 μba...

Page 126: ...2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 HIGH QUIET Heating Octave band sound pressure level dB 0 dB 0 00020 μbar Octave band center frequency Hz NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 HIGH QUIET 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 118 MULTI TYPE 5 6 ROOMS TYPE ...

Page 127: ...enter frequency Hz NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 HIGH QUIET Model ARYG09LSLAP Cooling 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 Octave band sound pressure level dB 0 dB 0 00020 μbar Octave band center frequency Hz HIGH QUIET NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 Heating NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 ...

Page 128: ... 30 NC 25 NC 20 NC 15 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 Model ARYG14LSLAP Cooling 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 Octave band sound pressure level dB 0dB 0 00020 μbar Octave band center frequency Hz QUIET HIGH NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Heating 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000...

Page 129: ...enter frequency Hz QUIET HIGH NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Heating 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 Octave band sound pressure level dB 0dB 0 00020 μbar Octave band center frequency Hz QUIET HIGH NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 121 MULTI TYPE 5 6 ROOMS TYPE ...

Page 130: ...enter frequency Hz NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 HIGH QUIET Model ARYG09LLTA Cooling 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 Octave band sound pressure level dB 0 dB 0 00020 μbar Octave band center frequency Hz NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 HIGH QUIET Heating 0 10 20 30 40 50 60 70 80 63 125 250 500 1 ...

Page 131: ...quency Hz NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 HIGH QUIET Model ARYG14LLTB Cooling 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 Octave band sound pressure level dB 0 dB 0 00020 μbar Octave band center frequency Hz NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 HIGH QUIET Heating 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000...

Page 132: ...nter frequency Hz NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 HIGH QUIET Heating 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 Octave band sound pressure level dB 0 dB 0 00020 μbar Octave band center frequency Hz NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 HIGH QUIET 124 MULTI TYPE 5 6 ROOMS TYPE ...

Page 133: ...center frequency Hz NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 QUIET HIGH Model ASYG09LUCA Cooling 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 Octave band sound pressure level dB 0 dB 0 00020 μbar Octave band center frequency Hz NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 QUIET HIGH Heating 0 10 20 30 40 50 60 70 80 63 125 250 500 1...

Page 134: ...quency Hz NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 QUIET HIGH Model ASYG14LUCA Cooling 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 Octave band sound pressure level dB 0 dB 0 00020 μbar Octave band center frequency Hz NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 QUIET HIGH Heating 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000...

Page 135: ...quency Hz NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 QUIET HIGH Models ASYG09LMCA and ASYG09LMCE Cooling 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 Octave band sound pressure level dB 0 dB 0 00020 μbar Octave band center frequency Hz NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 QUIET HIGH Heating 0 10 20 30 40 50 60 70 80 63 125 250...

Page 136: ...quency Hz NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 QUIET HIGH Models ASYG14LMCA and ASYG14LMCE Cooling 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 Octave band sound pressure level dB 0 dB 0 00020 μbar Octave band center frequency Hz NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 QUIET HIGH Heating 0 10 20 30 40 50 60 70 80 63 125 250...

Page 137: ...z NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 QUIET HIGH Models ASYG24LFCA and ASYG24LFCC Cooling 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 Octave band sound pressure level dB 0 dB 0 00020 μbar Octave band center frequency Hz NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 QUIET HIGH Heating 0 10 20 30 40 50 60 70 80 63 125 250 500 1 0...

Page 138: ... center frequency Hz QUIET HIGH NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Model ABYG18LVTB Cooling 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 Octave band sound pressure level dB 0 dB 0 00020 μbar Octave band center frequency Hz NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH QUIET Heating 0 10 20 30 40 50 60 70 80 63 125 250 500 ...

Page 139: ...ter frequency Hz NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH QUIET Model AGYG12LVCA Cooling 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 Octave band sound pressure level dB 0 dB 0 00020 μbar Octave band center frequency Hz NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH QUIET Heating 0 10 20 30 40 50 60 70 80 63 125 250 500 1 00...

Page 140: ...nter frequency Hz NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH QUIET Heating 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 Octave band sound pressure level dB 0 dB 0 00020 μbar Octave band center frequency Hz NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH QUIET 132 MULTI TYPE 5 6 ROOMS TYPE ...

Page 141: ...8 7 Sound level check point Compact cassette type Microphone Microphone 1 5m 133 MULTI TYPE 5 6 ROOMS TYPE ...

Page 142: ...his area Mini duct type Front view Side view 1 5 m 2 m 1 m Microphone Measuring duct Measuring duct Microphone Set the static pressure as rating in this area Wall mounted type 0 8 m 1 m Microphone Microphone NOTE Detailed shape of the actual indoor unit might be slightly different from the one illustrated above 134 MULTI TYPE 5 6 ROOMS TYPE ...

Page 143: ... Floor Ceiling type Floor console Microphone Microphone 1 m 1 m 1 m Under ceiling Microphone Microphone 0 8 m 1 m Floor type Microphone Airflow Airflow 1 m 1 m Microphone 135 MULTI TYPE 5 6 ROOMS TYPE ...

Page 144: ...LLTB 0 44 58 0 35 ARYG14LLTB 0 64 76 0 51 ARYG18LLTB 0 55 73 0 44 ASYG07LUCA 50 230 0 16 13 0 13 ASYG09LUCA 0 18 16 0 14 ASYG12LUCA 0 21 19 0 17 ASYG14LUCA 0 25 23 0 20 Wall mounted ASYG07LMCA ASYG07LMCE 0 16 15 0 13 ASYG09LMCA ASYG09LMCE 0 19 17 0 15 ASYG12LMCA ASYG12LMCE 0 24 22 0 19 ASYG14LMCA ASYG14LMCE 0 31 28 0 25 ASYG18LFCA 0 41 37 0 33 ASYG24LFCA ASYG24LFCC 0 66 69 0 53 Floor Ceiling ABYG1...

Page 145: ... ARYG18LSLAP Slim duct ARYG07LLTA 250V 5A 135 15 C ARYG09LLTA ARYG12LLTB ARYG14LLTB ARYG18LLTB ASYG07LUCA 150 15 C 102 C Off ASYG09LUCA ASYG12LUCA ASYG14LUCA Wall mounted ASYG07LMCA ASYG07LMCE 140 195 C ASYG09LMCA ASYG09LMCE ASYG12LMCA ASYG12LMCE 250V 3 15A ASYG14LMCA ASYG14LMCE ASYG18LFCA 120 15 C 102 C Off ASYG24LFCA ASYG24LFCC Floor Ceiling ABYG14LVTA 135 15 C ABYG18LVTB Floor AGYG09LVCA 150 15...

Page 146: ...nection should be separate from the power cable line Control input Operation Stop or Forced stop Indoor unit type Connector Compact cassette CN102 Slim duct Wall mounted LU LM CNA01 LF CN14 Floor Ceiling CN102 Floor CN14 The air conditioner can be remotely operated by means of the following on site work Operation is started at the following contents by adding the contact input of a commercial on o...

Page 147: ...he connected unit within 10 m Use non polar relays and switches Indoor unit type 1 pin 3 pin Polarity Polarity Compact cassette Slim duct Wall mounted LU LM LF Floor Ceiling Floor When function setting is Operation Stop mode Operation Stop On Off Input signal Indoor unit When function setting is Forced stop mode Remote controller On On On Input signal Indoor unit Command Remote control operation i...

Page 148: ...Y XWZX Floor UTY XWZX UTY XWZX UTD ECS5A UTY XWZXZ5 Indoor unit type Part name Model name Compact cassette Slim duct Wall mounted LU Communication kit UTY TWBXF LM UTY XCBXZ2 LF Floor Ceiling Floor For operating the external input function the wall mounted type LU and LM requires the fol lowing communication kit in addition to the wire UTY XWZXZ5 or UTY XWZX 140 MULTI TYPE 5 6 ROOMS TYPE ...

Page 149: ...ir conditioner operation status signal can be output Circuit diagram example Locally purchased Indoor unit control PCB 1 Connected unit Example Display Example Relay unit Relay power supply DC 24 V 1 2 Signal V Connector 10 m 2 1 PCB of communication kit is used for wall mounted type LU and LM 2 Make the distance from the PCB to the connected unit within 10 m Relay spec Max DC 24 V 10 mA to less t...

Page 150: ...loor Ceiling UTY XWZX Floor UTY XWZX Indoor unit type Part name Model name Compact cassette Slim duct Wall mounted LU Communication kit UTY TWBXF LM UTY XCBXZ2 LF Floor Ceiling Floor For operating the external output function the wall mounted type LU and LM requires the fol lowing communication kit in addition to the wire UTY XWZXZ5 or UTY XWZX 142 MULTI TYPE 5 6 ROOMS TYPE ...

Page 151: ...CB Connector 1 12 V On Off 2 Signal Relay power supply Example Fan Connected unit Example Relay unit 10 m Make the distance from the PCB to the connected unit within 10 m Relay spec Rated DC 12 V 50 mA to less On Off Operation Stop Indoor fan Output signal Optional part Indoor unit type Part name Model name Compact cassette Fresh air intake kit UTZ VXAA Slim duct External control set UTD ECS5A Wal...

Page 152: ...room temperature Tr increase above 12 C signal output is on and room temperature Tr increase above 21 C signal output is off and room temperature Tr decrease below 19 C signal output is on and room temperature Tr decrease below 10 C signal output is off Off Off On Tr Ts Tr Ts 1 C Tr Ts 10 C Tr Ts 3 C Tr Ts 12 C Fan delay setting JM3 This is used to continue indoor unit fan operation for 1 minute a...

Page 153: ... the connected unit within 10 m On Off Operation Stop Heating operation Indoor unit fan On Off Output signal 1min CAUTION Locate an external heater between the indoor unit and the outlet External Heater Supply air Return air Indoor unit Be sure to use delay control of a fan Optional part Indoor unit type Part name Model name Compact cassette Slim duct External control set UTD ECS5A Wall mounted Fl...

Page 154: ...ocally purchased Example Display Indoor unit control PCB 1 Connected unit Example Relay unit 1 2 Signal Relay power supply V Connector 10 m 2 DC 24 V 1 PCB of communication kit is used for wall mounted type 2 Make the distance from the PCB to the connected unit within 10 m Relay spec Max DC 24 V 10 mA to less than 500 mA On Off Error Normal Error status Output signal 146 MULTI TYPE 5 6 ROOMS TYPE ...

Page 155: ...Ceiling Floor Indoor unit type Part name Model name Compact cassette Slim duct Wall mounted LU Communication kit UTY TWBXF LM UTY XCBXZ2 LF Floor Ceiling Floor For operating the external output function the wall mounted type LU and LM requires the fol lowing communication kit in addition to the wire UTY XWZXZ5 or UTY XWZX 147 MULTI TYPE 5 6 ROOMS TYPE ...

Page 156: ... external input function some functions on this product can be controlled from an exter nal device Operation Stop mode or Forced stop mode can be selected with function setting of indoor unit A twisted pair cable 22AWG should be used Maximum length of cable is 150 m The wire connection should be separate from the power cable line Indoor unit functions such as Operation Stop can be done by using in...

Page 157: ... 2 V Low 0 V Permissible current 50 mA For details refer to Combination of external input and output on page 150 When indicator etc are connected directly Example Function setting 60 is set to 00 1 2 CN47 LED PCB Resistor Connected unit When connecting with a device equipped with a power supply Example Function setting 60 is set to 00 1 2 Connected device CN47 PCB Connected unit Relay Operation st...

Page 158: ...0 00 Operation Stop 1 8 60 01 to 60 08 Setting prohibited 9 60 09 Operation Stop Error status 10 60 10 Operation Stop Indoor unit fan operation status 11 60 11 Operation Stop External heater output NOTE Input of Operation Stop depends on the setting of function setting 46 00 Operation Stop mode 1 R C enabled 01 Setting prohibited 02 Forced stop 03 Operation Stop mode 2 R C disabled Input signal ty...

Page 159: ...erates in the same mode When function setting is Forced stop mode Function setting External input Input signal Command 46 02 Terminal Off On Forced stop On Off Normal On Off Forced stop Normal Operation Stop Remote controller On On Indoor unit On Input NOTES When the forced stop is triggered indoor unit stops and Operation Stop operation by the remote controller is restricted When forced stop func...

Page 160: ...r group connect the same equipment to each indoor unit within the group Control output function Function setting External output Output signal Command 60 00 CN47 Low High Operation High Low Stop The output is low when the unit is stopped Operation Stop High Low CN47 Indoor unit Error status Function setting External output Output signal Command 60 09 CN47 Low High Error High Low Normal The output ...

Page 161: ... Condition Low High Heater turns on as shown in diagram of heating temperature Off On High Low Heater turns off as shown in diagram of heating temperature Other than Heating mode Error occurred On Off Forced thermo off Fan stop protection Specifications of the signal output performance are as shown as follows Example When set temperature Ts is set at 22 C And room temperature Tr increase above 12 ...

Page 162: ...ove might be different from the actual one NOTES Group connection is applicable for multi system consists of following products that are pro duced in 2013 or later LU LM LF series in wall mounted type Floor type Maximum number of connectable indoor units is depend on the outdoor unit Non polar 2 wired remote controller and Polar 3 wired remote controller cannot be connected within same group conne...

Page 163: ...ndoor unit Group connection is allowed only in the same refrigerant system Maximum number of con nectable indoor units is depend on the outdoor unit Outdoor unit Piping Wired remote controller wiring Indoor unit Indoor unit Outdoor unit Indoor unit Indoor unit Indoor unit Exterior of each device shown above might be different from the actual one Central remote controller UTY DMMYM cannot be connec...

Page 164: ...lly purchased Indoor unit Indoor unit To the other indoor units or wired remote controller To the other indoor units or wired remote controller NOTES Conceal the wirings of the group connection inside of the wall or by means of trunking at the thickness of 1 mm or more to prevent electrical shocks when getting in touch with the cables under certain circumstances When using the Communication kit fo...

Page 165: ... the function setting mode of the wireless remote controller For details refer to Func tion settings on page 198 2 Select the function number 00 Remote controller address setting and then select any of the number Setting value from 00 to 15 Factory setting 00 157 MULTI TYPE 5 6 ROOMS TYPE ...

Page 166: ...d when replacing batteries g Timer set button Sets the current time and on off time h TEST RUN button Only used for the initial test in the unit installation i CLOCK ADJUST button Used for adjusting the clock j TIMER MODE button Selects the timer mode off timer on timer program timer and timer reset k SLEEP button Pressed to select sleep timer l ECONOMY button m 10 C HEAT button n SET TEMP tempera...

Page 167: ...T RUN button Only used for the initial test in the unit installation h CLOCK ADJUST button Used for adjusting the clock i TIMER MODE button Selects the timer mode off timer on timer program timer and timer reset j SLEEP button Pressed to select sleep timer k ECONOMY button l 10 C HEAT button m SET TEMP temperature button Sets desired temperature Sets remote controller custom code n MODE button Swi...

Page 168: ... W D mm 170 56 19 Weight g 85 without batteries NOTE Actual number of buttons might be different from the figure above Holder Unit mm Front view Side view Bottom view 60 4 30 2 Ø 3 5 3 5 x 6 5 hole hole 26 2 25 5 95 154 7 Size H W D mm 154 7 60 4 26 2 Weight g 28 160 MULTI TYPE 5 6 ROOMS TYPE ...

Page 169: ...refer to the operation manual Display panel To facilitate explanation the accompanying illustration has been drawn to show all possible indicators in actual operation however the display will only show those indicators appropriate to the current operation MODE indicator LOW NOISE MODE indicator CLOCK TIMER indicator SEND indicator TEMPERATURE indicator Transmit indicator FAN Speed indicator SWING ...

Page 170: ... button NOTE Functions may differ by type of the indoor unit For details refer to the operation manual Display panel Mode indicator Clock and Timer indicator LOW NOISE mode indicator Transmit indicator Temperature indicator Fan speed indicator Swing indicator To facilitate explanation the accompanying illustration has been drawn to show all possible indica tors in actual operation however the disp...

Page 171: ...iew Side view 205 17 61 Size H W D mm 205 61 17 Weight g 122 without batteries Holder Unit mm 48 5 5 5 26 2 69 3 6 5 Front View Side View Bottom View Ø 3 5 Hole 150 106 8 Hole 3 5 2 R Size H W D mm 150 69 3 26 2 Weight g 27 163 MULTI TYPE 5 6 ROOMS TYPE ...

Page 172: ...set button Sets the current time and on off time g TEST RUN button Only used for the initial test in the unit installation h CLOCK ADJUST button Used for adjusting the clock i TIMER MODE button Selects the timer mode off timer on timer program timer and timer reset j SLEEP button Pressed to select sleep timer k ECONOMY button l 10 C HEAT button m SET TEMP temperature button Sets desired temperatur...

Page 173: ...Rear view 170 19 56 Top view Size H W D mm 170 56 19 Weight g 85 without batteries Holder Unit mm Front view Side view Bottom view 60 4 30 2 Ø 3 5 3 5 x 6 5 hole hole 26 2 25 5 95 154 7 Size H W D mm 154 7 60 4 26 2 Weight g 28 165 MULTI TYPE 5 6 ROOMS TYPE ...

Page 174: ... IR receiver Unit mm Front view 90 8 5 11 5 18 5 13 6 7 2 7 2 17 57 4 13 6 145 22 9 118 4 60 72 4 8 3 5 57 6 Side view Rear view Size H W D mm 145 90 30 Weight g 150 166 MULTI TYPE 5 6 ROOMS TYPE ...

Page 175: ...UST button SWING button SET button FAN button NOTE Functions may differ by type of the indoor unit For details refer to the operation manual Display panel Mode indicator Clock and Timer indicator Fan speed indicator Swing indicator Temperature indicator Transmit indicator To facilitate explanation the accompanying illustration has been drawn to show all possible indica tors in actual operation how...

Page 176: ...iew Side view 205 17 61 Size H W D mm 205 61 17 Weight g 122 without batteries Holder Unit mm 48 5 5 5 26 2 69 3 6 5 Front View Side View Bottom View Ø 3 5 Hole 150 106 8 Hole 3 5 2 R Size H W D mm 150 69 3 26 2 Weight g 27 168 MULTI TYPE 5 6 ROOMS TYPE ...

Page 177: ... IR receiver Unit mm Front view 90 8 5 11 5 18 5 13 6 7 2 7 2 17 57 4 13 6 145 22 9 118 4 60 72 4 8 3 5 57 6 Side view Rear view Size H W D mm 145 90 30 Weight g 150 169 MULTI TYPE 5 6 ROOMS TYPE ...

Page 178: ...t time button Pressed to set time j TIMER DELETE button Deletes the weekly timer schedule k TIMER SET button Sets the date hour minute and on off time l Vertical airflow direction and swing button Push for 2 seconds to change the swing mode m Horizontal airflow direction and swing but ton Push for 2 seconds to change the swing mode n FILTER RESET button o Operation lamp Lights during operation and...

Page 179: ... controller cable A 500 m B C 500 m Electrical wiring 1 remote controller Remote controller 1 Red 12 V 2 White Signal 3 Black COM Indoor unit Remote controller 1 2 3 1 2 3 G G 2 remote controllers Remote controllers 1 Red 12 V 2 White Signal 3 Black COM Primary Secondary Indoor unit 1 2 3 1 2 3 1 2 3 Remote controller G G G 171 MULTI TYPE 5 6 ROOMS TYPE ...

Page 180: ...ction pattern is different according to type of Indoor unit Indoor unit type Connection pattern Compact cassette Pattern A Slim duct Mini duct Floor Ceiling Wall mounted LU Pattern B LM LF Pattern C Floor Pattern A Connect the end of remote controller cable directly to the exclusive terminal block PCB M4 screw Terminal block Remote controller cable Remote controller terminal block Outdoor unit or ...

Page 181: ...nnect the cable from the terminal 2 of communication kit to the indoor unit PCB 1 CNC01 for LU type UTY TWBXF CNC01 for LM type UTY XCBXZ2 2 CND01 for LU type UTY TWBXF CNC01 for LM type UTY XCBXZ2 Remote controller cable Connecting cable Terminal 1 Terminal 2 Communication kit Indoor unit PCB Pattern C 1 Modify the remote controller cable as follows Use a tool to cut off the terminal on the end o...

Page 182: ... the indoor unit PCB Remote controller cable Connecting cable Indoor unit PCB Optional parts Wall mounted Model name LU UTY TWBXF LM UTY XCBXZ2 The communication kit is needed for connecting the wired remote controller to the wall mount ed type 174 MULTI TYPE 5 6 ROOMS TYPE ...

Page 183: ...enses ambient temperature of unit f buttons Used to select setting items during the setting item se lection screen is displayed g MENU button Used to display the setting item selection screen h MODE button Each time the button is pressed operation mode switch es as follows Auto Cool Dry Fan Heat i On Off button Starts or stops the operation NOTE On Off button cannot be operated at screens oth er t...

Page 184: ...n there is a functional grounding Remote controller Indoor unit Y1 Y1 Y2 Y2 Y3 2 remote controllers When there is a functional grounding Remote controller Remote controller Y1 Y1 Y2 Y2 Y1 Y2 Y3 Indoor unit Group control When there is a functional grounding Remote controller Indoor units Y2 Y2 Y2 Y2 Y2 Y3 Y3 Y3 Y3 Y1 Y1 Y1 Y1 Y1 NOTE Group connection with Polar 3 wired remote controller is not allo...

Page 185: ...e Remarks Remote controller cable 0 33 to 1 25 mm2 Non polar 2 core Twisted pair Use sheathed PVC cable Installation Connect the end of remote controller cable directly to the exclusive terminal block Terminal block Functional earthing If necessary Remote controller cable Non polar Indoor unit PCB NOTES Layout of terminal block and PCB varies depending on the type of indoor unit Operation may fail...

Page 186: ...al part Overview a b c d e f g h i a Display panel with backlight b Screen switch button Left c Menu button d Cancel button e Cursor button f Screen switch button Right g Power indicator h On off button i Enter button 178 MULTI TYPE 5 6 ROOMS TYPE ...

Page 187: ... 2 White Signal 3 Black COM Indoor unit Remote controller 1 2 3 1 2 3 2 remote controllers Remote controllers 1 Red 12 V 2 White Signal 3 Black COM Primary Secondary Indoor unit 1 2 3 1 2 3 1 2 3 Remote controller Controller combination As for the combined usage of the controller refer to following figures Good UTY RVNYM UTY RNNYM UTY RVNYM UTY RSNYM Indoor unit UTY RVNYM SET TEMP START STOP Indoo...

Page 188: ...20 21 3 120 Side view Front view Size H W D mm 120 120 21 3 Weight g 220 Wiring specifications Use Cable size Wire type Remarks Remote controller cable 0 33 mm2 Polar 3 core Use sheathed PVC cable 180 MULTI TYPE 5 6 ROOMS TYPE ...

Page 189: ...ough space where a flat blade screwdriver to remove the case can be insert ed Installation procedures 1 Process the remote controller cable 8 8 8 30 45 55 Unit mm 1 12V Red 2 Signal White 3 COM Black 2 Insert the flat blade screwdriver and twist it slightly to separate the front case and rear case 181 MULTI TYPE 5 6 ROOMS TYPE ...

Page 190: ... the wall directly a Seal the wiring hole of the remote controller cable b Put a remote controller cable through the back hole of the rear case of the main body c Fix the rear case by securing it with attached screws 2 places When routing the cable on wall a Cut off the cable guide of the front case with using a knife or a nipper b Deburr the edge of the cable guide c Fix the rear case by securing...

Page 191: ... White 3 COM Black Cable tie Remote controller cable sheath Hole for cable tie 2 mm Good Prohibited To avoid an excessive tension or pressure to the terminal block fix the remote controller cable with the cable tie properly CAUTION Be careful to avoid breaking the cable by over tightening the cable tie When connecting the remote controller cables do not over tighten the screws 183 MULTI TYPE 5 6 R...

Page 192: ... to type of Indoor unit Indoor unit type Connection pattern Compact cassette Pattern A Slim duct Mini duct Floor Ceiling Wall mounted LU Pattern B LM LF Pattern C Floor Pattern A Connect the end of remote controller cable directly to the exclusive terminal block PCB M4 screw Terminal block Remote controller cable Remote controller terminal block Outdoor unit or Power supply terminal block or Remot...

Page 193: ...nnect the cable from the terminal 2 of communication kit to the indoor unit PCB 1 CNC01 for LU type UTY TWBXF CNC01 for LM type UTY XCBXZ2 2 CND01 for LU type UTY TWBXF CNC01 for LM type UTY XCBXZ2 Remote controller cable Connecting cable Terminal 1 Terminal 2 Communication kit Indoor unit PCB Pattern C 1 Modify the remote controller cable as follows Use a tool to cut off the terminal on the end o...

Page 194: ... the indoor unit PCB Remote controller cable Connecting cable Indoor unit PCB Optional parts Wall mounted Model name LU UTY TWBXF LM UTY XCBXZ2 The communication kit is needed for connecting the wired remote controller to the wall mount ed type 186 MULTI TYPE 5 6 ROOMS TYPE ...

Page 195: ...ing the Monitor mode screen c LED lamp operation indicator d Touch panel display e Set temperature Operating temperature can be set f Remote controller group name g Mode Operation mode can be set h Status icons i Clock j Fan Fan speed can be set k Room temperature l Menu Various settings can be set m Status Status of the indoor unit and error can be checked NOTE Functions may differ by type of the...

Page 196: ...n there is a functional grounding Remote controller Indoor unit Y1 Y1 Y2 Y2 Y3 2 remote controllers When there is a functional grounding Remote controller Remote controller Y1 Y1 Y2 Y2 Y1 Y2 Y3 Indoor unit Group control When there is a functional grounding Remote controller Indoor units Y2 Y2 Y2 Y2 Y2 Y3 Y3 Y3 Y3 Y1 Y1 Y1 Y1 Y1 NOTE Group connection with Polar 3 wired remote controller is not allo...

Page 197: ...o 60 Storage humidity range 20 to 90 no condensation Wiring specifications Use Cable size Wire type Remarks Remote controller cable 0 33 to 1 25 mm2 Non polar 2 core Twisted pair Use sheathed PVC cable Installation Connect the end of remote controller cable directly to the exclusive terminal block Terminal block Functional earthing If necessary Remote controller cable Non polar Indoor unit PCB NOT...

Page 198: ...sting opera tion h Power source indicator Indicates the main power is on i Central control indicator Indicates when function is locked j Fan speed indicator Deletes the weekly timer schedule k Set temperature Indicates error history number in error code history display mode Indicates indoor unit address in address display mode l Operating mode indicator m Indicator Upper Indicates the error code i...

Page 199: ...emote controller cable A 500 m B C 500 m Electrical wiring 1 remote controller Remote controller 1 Red 12 V 2 White Signal 3 Black COM Indoor unit Remote controller 1 2 3 1 2 3 2 remote controllers Remote controllers 1 Red 12 V 2 White Signal 3 Black COM Primary Secondary Indoor unit 1 2 3 1 2 3 1 2 3 Remote controller 191 MULTI TYPE 5 6 ROOMS TYPE ...

Page 200: ...Polar 3 core Use sheathed PVC cable Installation Connection pattern NOTE Connection pattern is different according to type of Indoor unit Indoor unit type Connection pattern Compact cassette Pattern A Slim duct Mini duct Floor Ceiling Wall mounted LU Pattern B LM LF Pattern C Floor Pattern A Connect the end of remote controller cable directly to the exclusive terminal block PCB M4 screw Terminal b...

Page 201: ...o the terminal 1 of optional communication kit Connect the cable from the terminal 2 of communication kit to the indoor unit PCB 1 CNC01 for LU type UTY TWBXF CNC01 for LM type UTY XCBXZ2 2 CND01 for LU type UTY TWBXF CNC01 for LM type UTY XCBXZ2 Remote controller cable Connecting cable Terminal 1 Terminal 2 Communication kit Indoor unit PCB Pattern C 1 Modify the remote controller cable as follow...

Page 202: ... the indoor unit PCB Remote controller cable Connecting cable Indoor unit PCB Optional parts Wall mounted Model name LU UTY TWBXF LM UTY XCBXZ2 The communication kit is needed for connecting the wired remote controller to the wall mount ed type 194 MULTI TYPE 5 6 ROOMS TYPE ...

Page 203: ...ry Fan Heat 2 3 4 h Operating mode indicator i Airflow direction indicator j FAN speed indicator k Remote controller address indicator l Status icons Mode mismatch Filter sign 5 Defrost operation Oil recovery operation Under maintenance Error Special state Conducting electricity Emergency stop Operation controlled Forced stop Remote controller sensor is enabled 5 Central controlled Setting tempera...

Page 204: ...n there is a functional grounding Remote controller Indoor unit Y1 Y1 Y2 Y2 Y3 2 remote controllers When there is a functional grounding Remote controller Remote controller Y1 Y1 Y2 Y2 Y1 Y2 Y3 Indoor unit Group control When there is a functional grounding Remote controller Indoor units Y2 Y2 Y2 Y2 Y2 Y3 Y3 Y3 Y3 Y1 Y1 Y1 Y1 Y1 NOTE Group connection with Polar 3 wired remote controller is not allo...

Page 205: ...le size Wire type Remarks Remote controller cable 0 33 to 1 25 mm2 Non polar 2 core Twisted pair Use sheathed PVC cable Installation Connect the end of remote controller cable directly to the exclusive terminal block Terminal block Functional earthing If necessary Remote controller cable Non polar Indoor unit PCB NOTES Layout of terminal block and PCB varies depending on the type of indoor unit Op...

Page 206: ...umper wire By using some components on the PCB you can change the function settings Related components on the PCB and the applicable settings Component Setting content DIP switch 1 Remote controller address setting 2 3 4 Jumper wire JM1 Drainage function setting JM2 Auto louver grille setting JM3 Fan delay setting Component location Components on the indoor unit main PC board used for the function...

Page 207: ...OFF ON OFF 05 ON OFF ON OFF 06 OFF ON ON OFF 07 ON ON ON OFF 08 OFF OFF OFF ON 09 ON OFF OFF ON 10 OFF ON OFF ON 11 ON ON OFF ON 12 OFF OFF ON ON 13 ON OFF ON ON 14 OFF ON ON ON 15 ON ON ON ON Jumper wire setting Drainage function setting JM1 JM1 Function Factory setting Connect Enable Disconnect Disable Auto louver grille setting JM2 When auto louver grille kit optional parts is attached set the ...

Page 208: ...le settings Component Setting content DIP switch100 1 Remote controller address setting 2 3 4 DIP switch101 1 Drainage function setting 2 Auto louver grille setting 3 Fan delay setting Component location Components on the indoor unit main PCB used for the function settings are located as shown in the following figure SW100 1 2 3 4 SW101 1 2 3 200 MULTI TYPE 5 6 ROOMS TYPE ...

Page 209: ...FF ON OFF ON 11 ON ON OFF ON 12 OFF OFF ON ON 13 ON OFF ON ON 14 OFF ON ON ON 15 ON ON ON ON 00 01 02 Remote controller address Indoor unit Remote controller Switch 1 Drainage function setting SW101 Switch 1 Drainage function Factory setting ON Disabled OFF Enabled Switch 2 Auto louver grille setting SW101 When Auto louver grille kit optional parts is attached set to Enabled Switch 2 Auto louver g...

Page 210: ... Piping air tight test and vacuuming have been performed firmly There is no wiring mistake Then connect the power supply of the indoor unit Breaker on Outdoor unit Indoor units AR RAH2E AR RAH1E Button name and function During address setting mode indoor unit reject the any operation command from remote con troller MODE button START STOP button TIMER MODE button SET TEMP FAN button Setting number ...

Page 211: ...unit By selecting the appropriate custom code the communication between the indoor unit and the wireless remote controller become possible Custom code The initial setting is 4 For confirming the custom code press the TIMER MODE button to send the code to the in door unit 2 short beeps 5 Press the MODE button to enter the function setting mode 6 Select the function number by pressing the or the but...

Page 212: ... the function mode information by pressing the TIMER MODE button once 2 short beeps 10 Send the function setting information by pressing the START STOP button once 2 short beeps will be emitted from the indoor unit when the signal is received correctly If wrong code is set no beep sound will be emitted 2 short beeps NOTE Press START STOP button within 30 seconds after pressing TIMER MODE button Fu...

Page 213: ...assed power can be restored The set function is stored in the PCB and will remain in memory even when the power of indoor unit is turned off However setting function is effective after disconnecting the power supply and then recon necting it Record the latest configuration of the indoor unit function setting on a label and put the label on the unit so it can be used for after sales service operati...

Page 214: ...stom code setting of the wireless remote controller do as follows 1 Press the START STOP button until only the clock is displayed on the remote controller dis play 2 Press the MODE button for at least 5 seconds to display the current custom code initially set to A 3 Press the SET TEMP or the button to change the custom code between 206 MULTI TYPE 5 6 ROOMS TYPE ...

Page 215: ... step 1 The air conditioner custom code is set to A prior to shipment The remote controller resets to custom code A when the batteries in the remote controller are replaced If you use a custom code other than custom code A reset the custom code after re placing the batteries If you do not know the air conditioner custom code setting try each of the custom codes until you find the code which operat...

Page 216: ...tion number top line The displayed number Increases and decreases Changes the display digits Transmits function setting Transmits function mode POWERFUL button SET TEMP button START STOP button RESET button MODE button Function setting procedure 1 Connect the power supply of the outdoor unit 2 To enter the function setting mode while holding down the POWERFUL and SET TEMP buttons press the RESET b...

Page 217: ... the setting number by pressing the POWERFUL button To return to the function number selection press the POWERFUL button again 5 Select the function number by pressing the or the button Each time the 10 C HEAT button is pressed it switches between the right digit and the left digit Change digit 6 Press the MODE button once to transmit the function mode information 209 MULTI TYPE 5 6 ROOMS TYPE ...

Page 218: ...d 2 short beeps NOTE Press button within 30 seconds after pressing MODE button For the function details refer to Chapter 14 6 Function details on page 241 8 Exit the function setting mode by pressing the RESET button RESET Setting up each indoor unit Repeat step from 1 to 8 to set up each indoor unit If the custom code is other than steps from 1 to 2 and 8 need to be performed 210 MULTI TYPE 5 6 R...

Page 219: ...wever setting function is effective after disconnecting the power supply and then recon necting it Record the latest configuration of the indoor unit function setting on a label and put the label on the unit so it can be used for after sales service operations Once the RESET button is pressed on the remote controller the operation mode will be set to the AUTO MODE Adjust the operation mode to eith...

Page 220: ...de initially set to A 3 Press the SET TEMP or the button to change the custom code between 4 Press the MODE button again to return to the clock display The custom code will be changed If no buttons are pressed within 30 seconds after the custom code is displayed the system re turns to the original clock display In this case start again from step 1 The air conditioner custom code is set to A prior ...

Page 221: ...unction number top line The displayed number Increases and decreases Changes the displayed digits Fixes function setting Transmits function mode POWERFUL button TEMP button Start Stop button RESET button MODE button Function setting procedure 1 Connect the power supply of the outdoor unit 2 To enter the function setting mode while holding down the POWERFUL and SET TEMP buttons press the RESET butt...

Page 222: ...tting number by pressing the POWERFUL button To return to the function number selection press the POWERFUL button again 5 Select the function number by pressing the or the button Each time the 10 C HEAT button is pressed it switches between the right digit and the left digit Change digit 6 Press the MODE button once to transmit the function mode information 2 short beeps 214 MULTI TYPE 5 6 ROOMS T...

Page 223: ...d 2 short beeps NOTE Press button within 30 seconds after pressing MODE button For the function details refer to Chapter 14 6 Function details on page 241 8 Exit the function setting mode by pressing the RESET button RESET Setting up each indoor unit Repeat step from 1 to 8 to set up each indoor unit If the custom code is other than steps from 1 to 2 and 8 need to be performed 215 MULTI TYPE 5 6 R...

Page 224: ...wever setting function is effective after disconnecting the power supply and then recon necting it Record the latest configuration of the indoor unit function setting on a label and put the label on the unit so it can be used for after sales service operations Once the RESET button is pressed on the remote controller the operation mode will be set to the AUTO MODE Adjust the operation mode to eith...

Page 225: ...de initially set to A 3 Press the SET TEMP or the button to change the custom code between 4 Press the MODE button again to return to the clock display The custom code will be changed If no buttons are pressed within 30 seconds after the custom code is displayed the system re turns to the original clock display In this case start again from step 1 The air conditioner custom code is set to A prior ...

Page 226: ...om line and function number top line The displayed number Increases and decreases Changes the displayed digits Fixes function setting Transmits function mode ECONOMY button TEMP button Start Stop button RESET button MODE button Function setting procedure 1 Connect the power supply of the outdoor unit 2 To enter the function setting mode while holding down the ECONOMY and SET TEMP buttons press the...

Page 227: ...o the setting number by pressing the ECONOMY button To return to the function number selection press the ECONOMY button again 5 Select the function number by pressing the or the button Each time the 10 C HEAT button is pressed it switches between the right digit and the left digit Change digit 6 Press the MODE button once to transmit the function mode information 219 MULTI TYPE 5 6 ROOMS TYPE ...

Page 228: ...signal is received correctly If wrong code is set no beep sound will be emitted 1 short beep NOTE Press button within 30 seconds after pressing MODE button For the function details refer to Chapter 14 6 Function details on page 241 8 Exit the function setting mode by pressing the RESET button RESET 220 MULTI TYPE 5 6 ROOMS TYPE ...

Page 229: ... and will remain in memory even when the power of indoor unit is turned off However setting function is effective after disconnecting the power supply and then recon necting it Record the latest configuration of the indoor unit function setting on a label and put the label on the unit so it can be used for after sales service operations Once the RESET button is pressed on the remote controller the...

Page 230: ...de initially set to A 3 Press the SET TEMP or the button to change the custom code between 4 Press the MODE button again to return to the clock display The custom code will be changed If no buttons are pressed within 30 seconds after the custom code is displayed the system re turns to the original clock display In this case start again from step 1 The air conditioner custom code is set to A prior ...

Page 231: ...ing the remote controller The settings may be selected between the following two Function number or Setting number Settings will not be changed if invalid numbers or setting numbers are selected This function cannot be used on the secondary units Preparation Before connecting the power supply of the indoor unit reconfirm following items Piping air tight test and vacuuming have been performed firml...

Page 232: ...tting number TIMER SET button Transmits function setting Function setting procedure 1 Connect the power supply of the outdoor unit 2 Switch to the function setting mode To enter the function setting mode hold down the 3 buttons of SET TEMP SET TEMP and FAN at the same time for 5 seconds or longer 3 Select the function number by pressing the SET TIME or the SET TIME button 4 Select the setting numb...

Page 233: ...entionally during setting enter the mode again ac cording to the procedure in step 2 Setting up each indoor unit Repeat the procedures from step 1 to 6 and set up the indoor units requiring function setting Resetting the power after setting up function of all indoor units NOTES If the reset is not performed function cannot be read correctly After all the functions have been set the circuit breaker...

Page 234: ...M Press the Screen switch button Left and Screen switch button Right simultaneously for 5 seconds to switch to Service screen Back Setting Service Mo 10 00AM Function setting Error history I U address verification Version Test run Back Setting Date and time Submenu 1 2 Monitor Screen Filter sign R C sensor control Room temp display Off Off Mo 10 00AM Select Function setting with pressing the Curso...

Page 235: ...unction setting Mo 10 00AM R C Function Setting address No No Version Error history 00 30 01 5 Pressing the Enter button confirm the setting The data will be transferred to the indoor unit Cancel OK Function setting Mo 10 00AM R C Function Setting address No No Version Error history 00 30 01 Cancel OK Function setting Mo 10 00AM R C Function Setting address No No Version Error history 00 30 Cancel...

Page 236: ... up each indoor unit Repeat the procedures from step 1 to 6 and set up the indoor units requiring function setting Resetting the power after setting up function of all indoor units NOTES If the reset is not performed function cannot be read correctly After all the functions have been set the circuit breaker needs to be switched off for at least 2 minutes After the 2 minutes has passed power can be...

Page 237: ... following items Piping air tight test and vacuuming have been performed firmly There is no wiring mistake 1 Connect the power supply 2 To activate the address setting mode hold down the three buttons of MENU and EN TER at the same time for 2 seconds or longer Menu 2 setting screen is displayed 3 Select the 13 in Menu 2 settings Then press the ENTER button 4 Pressing the or button select a remote ...

Page 238: ...peat the procedure from step 1 to 6 and set up the indoor units requiring function setting Resetting the power after setting up function of all indoor units NOTES If the reset is not performed function cannot be read correctly After all the functions have been set the circuit breaker needs to be switched off for at least 2 minutes After the 2 minutes has passed power can be restored The set functi...

Page 239: ...r enter the installer password and touch the OK Function Setting screen is displayed Previous Page Back Next Page Page 2 3 Maintenance Test Run R C Address Setting Function Setting I U Address Setting 002 01 00 00 Address Function No Setting No Function Setting Back Setting Address setting mode initial display 3 Touch the Address on the Function Setting screen 002 01 00 00 Address Function No Sett...

Page 240: ...ing No Function Setting Back Setting 1 NOTE 1 When All is chosen by 5 and different set up Setting No from two or more in door units is displayed on Setting No 8 Setting screen of Setting No is displayed Set the Function No with or 01 002 01 30 Function Setting Cancel OK Address Function No Setting No Example Function number 30 Setting Number 01 When the OK is touched the Function Setting verifica...

Page 241: ...ack Setting Setting up each indoor unit Repeat the procedure from step 1 to 6 and set up the indoor units requiring function setting Resetting the power after setting up function of all indoor units NOTES If the reset is not performed function cannot be read correctly After all the functions have been set the circuit breaker needs to be switched off for at least 2 minutes After the 2 minutes has p...

Page 242: ...ing the remote controller The settings may be selected between the following two Function number or Setting number Settings will not be changed if invalid numbers or setting numbers are selected This function cannot be used on the secondary units Preparation Before connecting the power supply of the indoor unit reconfirm following items Piping air tight test and vacuuming have been performed firml...

Page 243: ...ils START STOP button Transmits function setting SET TEMP and button Switches the various numbers Function setting procedure 1 Connect the power supply of the outdoor unit 2 Switch to the function setting mode To enter the function setting mode hold down the 3 buttons of SET TEMP SET TEMP and FAN at the same time for 5 seconds or longer Function setting mode initial display 3 Press the FAN button ...

Page 244: ...etails Refer to Chapter 14 6 Function details on page 241 6 Exit the function setting mode by pressing the 3 buttons of SET TEMP SET TEMP and FAN at the same time for 5 seconds or longer After exiting the function setting mode the display returns to the normal mode Normal mode display If no button is pressed within 60 seconds after buttons mentioned above are pressed it will automatically exit the...

Page 245: ...he 2 minutes has passed power can be restored The set function is stored in the PCB and will remain in memory even when the power of indoor unit is turned off However setting function is effective after disconnecting the power supply and then recon necting it Record the latest configuration of the indoor unit function setting on a label and put the label on the unit so it can be used for after sal...

Page 246: ...ming have been performed firmly There is no wiring mistake NOTE Set only one Master remote controller 1 Connect the power supply 2 With Monitor mode screen displayed press and hold the SET TEMP button and FAN button simultaneously for at least 2 seconds 3 The Menu 1 screen is displayed Press and hold the SET TEMP button at least 2 sec onds Setting mode selection screen is displayed 4 Press the SET...

Page 247: ...t the 2 wire remote controller address with the SET TEMP or SET TEMP but ton Then press the button Select the 2 wire remote controller address Ex Select the 002 03 9 Set the function number with the SET TEMP or SET TEMP button Then press the button Function number 10 Set the setting number with the SET TEMP or SET TEMP button Then press the button Setting number 239 MULTI TYPE 5 6 ROOMS TYPE ...

Page 248: ...its NOTES If the reset is not performed function cannot be read correctly After all the functions have been set the circuit breaker needs to be switched off for at least 2 minutes After the 2 minutes has passed power can be restored The set function is stored in the PCB and will remain in memory even when the power of indoor unit is turned off However setting function is effective after disconnect...

Page 249: ...rections 5 Vertical airflow direction range control 6 Static pressure 7 Room temperature sensor control for cooling 8 Room temperature sensor control for heating 9 Room temperature control for indoor unit sensor 10 Room temperature control for wired remote controller sensor 11 Auto restart 12 Room temperature sensor switching 13 Remote controller custom code 14 External input control 15 Room tempe...

Page 250: ...er of 0 1 2 and 15 When different type of indoor units such as wall mounted type and cassette type cassette type and duct type or other combinations are connected using group control system some functions may no longer be available 2 Filter sign Select appropriate intervals for displaying the filter sign on the indoor unit according to the esti mated amount of dust in the air of the room If the in...

Page 251: ...000 Btu h models cannot be installed in high ceilings Do not change this setting 4 Outlet directions Select the appropriate number of outlet directions according to the installation conditions Function number Setting value Setting description Factory setting 22 00 4 way 01 3 way 5 Vertical airflow direction range control In a concealed installation change the setting to Fixed 02 to restrict the mo...

Page 252: ...t by model Model name Range of static pressure 07 type 0 to 30 Pa 09 type 12 type 14 type 0 to 50 Pa 18 type Setting number in 07 09 or 12 type is 04 to 30 Operation is same as that 03 Setting number in 14 or 18 type is 06 to 30 Operation is same as that 05 Setting number value cannot be set to 32 or more For slim duct type Function number Setting value Setting description Factory setting 26 00 0 ...

Page 253: ...er Setting value Setting description Factory setting 00 Standard 01 Lower control 31 02 Slightly higher control 03 Higher control In case of Slim duct type and Floor Ceiling type models In floor console installations select 01 9 Room temperature control for indoor unit sensor for Mini duct type only Depending on the installed environment correction of the room temperature sensor may be re quired S...

Page 254: ...5 C 13 2 0 C 14 2 5 C 15 3 0 C 16 3 5 C 17 4 0 C 11 Auto restart Enables or disables automatic restart after a power interruption Function number Setting value Setting description Factory setting 40 00 Enable 01 Disable NOTE Auto restart is an emergency function such as for power outage etc Do not attempt to use this function in normal operation Be sure to operate the unit by remote controller or ...

Page 255: ...nly work if the function setting 42 is set at Both 01 When the setting value is set to Both 00 more suitable control of the room temperature is pos sible by setting function setting 30 and 31 too Function number Setting value Setting description Factory setting 48 00 Both 01 Wired remote controller 16 Indoor unit fan control for energy saving for cooling for other than Mini duct type Enables or di...

Page 256: ...speed 02 Enable or disable this function by remote controller setting NOTES As the factory setting this setting is initially activated Set to 00 or 01 when connecting a remote controller that cannot set the Fan control for energy saving function or connecting a network converter To confirm if the remote controller has this setting refer to the operating manual of each re mote controller 18 Switchi...

Page 257: ...W1 Prohibited SW2 Dual remote controller setting SW3 Prohibited SW4 F C switch SW5 Prohibited SW6 Memory backup setting Do not use DIP switch 2 Switch location 1 2 3 4 5 6 Front case back side DIP switch 2 DIP switch 1 ON OFF 249 MULTI TYPE 5 6 ROOMS TYPE ...

Page 258: ...4 Switching temperature unit F C Displayed temperature unit can be switched between Fahrenheit F and Celsius C SW4 Fahrenheit F Celsius C Factory setting OFF C ON F SW6 Memory backup setting only for wired remote controller Set to ON to use batteries for the memory backup When batteries are not used all of settings stored in memory will be deleted if there is a pow er failure SW6 Memory backup Fac...

Page 259: ... memory will be deleted if there is a pow er failure SW1 Memory backup Factory setting OFF Invalidity ON Validity NOTE Never turn it on in the case of simple remote controller SW2 Dual remote controller setting Set the remote controller SW2 according to the following table Number of remote controller Primary unit Secondary unit Factory setting SW2 SW2 1 Normal OFF 2 Dual OFF ON 1 2 3 1 2 3 1 2 3 I...

Page 260: ...W1 Memory backup setting only for wired remote controller Set to ON to use batteries for the memory backup When batteries are not used all of settings stored in memory will be deleted if there is a pow er failure SW1 Memory backup Factory setting OFF Invalidity ON Validity NOTE Never turn it on in the case of simple remote controller 252 MULTI TYPE 5 6 ROOMS TYPE ...

Page 261: ...g SW1 Memory backup setting only for wired remote controller Set to ON to use batteries for the memory backup When batteries are not used all of settings stored in memory will be deleted if there is a pow er failure SW1 Memory backup Factory setting OFF Invalidity ON Validity NOTE Never turn it on in the case of simple remote controller 253 MULTI TYPE 5 6 ROOMS TYPE ...

Page 262: ...et the remote controller SW2 according to the following table Number of remote controller Primary unit Secondary unit Factory setting SW2 SW2 1 Normal OFF 2 Dual OFF ON 1 2 3 1 2 3 1 2 3 Indoor unit Remote controller cable Primary unit Secondary unit Remote controller SW3 Switching temperature unit F C Displayed temperature unit can be switched between Fahrenheit F and Celsius C SW3 Fahrenheit F C...

Page 263: ...troller 1 Coupler heat insulation Small 1 Remote controller holder 1 Special nut A Large flange 4 Battery 2 Special nut B Small flange 4 Tapping screw M3 12mm 2 Template Carton top 1 Cable tie 2 Drain hose 1 Wire clamper 1 Cassette grille accessories Part name Exterior Q ty Part name Exterior Q ty Connector cover 1 Hook wire 2 Tapping screw M5 12 mm 4 Screw pitch small M4 10 mm 2 Tapping screw M4 ...

Page 264: ...dium 2 Installation manual Wired remote controller 1 Filter small For 07 09 12 14 models 2 Operating manual Wired remote controller 1 Filter big For 18 model 2 Operating manual CD ROM 1 Wired remote controller 2 wire type 1 Template Carton top 1 Remote controller accessories 1 set Washer 8 Drain hose insulation B 1 Coupler heat insulation large 1 Drain hose 1 Coupler heat insulation small 1 Hose b...

Page 265: ...e large 4 Installation manual 1 Cable tie medium 3 Installation template 1 Drain hose 1 Washer 8 Hose band 1 Coupler heat insulation large 1 Drain hose insulation B 1 Coupler heat insulation small 1 Remote controller 1 Filter Small For 07 09 12 14 models 2 Tapping screw M4 16 mm 2 Filter Big For 18 model 2 Remote controller cable 1 257 MULTI TYPE 5 6 ROOMS TYPE ...

Page 266: ...g manual 1 Cloth tape 1 Installation manual 1 Tapping screw large M4 25 mm 5 Wall hook bracket 1 Tapping screw small M3 12 mm 2 Remote controller 1 Air cleaning filter 2 Battery 2 Seal A It is necessary when using AS14 It is used when the diameter of gas pipe is Ø12 70 or more 1 Remote controller holder 1 258 MULTI TYPE 5 6 ROOMS TYPE ...

Page 267: ...ng manual 1 Cloth tape 1 Installation manual 1 Tapping screw large M4 25 mm 5 Wall hook bracket 1 Tapping screw small M3 12 mm 2 Remote controller 1 Air cleaning filter 2 Battery 2 Filter holder 2 Remote controller holder 1 Seal A It is necessary when using 14 model It is used when the diameter of gas pipe is Ø12 70 or more 1 259 MULTI TYPE 5 6 ROOMS TYPE ...

Page 268: ...perating manual 1 Drain hose insulation 1 Installation manual 1 Cloth tape 1 Wall hook bracket 1 Tapping screw large M4 25 mm 8 Remote controller 1 Tapping screw small M3 12 mm 2 Battery 2 Air cleaning filter 2 Remote controller holder 1 Air cleaning filter frame 2 260 MULTI TYPE 5 6 ROOMS TYPE ...

Page 269: ...pending the indoor unit from ceiling 1 Drain hose insulation Adhesive type 100 220 mm 1 Bracket Right For suspending the indoor unit from ceiling 1 Hose band For installing drain hose 1 Wall bracket For suspending the indoor unit on the wall 2 VT wire For fixing the drain hose L 280 mm 1 Tapping screw M4 10 mm 2 Remote controller 1 Tapping screw M4 20 mm For fixing the wall bracket 6 Battery 2 Coupl...

Page 270: ...ior Q ty Part name Exterior Q ty Operating manual 1 Remote controller holder 1 Installation manual 1 Cloth tape 1 Wall hook bracket 1 Tapping screw large M4 25 mm 9 Remote controller 1 Tapping screw small M3 12 mm 2 Battery 2 Air cleaning filter 2 262 MULTI TYPE 5 6 ROOMS TYPE ...

Page 271: ... Floor Ceiling Floor Indoor unit type Type IR receiver kit with Wireless remote controller Simple remote controller UTY LRHYM UTY LBTYM UTY RSNYM UTY RSRY UTY RHRY Compact cassette Mini duct Slim duct Wall mounted LU 1 LM 2 LF Floor Ceiling Floor Accessory Optional Not applicable 1 Optional Communication kit UTY TWBXF is necessary for the installation 2 Optional Communication kit UTY XCBXZ2 is nec...

Page 272: ...E AR RAH1E AR REA2E AR REB1E Wired remote controller UTY RNNYM UTY RVNYM UTY RLRY UTY RNRYZ IR receiver kit with Wireless remote controller Simple remote controller UTY LRHYM UTY LBTYM UTY RSNYM UTY RSRY UTY RHRY 264 MULTI TYPE 5 6 ROOMS TYPE ...

Page 273: ...16 2 Cassette grille Lineup Type Model Indoor units Compact cassette Cassette grille UTG UFYD W Accessory Optional Not applicable Part Cassette grille UTG UFYD W 265 MULTI TYPE 5 6 ROOMS TYPE ...

Page 274: ...TY VTGXV UTY VKSX UTY VMSX Compact cassette Mini duct Slim duct Wall mounted LU 1 1 1 LM 2 2 2 LF Floor Ceiling Floor Indoor unit type Type Remote sensor unit Communication kit Half concealed kit Wireless LAN interface 3 UTY XSZX UTY XCBXZ2 UTY TWBXF UTR STA UTY TFNXZ1 UTY TFSXZ1 Compact cassette Mini duct Slim duct Wall mounted LU 1 LM 2 LF Floor Ceiling Floor Accessory Optional Not applicable 1 ...

Page 275: ...NOTE Combined use of MODBUS converter KNX converter and Wireless LAN interface UTY TFSXZ1 only is not allowed 267 MULTI TYPE 5 6 ROOMS TYPE ...

Page 276: ...kit Model UTY XWZX External connect kit Model UTY XWZXZ5 x 1 x 1 For compact cassette type wall mounted type LF floor ceiling type and floor type x 1 x 2 For wall mounted LU LM type External connect kit Model UTY XWZXZG MODBUS converter Model UTY VMSX For mini duct type For mini duct type KNX converter Model UTY VKSX External switch controller Models UTY TERX For mini duct type For mini duct type ...

Page 277: ...ype and mini duct type 18 models Communication kit Model UTY XCBXZ2 Communication kit Model UTY TWBXF For wall mounted LM type For wall mounted LU type Half concealed kit Model UTR STA Wireless LAN interface Model UTY TFNXZ1 1 UTY TFSXZ1 2 For floor type 1 For compact cassette type slim duct type wall mounted type floor ceiling type and floor type 2 For mini duct type 269 MULTI TYPE 5 6 ROOMS TYPE...

Page 278: ...cid alkali or other matter which effects equipment is generated Places where there is a lot of oil splash and steam such as kitchen or machinery room Places where machinery which generates high frequencies is used Ocean beaches and other areas where there is a lot of salt Places where carbon fibers or any kind of powder suspended in the air Inside of vehicles ships and other conveyances Places whe...

Page 279: ...from the floor will increase In this case even if the room temperature is suitable you may feel the foot level is cold When the airflow distribution is poor When an indoor unit is installed in a position where the outlet airflow will directly contact people a draft may be felt In addition when there are obstructions in the path of the intake and outlet airflow the air distribution may become extre...

Page 280: ... refrigerant flow may be sensed as noise and must be taken into account 1 Plan installation of a model with external expansion valve 2 Plan installation of a branch box farther from indoor unit 3 Plan installation using another air conditioner When installing duct type in ceiling chamber system In the case of the ceiling chamber system duct is not installed at indoor unit inlet side and room air i...

Page 281: ...Part 2 OUTDOOR UNIT 5 ROOMS TYPE MULTI TYPE AOYG36LBLA5 ...

Page 282: ...f Munsell 10YR 7 5 1 0 NN Dimensions H W D Net mm 998 970 370 Gross 1 162 1 150 478 Weight Net kg 94 Gross 104 Connection pipe Size Liquid mm Ø 6 35 Ø 1 4 x 5 Gas Ø 9 52 Ø3 8 x 3 Ø 12 70 Ø 1 2 x 2 Method Flare Pre charge length Total m 50 Maximum length Total 80 Maximum length Each 25 Minimum length Total 15 Minimum length Each 5 Maximum height difference between out door unit and each indoor unit...

Page 283: ...cy class Cooling A Heating average A Pdesign Cooling kW 10 0 Heating 9 0 SEER Cooling kWh kWh 7 00 SCOP Heating 4 40 Annual energy con sumption QCE kWh a 500 QHE average 2 859 Sound power level Cooling High dB A 67 Heating 68 275 OUTDOOR UNIT AOYG36LBLA5 ...

Page 284: ...3 370 14 cable port 92 5 76 3 440 Unit mm 22 2 100 81 76 52 104 198 104 4 416 Top view Rear view Front view Side view Bottom view 140 227 296 305 40 315 321 341 50 278 76 438 526 622 690 Drain cap mounting hole 7 Drain pipe mounting hole 1 276 OUTDOOR UNIT AOYG36LBLA5 ...

Page 285: ...r and sides 150 or more 200 or more 250 or more 300 or more When there are obstacles at the front only When there are obstacles at the front and rear 1 000 or more 1 000 or more 150 or more When there is an obstruction in the upper space Unit mm When there are obstacles at the rear and above When there are obstacles at the rear sides and above Max 500 300 or more 1 000 or more 1 000 or more 500 or...

Page 286: ...t the front only 300 or more 250 or more 250 or more 1 500 or more When there are obstacles at the front and rear 500 or more 1 500 or more 250 or more When there is an obstruction in the upper space Unit mm When there are obstacles at the rear and above 1 500 or more 500 or more Max 300 1 500 or more 250 or more 278 OUTDOOR UNIT AOYG36LBLA5 ...

Page 287: ...era tion efficiency CAUTION Do not install the outdoor unit in two stage where the drain water could freeze Otherwise the drainage from the upper unit may form ice and cause a malfunction of the lower unit When the outdoor temperature is 0 C or less do not use the accessory drain pipe and drain cap If the drain pipe and drain cap are used the drain water in the pipe may freeze in ex tremely cold c...

Page 288: ...AINER EXPANSION VALVE 4 WAY VALVE HEAT COOL STRAINER EXPANSION VALVE STRAINER EXPANSION VALVE THERMISTOR DISCHARGE TEMP THERMISTOR COMPRESSER TEMP THERMISTOR ROOM TEMP THERMISTOR PIPE TEMP THERMISTOR PIPE TEMP THERMISTOR OUTDOOR TEMP MUFFLER SOLENOID VALVE STRAINER MUFFLER STRAINER HEAT EXCHANGER Indoor unit E STRAINER EXPANSION VALVE ACCUMULATOR CONDENSER CHARGING VALVE CHARGING VALVE 280 OUTDOOR...

Page 289: ...5 Wiring diagram 5 1 Model AOYG36LBLA5 281 OUTDOOR UNIT AOYG36LBLA5 ...

Page 290: ... 3 5 10 0 12 5 0 8 2 78 3 88 3 60 10 0 6 5 A 9 18 24 51 1 76 3 53 4 71 3 5 10 0 12 5 0 8 2 76 3 88 3 62 10 0 6 5 A 12 12 12 36 3 33 3 33 3 33 3 5 10 0 12 5 0 8 2 81 3 88 3 56 10 0 6 6 A 12 12 14 38 3 16 3 16 3 68 3 5 10 0 12 5 0 8 2 81 3 88 3 56 10 0 6 6 A 12 12 18 42 2 86 2 86 4 28 3 5 10 0 12 5 0 8 2 79 3 88 3 58 10 0 6 6 A 12 12 24 48 2 50 2 50 5 00 3 5 10 0 12 5 0 8 2 77 3 88 3 61 10 0 6 5 A 1...

Page 291: ... 7 7 7 7 9 37 1 89 1 89 1 89 1 89 2 44 3 5 10 0 12 5 0 8 2 44 3 88 4 10 10 0 7 0 A 7 7 7 7 12 40 1 75 1 75 1 75 1 75 3 00 3 5 10 0 12 5 0 8 2 43 3 88 4 11 10 0 7 0 A 7 7 7 7 14 42 1 67 1 67 1 67 1 67 3 32 3 5 10 0 12 5 0 8 2 42 3 88 4 13 10 0 7 0 A 7 7 7 7 18 46 1 52 1 52 1 52 1 52 3 92 3 5 10 0 12 5 0 8 2 41 3 88 4 15 10 0 6 9 A 7 7 7 7 24 52 1 35 1 35 1 35 1 35 4 60 3 5 10 0 12 5 0 8 2 39 3 88 4...

Page 292: ...tioned in the table are based on the following conditions Power source of specifications 230V Pipe length 5 m Height difference 0 m Outdoor unit Indoor unit 2 or more indoor units should be connected The total ability of connected a indoor unit is up to 54 000 Btu from 27 000 Btu 284 OUTDOOR UNIT AOYG36LBLA5 ...

Page 293: ... 18 44 3 27 3 82 4 91 3 5 12 0 14 0 0 7 3 13 3 82 3 83 9 0 4 0 A 12 14 24 50 2 88 3 36 5 76 3 5 12 0 14 0 0 7 3 13 3 82 3 84 9 0 4 0 A 12 18 18 48 3 00 4 50 4 50 3 5 12 0 14 0 0 7 3 13 3 82 3 84 9 0 4 0 A 12 18 24 54 2 67 4 00 5 33 3 5 12 0 14 0 0 7 3 12 3 82 3 85 9 0 4 0 A 14 14 14 42 4 00 4 00 4 00 3 5 12 0 14 0 0 7 3 13 3 82 3 83 9 0 4 0 A 14 14 18 46 3 65 3 65 4 70 3 5 12 0 14 0 0 7 3 13 3 82 ...

Page 294: ... 0 4 4 A 7 7 7 9 18 48 1 75 1 75 1 75 2 25 4 50 3 5 12 0 14 0 0 7 2 77 3 82 4 33 9 0 4 4 A 7 7 7 9 24 54 1 56 1 56 1 56 2 00 5 32 3 5 12 0 14 0 0 7 2 76 3 82 4 35 9 0 4 4 A 7 7 7 12 12 45 1 87 1 87 1 87 3 20 3 20 3 5 12 0 14 0 0 7 2 77 3 82 4 33 9 0 4 4 A 7 7 7 12 14 47 1 79 1 79 1 79 3 06 3 57 3 5 12 0 14 0 0 7 2 77 3 82 4 33 9 0 4 4 A 7 7 7 12 18 51 1 65 1 65 1 65 2 82 4 23 3 5 12 0 14 0 0 7 2 7...

Page 295: ...8 3 72 11 68 3 75 12 50 3 79 13 36 3 83 13 78 3 85 35 0 9 80 3 90 11 08 3 97 11 68 4 00 12 50 4 04 13 36 4 09 13 78 4 11 40 0 9 27 4 09 10 48 4 17 11 05 4 20 11 83 4 25 12 64 4 30 13 03 4 32 46 0 8 75 4 29 9 88 4 36 10 42 4 40 11 15 4 45 11 92 4 50 12 29 4 52 51 10 0 9 80 1 42 11 08 1 45 11 68 1 46 12 50 1 48 13 36 1 49 13 78 1 50 5 0 9 80 1 42 11 08 1 44 11 68 1 45 12 50 1 47 13 36 1 49 13 78 1 4...

Page 296: ... 1 57 11 08 1 60 11 68 1 61 12 50 1 63 13 36 1 65 13 78 1 66 10 0 9 80 1 73 11 08 1 76 11 68 1 78 12 50 1 80 13 36 1 82 13 78 1 83 15 0 9 80 2 38 11 08 2 42 11 68 2 44 12 50 2 47 13 36 2 50 13 78 2 51 20 0 9 80 3 03 11 08 3 09 11 68 3 11 12 50 3 15 13 36 3 18 13 78 3 20 25 0 9 80 3 34 11 08 3 40 11 68 3 43 12 50 3 47 13 36 3 51 13 78 3 53 30 0 9 80 3 65 11 08 3 72 11 68 3 75 12 50 3 79 13 36 3 83 ...

Page 297: ... 1 57 11 08 1 60 11 68 1 61 12 50 1 63 13 36 1 65 13 78 1 66 10 0 9 80 1 73 11 08 1 76 11 68 1 78 12 50 1 80 13 36 1 82 13 78 1 83 15 0 9 80 2 38 11 08 2 42 11 68 2 44 12 50 2 47 13 36 2 50 13 78 2 51 20 0 9 80 3 03 11 08 3 09 11 68 3 11 12 50 3 15 13 36 3 18 13 78 3 20 25 0 9 80 3 34 11 08 3 40 11 68 3 43 12 50 3 47 13 36 3 51 13 78 3 53 30 0 9 80 3 65 11 08 3 72 11 68 3 75 12 50 3 79 13 36 3 83 ...

Page 298: ...1 25 11 84 1 26 12 20 1 27 5 0 8 68 1 34 9 81 1 36 10 34 1 38 11 07 1 39 11 84 1 41 12 20 1 41 10 0 8 68 1 48 9 81 1 50 10 34 1 52 11 07 1 53 11 84 1 55 12 20 1 56 15 0 8 68 2 03 9 81 2 07 10 34 2 09 11 07 2 11 11 84 2 14 12 20 2 15 20 0 8 68 2 59 9 81 2 64 10 34 2 66 11 07 2 69 11 84 2 72 12 20 2 73 25 0 8 68 2 85 9 81 2 91 10 34 2 93 11 07 2 96 11 84 3 00 12 20 3 01 30 0 8 68 3 12 9 81 3 17 10 3...

Page 299: ... 2 15 8 54 2 19 9 01 2 20 9 64 2 23 10 31 2 25 10 63 2 27 25 0 7 56 2 37 8 54 2 41 9 01 2 43 9 64 2 46 10 31 2 48 10 63 2 50 30 0 7 56 2 59 8 54 2 63 9 01 2 65 9 64 2 68 10 31 2 71 10 63 2 73 35 0 7 56 2 76 8 54 2 81 9 01 2 83 9 64 2 86 10 31 2 90 10 63 2 91 40 0 7 15 2 90 8 08 2 95 8 52 2 97 9 12 3 01 9 75 3 04 10 05 3 06 46 0 6 75 3 04 7 62 3 09 8 04 3 12 8 61 3 15 9 20 3 19 9 48 3 20 NOTES TC T...

Page 300: ...72 3 05 2 22 3 26 2 43 3 36 2 78 46 0 1 87 1 10 2 25 1 34 2 55 1 53 2 87 1 97 3 07 2 16 3 17 2 47 MODEL AUYG12LVLB Outdoor temperature Indoor temperature CDB CWB 18 0 12 0 21 0 15 0 23 0 16 0 27 0 19 0 29 0 21 0 32 0 23 0 CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 0 2 80 1 82 3 37 2 22 3 81 2 53 4 30 3 27 4 60 3 57 4 74 4 10 5 0 2 80 1 82 3 37 2 22 3 81 2 53 4 30 3 27 4 60 3 57 4 74 4 10 0 0...

Page 301: ... 7 07 5 63 15 0 4 18 2 50 5 03 3 05 5 69 3 47 6 42 4 49 6 86 4 92 7 07 5 63 20 0 4 18 2 50 5 03 3 05 5 69 3 47 6 42 4 49 6 86 4 92 7 07 5 63 25 0 4 18 2 50 5 03 3 05 5 69 3 47 6 42 4 49 6 86 4 92 7 07 5 63 30 0 4 18 2 50 5 03 3 05 5 69 3 47 6 42 4 49 6 86 4 92 7 07 5 63 35 0 4 18 2 50 5 03 3 05 5 69 3 47 6 42 4 49 6 86 4 92 7 07 5 63 40 0 3 96 2 24 4 76 2 73 5 38 3 11 6 07 4 02 6 49 4 40 6 69 5 04...

Page 302: ...3 05 2 13 3 26 2 33 3 36 2 67 46 0 1 87 1 06 2 25 1 29 2 55 1 47 2 87 1 90 3 07 2 08 3 17 2 38 MODEL ARYG12LSLAP Outdoor temperature Indoor temperature CDB CWB 18 0 12 0 21 0 15 0 23 0 16 0 27 0 19 0 29 0 21 0 32 0 23 0 CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 0 2 80 1 77 3 37 2 16 3 81 2 46 4 30 3 18 4 60 3 48 4 74 3 99 5 0 2 80 1 77 3 37 2 16 3 81 2 46 4 30 3 18 4 60 3 48 4 74 3 99 0 0 2...

Page 303: ...6 7 07 5 79 15 0 4 18 2 57 5 03 3 13 5 69 3 57 6 42 4 62 6 86 5 06 7 07 5 79 20 0 4 18 2 57 5 03 3 13 5 69 3 57 6 42 4 62 6 86 5 06 7 07 5 79 25 0 4 18 2 57 5 03 3 13 5 69 3 57 6 42 4 62 6 86 5 06 7 07 5 79 30 0 4 18 2 57 5 03 3 13 5 69 3 57 6 42 4 62 6 86 5 06 7 07 5 79 35 0 4 18 2 57 5 03 3 13 5 69 3 57 6 42 4 62 6 86 5 06 7 07 5 79 40 0 3 96 2 30 4 76 2 81 5 38 3 20 6 07 4 14 6 49 4 53 6 69 5 1...

Page 304: ...3 05 2 13 3 26 2 33 3 36 2 67 46 0 1 87 1 06 2 25 1 29 2 55 1 47 2 87 1 90 3 07 2 08 3 17 2 38 MODEL ARYG12LLTB Outdoor temperature Indoor temperature CDB CWB 18 0 12 0 21 0 15 0 23 0 16 0 27 0 19 0 29 0 21 0 32 0 23 0 CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 0 2 80 1 77 3 37 2 16 3 81 2 46 4 30 3 18 4 60 3 48 4 74 3 99 5 0 2 80 1 77 3 37 2 16 3 81 2 46 4 30 3 18 4 60 3 48 4 74 3 99 0 0 2 ...

Page 305: ... 7 07 5 79 15 0 4 18 2 57 5 03 3 13 5 69 3 57 6 42 4 62 6 86 5 06 7 07 5 79 20 0 4 18 2 57 5 03 3 13 5 69 3 57 6 42 4 62 6 86 5 06 7 07 5 79 25 0 4 18 2 57 5 03 3 13 5 69 3 57 6 42 4 62 6 86 5 06 7 07 5 79 30 0 4 18 2 57 5 03 3 13 5 69 3 57 6 42 4 62 6 86 5 06 7 07 5 79 35 0 4 18 2 57 5 03 3 13 5 69 3 57 6 42 4 62 6 86 5 06 7 07 5 79 40 0 3 96 2 30 4 76 2 81 5 38 3 20 6 07 4 14 6 49 4 53 6 69 5 19...

Page 306: ... 3 05 2 34 3 26 2 55 3 36 2 93 46 0 1 87 1 16 2 25 1 41 2 55 1 61 2 87 2 08 3 07 2 27 3 17 2 60 MODELS ASYG12LMCA ASYG12LMCE and ASYG12LUCA Outdoor temperature Indoor temperature CDB CWB 18 0 12 0 21 0 15 0 23 0 16 0 27 0 19 0 29 0 21 0 32 0 23 0 CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 0 2 80 1 82 3 37 2 22 3 81 2 53 4 30 3 27 4 60 3 57 4 74 4 10 5 0 2 80 1 82 3 37 2 22 3 81 2 53 4 30 3 2...

Page 307: ...CA and ASYG24LFCC Outdoor temperature Indoor temperature CDB CWB 18 0 12 0 21 0 15 0 23 0 16 0 27 0 19 0 29 0 21 0 32 0 23 0 CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 0 5 60 3 34 6 73 4 08 7 61 4 65 8 59 6 01 9 18 6 58 9 47 7 53 5 0 5 60 3 34 6 73 4 08 7 61 4 65 8 59 6 01 9 18 6 58 9 47 7 53 0 0 5 60 3 34 6 73 4 08 7 61 4 65 8 59 6 01 9 18 6 58 9 47 7 53 5 0 5 60 3 34 6 73 4 08 7 61 4 65 8 ...

Page 308: ...60 MODEL ABYG18LVTB Outdoor temperature Indoor temperature CDB CWB 18 0 12 0 21 0 15 0 23 0 16 0 27 0 19 0 29 0 21 0 32 0 23 0 CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 0 4 18 2 50 5 03 3 05 5 69 3 47 6 42 4 49 6 86 4 60 7 07 5 63 5 0 4 18 2 50 5 03 3 05 5 69 3 47 6 42 4 49 6 86 4 92 7 07 5 63 0 0 4 18 2 50 5 03 3 05 5 69 3 47 6 42 4 49 6 86 4 92 7 07 5 63 5 0 4 18 2 50 5 03 3 05 5 69 3 47 ...

Page 309: ...0 3 48 4 74 3 99 15 0 2 80 1 77 3 37 2 16 3 81 2 46 4 30 3 18 4 60 3 48 4 74 3 99 20 0 2 80 1 77 3 37 2 16 3 81 2 46 4 30 3 18 4 60 3 48 4 74 3 99 25 0 2 80 1 77 3 37 2 16 3 81 2 46 4 30 3 18 4 60 3 48 4 74 3 99 30 0 2 80 1 77 3 37 2 16 3 81 2 46 4 30 3 18 4 60 3 48 4 74 3 99 35 0 2 80 1 77 3 37 2 16 3 81 2 46 4 30 3 18 4 60 3 48 4 74 3 99 40 0 2 65 1 58 3 19 1 93 3 60 2 20 4 07 2 85 4 35 3 12 4 4...

Page 310: ...4 00 3 97 13 35 3 86 12 70 3 75 15 0 10 0 16 05 4 14 15 02 4 06 14 00 3 94 13 40 3 82 12 80 3 70 20 0 15 0 15 93 3 97 14 92 3 89 14 00 3 78 13 46 3 66 12 91 3 54 24 0 18 0 15 73 3 83 14 82 3 76 14 00 3 65 13 75 3 62 13 51 3 58 50 15 0 16 0 10 28 4 30 9 79 4 30 9 40 4 30 9 20 4 29 9 01 4 28 10 0 11 0 11 50 4 30 10 96 4 30 10 60 4 30 10 38 4 29 10 15 4 28 5 0 7 0 12 78 4 30 12 24 4 30 11 80 4 30 11 ...

Page 311: ... 4 30 11 80 4 30 11 62 4 29 11 45 4 28 0 0 2 0 14 08 4 30 13 54 4 30 13 00 4 30 12 69 4 28 12 37 4 26 5 0 3 0 15 87 4 30 15 12 4 30 14 00 4 30 13 53 4 17 13 07 4 05 7 0 6 0 16 19 4 14 15 23 4 06 14 00 3 98 13 34 3 78 12 69 3 57 10 0 8 0 16 07 4 13 15 12 4 05 14 00 3 97 13 35 3 86 12 70 3 75 15 0 10 0 16 05 4 14 15 02 4 06 14 00 3 94 13 40 3 82 12 80 3 70 20 0 15 0 15 93 3 97 14 92 3 89 14 00 3 78 ...

Page 312: ...4 04 11 54 4 04 11 13 4 04 10 96 4 03 10 79 4 02 0 0 2 0 13 27 4 04 12 76 4 04 12 26 4 04 11 96 4 02 11 67 4 00 5 0 3 0 14 96 4 04 14 26 4 04 13 20 4 04 12 76 3 92 12 32 3 80 7 0 6 0 15 26 3 89 14 36 3 82 13 20 3 74 12 58 3 55 11 96 3 36 10 0 8 0 15 16 3 88 14 26 3 81 13 20 3 73 12 59 3 63 11 98 3 52 15 0 10 0 15 13 3 89 14 17 3 81 13 20 3 70 12 64 3 59 12 07 3 48 20 0 15 0 15 02 3 73 14 07 3 66 1...

Page 313: ...6 7 10 3 25 6 95 3 25 10 0 11 0 8 87 3 26 8 45 3 26 8 18 3 26 8 00 3 25 7 83 3 25 5 0 7 0 9 86 3 26 9 45 3 26 9 10 3 26 8 97 3 25 8 83 3 24 0 0 2 0 10 86 3 26 10 44 3 26 10 03 3 26 9 79 3 24 9 54 3 23 5 0 3 0 12 24 3 26 11 66 3 26 10 80 3 26 10 44 3 16 10 08 3 07 7 0 6 0 12 49 3 14 11 75 3 08 10 80 3 02 10 29 2 86 9 79 2 71 10 0 8 0 12 40 3 13 11 67 3 07 10 80 3 01 10 30 2 92 9 80 2 84 15 0 10 0 1...

Page 314: ...6 3 22 3 16 3 09 10 0 11 0 3 94 3 76 3 63 3 56 3 48 5 0 7 0 4 38 4 20 4 05 3 98 3 92 0 0 2 0 4 83 4 64 4 46 4 35 4 24 5 0 3 0 5 44 5 18 4 80 4 64 4 48 7 0 6 0 5 55 5 22 4 80 4 58 4 35 10 0 8 0 5 51 5 19 4 80 4 58 4 36 15 0 10 0 5 50 5 15 4 80 4 60 4 39 20 0 15 0 5 46 5 12 4 80 4 61 4 43 24 0 18 0 5 39 5 08 4 80 4 72 4 63 MODEL AUYG14LVLB Outdoor temperature Indoor temperature CDB 16 0 18 0 20 0 22...

Page 315: ...NOTES TC Total Capacity kW Values mentioned in the table are based on the following conditions Pipe length 5 m Height difference 0 m Outdoor unit Indoor unit 307 OUTDOOR UNIT AOYG36LBLA5 ...

Page 316: ... 22 3 16 3 09 10 0 11 0 3 94 3 76 3 63 3 56 3 48 5 0 7 0 4 38 4 20 4 05 3 98 3 92 0 0 2 0 4 83 4 64 4 46 4 35 4 24 5 0 3 0 5 44 5 18 4 80 4 64 4 48 7 0 6 0 5 55 5 22 4 80 4 58 4 35 10 0 8 0 5 51 5 19 4 80 4 58 4 36 15 0 10 0 5 50 5 15 4 80 4 60 4 39 20 0 15 0 5 46 5 12 4 80 4 61 4 43 24 0 18 0 5 39 5 08 4 80 4 72 4 63 MODEL ARYG14LSLAP Outdoor temperature Indoor temperature CDB 16 0 18 0 20 0 22 0...

Page 317: ...NOTES TC Total Capacity kW Values mentioned in the table are based on the following conditions Pipe length 5 m Height difference 0 m Outdoor unit Indoor unit 309 OUTDOOR UNIT AOYG36LBLA5 ...

Page 318: ...22 3 16 3 09 10 0 11 0 3 94 3 76 3 63 3 56 3 48 5 0 7 0 4 38 4 20 4 05 3 98 3 92 0 0 2 0 4 83 4 64 4 46 4 35 4 24 5 0 3 0 5 44 5 18 4 80 4 64 4 48 7 0 6 0 5 55 5 22 4 80 4 58 4 35 10 0 8 0 5 51 5 19 4 80 4 58 4 36 15 0 10 0 5 50 5 15 4 80 4 60 4 39 20 0 15 0 5 46 5 12 4 80 4 61 4 43 24 0 18 0 5 39 5 08 4 80 4 72 4 63 MODEL ARYG14LLTB Outdoor temperature Indoor temperature CDB 16 0 18 0 20 0 22 0 2...

Page 319: ...NOTES TC Total Capacity kW Values mentioned in the table are based on the following conditions Pipe length 5 m Height difference 0 m Outdoor unit Indoor unit 311 OUTDOOR UNIT AOYG36LBLA5 ...

Page 320: ... 4 13 3 86 3 60 3 45 3 29 20 0 15 0 4 10 3 84 3 60 3 46 3 32 24 0 18 0 4 04 3 81 3 60 3 54 3 47 MODELS ASYG12LMCA ASYG12LMCE and ASYG12LUCA Outdoor temperature Indoor temperature CDB 16 0 18 0 20 0 22 0 24 0 CDB CWB TC TC TC TC TC 15 0 16 0 3 53 3 36 3 22 3 16 3 09 10 0 11 0 3 94 3 76 3 63 3 56 3 48 5 0 7 0 4 38 4 20 4 05 3 98 3 92 0 0 2 0 4 83 4 64 4 46 4 35 4 24 5 0 3 0 5 44 5 18 4 80 4 64 4 48 ...

Page 321: ... ASYG24LFCA and ASYG24LFCC Outdoor temperature Indoor temperature CDB 16 0 18 0 20 0 22 0 24 0 CDB CWB TC TC TC TC TC 15 0 16 0 7 05 6 71 6 45 6 31 6 18 10 0 11 0 7 88 7 51 7 27 7 11 6 96 5 0 7 0 8 76 8 40 8 09 7 97 7 85 0 0 2 0 9 65 9 28 8 91 8 70 8 48 5 0 3 0 10 88 10 37 9 60 9 28 8 96 7 0 6 0 11 10 10 44 9 60 9 15 8 70 10 0 8 0 11 02 10 37 9 60 9 16 8 71 15 0 10 0 11 00 10 30 9 60 9 19 8 78 20 ...

Page 322: ...93 5 60 5 50 5 40 MODEL ABYG18LVTB Outdoor temperature Indoor temperature CDB 16 0 18 0 20 0 22 0 24 0 CDB CWB TC TC TC TC TC 15 0 16 0 5 29 5 04 4 83 4 73 4 63 10 0 11 0 5 91 5 64 5 45 5 34 5 22 5 0 7 0 6 57 6 30 6 07 5 98 5 89 0 0 2 0 7 24 6 96 6 69 6 52 6 36 5 0 3 0 8 16 7 78 7 20 6 96 6 72 7 0 6 0 8 33 7 83 7 20 6 86 6 53 10 0 8 0 8 27 7 78 7 20 6 87 6 53 15 0 10 0 8 25 7 73 7 20 6 89 6 59 20 ...

Page 323: ...0 0 2 0 4 83 4 64 4 46 4 35 4 24 5 0 3 0 5 44 5 18 4 80 4 64 4 48 7 0 6 0 5 55 5 22 4 80 4 58 4 35 10 0 8 0 5 51 5 19 4 80 4 58 4 36 15 0 10 0 5 50 5 15 4 80 4 60 4 39 20 0 15 0 5 46 5 12 4 80 4 61 4 43 24 0 18 0 5 39 5 08 4 80 4 72 4 63 MODEL AGYG14LVCA Outdoor temperature Indoor temperature CDB 16 0 18 0 20 0 22 0 24 0 CDB CWB TC TC TC TC TC 15 0 16 0 4 11 3 92 3 76 3 68 3 60 10 0 11 0 4 60 4 38...

Page 324: ...0 935 7 5 0 988 0 980 0 966 0 952 0 939 5 0 992 0 992 0 984 0 970 0 956 0 942 0 1 000 1 000 0 992 0 978 0 964 0 950 Indoor unit is lower than outdoor unit 2 5 1 000 1 000 0 992 0 978 0 964 0 950 7 5 1 000 0 992 0 978 0 964 0 950 10 0 992 0 978 0 964 0 950 15 0 978 0 964 0 950 HEATING Pipe length m 5 7 5 10 15 20 25 Height difference H m Indoor unit is higher than outdoor unit 1 15 0 976 0 957 0 93...

Page 325: ... 934 7 5 0 993 0 986 0 970 0 952 0 932 10 0 983 0 967 0 949 0 930 15 0 962 0 944 0 925 Indoor unit 12 000 Btu COOLING Pipe length m 5 7 5 10 15 20 25 Height difference H m Indoor unit is higher than outdoor unit 1 15 0 937 0 912 0 888 10 0 970 0 944 0 919 0 896 7 5 0 988 0 974 0 948 0 923 0 899 5 0 992 0 992 0 978 0 952 0 927 0 903 0 1 000 1 000 0 986 0 960 0 934 0 910 Indoor unit is lower than ou...

Page 326: ... 914 7 5 0 993 0 985 0 965 0 938 0 912 10 0 982 0 962 0 935 0 910 15 0 957 0 930 0 905 Indoor unit 18 000 Btu COOLING Pipe length m 5 7 5 10 15 20 25 Height difference H m Indoor unit is higher than outdoor unit 1 15 0 968 0 961 0 954 10 0 982 0 976 0 969 0 962 7 5 0 988 0 986 0 980 0 973 0 966 5 0 992 0 992 0 990 0 984 0 977 0 970 0 1 000 1 000 0 998 0 992 0 985 0 978 Indoor unit is lower than ou...

Page 327: ... 002 0 992 0 976 7 5 1 000 1 002 1 002 0 992 0 976 10 1 002 1 002 0 992 0 976 15 1 002 0 992 0 976 HEATING Pipe length m 5 7 5 10 15 20 25 Height difference H m Indoor unit is higher than outdoor unit 1 15 0 964 0 939 0 913 10 0 988 0 964 0 939 0 913 7 5 1 000 0 988 0 964 0 939 0 913 5 1 000 1 000 0 988 0 964 0 939 0 913 0 1 000 1 000 0 988 0 964 0 939 0 913 Indoor unit is lower than outdoor unit ...

Page 328: ...rge calculation 8 1 Model AOYG36LBLA5 Refrigerant type R410 Refrigerant amount g 4 000 Refrigerant charge Total pipe length m 50or less 60 70 80 Max 20 g m Additional charge g 0 200 400 600 320 OUTDOOR UNIT AOYG36LBLA5 ...

Page 329: ...9 Airflow 9 1 Model AOYG36LBLA5 Cooling m3 h 4 200 l s 1 167 CFM 2 472 Heating m3 h 4 200 l s 1 167 CFM 2 472 321 OUTDOOR UNIT AOYG36LBLA5 ...

Page 330: ...35 NC 30 NC 25 NC 20 NC 15 Heating Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 10 2 Sound level check point 1 m Microphone Microphone Rear Airflow Rear view Side view NOTE Detailed shape of the actual outdoor unit might be sligh...

Page 331: ...urrent A 12 3 Wiring spec CKT BKR A 25 Power cable mm2 6 0 Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005 As the regulations of wire size and circuit breaker differ in each country or region select appropriate devices complied to the regional standard CKT BKR Circuit Breaker 323 OUTDOOR UNIT AOYG36LBLA5 ...

Page 332: ...protection Thermal protection program Activate 115 15 C Fan motor stop Reset 70 C Fan motor restart Compressor protection Thermal protection program Compressor temp Activate 108 C Compressor stop Reset 80 C Compressor restart Thermal protection program Discharge temp Activate 110 C Compressor stop Reset After 3 minutes and 110 C less than Compressor restart 324 OUTDOOR UNIT AOYG36LBLA5 ...

Page 333: ...ve prior to performing the local settings Otherwise the compressor may fail Discharge any static electricity from your body before touching the push switches Never touch any terminal or pattern of any parts on the control board The positions of the switches on the outdoor unit control board are shown in the figure below ON 1 2 3 4 ON 1 2 3 4 ON 1 2 3 4 PUMP DOWN 2 W S 1 W S CHECK TEST RUN SET1 SET...

Page 334: ...can be adjusted by changing DIP switches and push switches on the board of the outdoor unit The printed characters for the LED display are shown below DIP switch part ON 1 2 3 4 ON 1 2 3 4 ON 1 2 3 4 PUMP DOWN 2 W S 1 W S CHECK TEST RUN SET1 SET1 1 HEAT COOL SET2 SET3 F E D C MONITOR ERROR B A POWER MODE 1 2 3 SW2 SW1 LED display part 326 OUTDOOR UNIT AOYG36LBLA5 ...

Page 335: ...wn start and stop SW2 Push For when check run function is activated For displaying the check run For resetting the Automatic wiring correction memory SET1 1 DIP For selecting cooling or heating during test operation OFF SET1 2 DIP For switching SW1 operation OFF SET1 3 DIP Prohibited OFF Do not change SET1 4 DIP Prohibited OFF Do not change SET2 1 DIP For selecting outdoor unit low noise operation...

Page 336: ...pacity will de crease When changing the settings explain to the customer beforehand that the capacity de creases 13 3 Changing the current limit function Change the outdoor unit current limit function by using this setting SET2 3 SET2 4 Current Factory setting OFF OFF Full ON OFF 20 5 A OFF ON 16 5 A CAUTION When the current limited function is working cooling and heating capacity will decrease Wh...

Page 337: ...he 3 way valve of the outdoor unit open Gas pipe and liquid pipe 8 Is the power supply connected for more than 12 hours Restrictions applicable when performing the check run When the check run starts all indoor units connected to the outdoor unit will start to run auto matically During the check run you cannot check the operation of the indoor units separately After the check run check the operati...

Page 338: ...r of units places is not the same shut off the power and check whether the indoor and outdoor communication lines are properly connected If there is no operation for 1 minute the LED will return to the original display POWER MODE LED ON Example When 4 indoor units A to D are connected F E D C MONITOR ERROR B A POWER MODE 2 blink 3 Press the CHECK switch for 3 seconds or more again Check run is ini...

Page 339: ...ample When connection of B and C of the 4 units are reversed After the number of connected units are displayed B and C will light up in reverse F E D C MONITOR ERROR B A POWER MODE 7 sec 7 sec 7 sec 7 sec 2 blink NOTES Automatic wiring correction will not be completed if the power supply is disconnected while displaying the results To confirm the automatic wiring correction be sure to carry out st...

Page 340: ...t up in the order that they light up A B C D E F 1 2 3 4 5 6 7 b Based on the results of step a please record as follows Trace the dotted circle with a pen if multiple places light up A B C D E F Write the order from A to D in which the LEDs lit up inside the circle A B C D E F A B C D c Select the correction method Correct the wiring manually 2 Proceed to step 6 Use the Automatic wiring correctio...

Page 341: ...dicating that the automatic wiring correction is completed 2 blink F E D C MONITOR ERROR B A POWER MODE 6 Disconnect the power supply or turn off the breaker and wait 10 minutes then turn the power back on and perform test run NOTE If you do not disconnect the power supply or turn off the breaker normal operation is not possible Notices If an error occurs during check run it will be suspended Corr...

Page 342: ...k run results by referring to the result table in step 4 of Chapter 14 1 3 Operating procedure for check run on page 330 If the automatic wiring correction contents has not been done the POWER MODE LED will blink twice and the MONITOR LED will turn off Automatic wiring correction memory reset CAUTION When relocating the unit reset the memory beforehand or the unit may not function normally 1 Press...

Page 343: ...r supply or turn off the breaker before changing the DIP switch settings 1 Check the 3 way valves both at the liquid side and gas side are opened Confirm that the DIP switch SET1 2 is switched off 2 Set the operation mode to COOL or HEAT When switching the DIP switch SET1 1 between HEAT and COOL disconnect the power supply or turn off the circuit breaker be forehand ON 1 2 3 4 SET1 SET1 1 HEAT COO...

Page 344: ... location and the error code In the event of an error The error LED blink quickly F E D C MONITOR ERROR B A POWER MODE blink High speed Error location display LEDs A to F of MONITOR light up and display the error location In the case of an overall error LEDs A to F of MONITOR do not light up Example Coil error in indoor unit B F E D C MONITOR ERROR B A POWER MODE blink High speed 336 OUTDOOR UNIT ...

Page 345: ...ror cord 9A 1 F E D C MONITOR ERROR B A POWER MODE A 10 1 Blink High speed 9 blink F 1 2 3 4 5 6 7 8 9 A C F J P U E D C For MONITOR A and B Display mode LED on LED off Blink 0 5s Light on 0 5s Light off Number of blinking A 10 Blink C 11 Blink F 12 Blink J 13 Blink P 14 Blink U 15 Blink 337 OUTDOOR UNIT AOYG36LBLA5 ...

Page 346: ...ror 73 2 Heat exchanger middle temp sensor error 73 3 Heat exchanger liquid temp sensor error 74 1 Outdoor temp sensor error 75 1 Suction gas temp sensor error 76 1 Valve sensor error 76 2 77 1 Heat sink temp sensor error 84 1 Current sensor 1 error stoppage permanently 86 1 Discharge pressure sensor error 94 1 Trip detection 95 1 Compressor motor control error stoppage permanently 97 3 Fan motor ...

Page 347: ...re the power supply is disconnected on the breaker is turned off when changing the DIP switch 1 DIP switch SET1 2 ON 1 2 3 4 SET1 3 To start operation press the PUMP DOWN switch 2 for 3 seconds or press after the power has been on for 3 min PUMP DOWN 1 W S TEST RUN 2 Push switch SW1 During pump down the LED POWER MODE will flash 3 times consecutively 3 blink F E D C MONITOR ERROR B A POWER MODE NO...

Page 348: ...ipe valve and then start again from step 3 F E D C MONITOR ERROR B A POWER MODE 3 blink blink High speed In order to interrupt the pump down operation press the PUMP DOWN switch again The LED will return to the original display before starting pump down POWER MODE LED On The pump down may stop before completion due to error To complete the pump down correct the error open the liquid pipe valve and...

Page 349: ... 1 Drain cap 7 Drain pipe 1 Adapter K 12 70 mm 1 2 in 9 52 mm 3 8 in 2 set Cable tie with clip large 2 Adapter L 12 70 mm 1 2 in 15 88 mm 5 8 in 2 set Cable tie with clip small 2 Adapter H 9 52 mm 3 8 in 12 70 mm 1 2 in 1 set Cable tie 1 Grommet edging 1 341 OUTDOOR UNIT AOYG36LBLA5 ...

Page 350: ... 4 way navigation pad Remote controller cable 0 33 mm 22AWG NOTE The remote controller cable supplied with this controller is for indoor use If you require cables for outdoor use purchase locally Material is not specified However it should be selected considering the installing environment temperature humidity and regional regulations RoHS Directive etc 342 OUTDOOR UNIT AOYG36LBLA5 ...

Page 351: ...e following places Condition Contents Countermeasures Reference When installed near adjacent houses Perform installation work so that operating sound does not disturb the neighbors 1 Install a soundproof barrier 2 Change the installation site When there is the possibility of strong wind If the outdoor unit is exposed to strong wind capacity may drop frost may form during heating and operation may ...

Page 352: ... 344 OUTDOOR UNIT AOYG36LBLA5 ...

Page 353: ...Part 3 OUTDOOR UNIT 6 ROOMS TYPE MULTI TYPE AOYG45LBLA6 ...

Page 354: ...7 5 1 0 NN Dimensions H W D Net mm 998 970 370 Gross 1 162 1 150 478 Weight Net kg 94 Gross 105 Connection pipe Size Liquid mm Ø 6 35 Ø 1 4 x 6 Gas Ø9 52 Ø3 8 x 4 Ø 12 70 Ø 1 2 x 2 Method Flare Pre charge length Total m 50 Maximum length Total 80 Maximum length Each 25 Minimum length Total 15 Minimum length Each 5 Maximum height difference between out door unit and each indoor units 15 Maximum hei...

Page 355: ...3 370 14 cable port 92 5 76 3 440 Unit mm 22 2 100 81 76 52 104 198 104 5 520 Top view Rear view Front view Side view Bottom view 140 227 296 305 40 315 321 341 50 278 76 438 526 622 690 Drain cap mounting hole 7 Drain pipe mounting hole 1 347 OUTDOOR UNIT AOYG45LBLA6 ...

Page 356: ...r and sides 150 or more 200 or more 250 or more 300 or more When there are obstacles at the front only When there are obstacles at the front and rear 1 000 or more 1 000 or more 150 or more When there is an obstruction in the upper space Unit mm When there are obstacles at the rear and above When there are obstacles at the rear sides and above Max 500 300 or more 1 000 or more 1 000 or more 500 or...

Page 357: ...t the front only 300 or more 250 or more 250 or more 1 500 or more When there are obstacles at the front and rear 500 or more 1 500 or more 250 or more When there is an obstruction in the upper space Unit mm When there are obstacles at the rear and above 1 500 or more 500 or more Max 300 1 500 or more 250 or more 349 OUTDOOR UNIT AOYG45LBLA6 ...

Page 358: ...era tion efficiency CAUTION Do not install the outdoor unit in two stage where the drain water could freeze Otherwise the drainage from the upper unit may form ice and cause a malfunction of the lower unit When the outdoor temperature is 0 C or less do not use the accessory drain pipe and drain cap If the drain pipe and drain cap are used the drain water in the pipe may freeze in ex tremely cold c...

Page 359: ... VALVE HEAT COOL STRAINER EXPANSION VALVE STRAINER EXPANSION VALVE THERMISTOR DISCHARGE TEMP THERMISTOR COMPRESSER TEMP THERMISTOR ROOM TEMP THERMISTOR PIPE TEMP THERMISTOR PIPE TEMP THERMISTOR OUTDOOR TEMP MUFFLER SOLENOID VALVE STRAINER MUFFLER Indoor unit E STRAINER EXPANSION VALVE HEAT EXCHANGER ACCUMULATOR CONDENSER STRAINER CHARGING VALVE CHARGING VALVE HEAT EXCHANGER STRAINER EXPANSION VALV...

Page 360: ...5 Wiring diagram 5 1 Model AOYG45LBLA6 352 OUTDOOR UNIT AOYG45LBLA6 ...

Page 361: ... 3 5 12 5 14 0 0 8 3 85 4 84 3 25 12 24 24 60 2 50 5 00 5 00 3 5 12 5 14 0 0 8 3 81 4 84 3 28 14 14 14 42 4 00 4 00 4 00 3 5 12 0 13 4 0 8 3 65 4 46 3 29 14 14 18 46 3 80 3 80 4 90 3 5 12 5 14 0 0 8 3 88 4 84 3 22 14 14 24 52 3 37 3 37 5 76 3 5 12 5 14 0 0 8 3 85 4 84 3 25 14 18 18 50 3 50 4 50 4 50 3 5 12 5 14 0 0 8 3 86 4 84 3 24 14 18 24 56 3 13 4 02 5 35 3 5 12 5 14 0 0 8 3 83 4 84 3 26 14 24 ...

Page 362: ... 12 5 14 0 0 8 3 74 4 84 3 34 12 12 12 18 54 2 78 2 78 2 78 4 16 3 5 12 5 14 0 0 8 3 71 4 84 3 37 12 12 12 24 60 2 50 2 50 2 50 5 00 3 5 12 5 14 0 0 8 3 68 4 84 3 40 12 12 14 14 52 2 88 2 88 3 37 3 37 3 5 12 5 14 0 0 8 3 73 4 84 3 35 12 12 14 18 56 2 68 2 68 3 13 4 01 3 5 12 5 14 0 0 8 3 70 4 84 3 38 12 12 14 24 62 2 42 2 42 2 82 4 84 3 5 12 5 14 0 0 8 3 67 4 84 3 41 12 12 18 18 60 2 50 2 50 3 75 ...

Page 363: ... 3 55 4 84 3 52 9 9 14 14 14 60 1 87 1 87 2 92 2 92 2 92 3 5 12 5 14 0 0 8 3 56 4 84 3 51 9 12 12 12 12 57 1 98 2 63 2 63 2 63 2 63 3 5 12 5 14 0 0 8 3 58 4 84 3 49 9 12 12 12 14 59 1 91 2 54 2 54 2 54 2 97 3 5 12 5 14 0 0 8 3 57 4 84 3 50 9 12 12 14 14 61 1 84 2 46 2 46 2 87 2 87 3 5 12 5 14 0 0 8 3 56 4 84 3 51 12 12 12 12 12 60 2 50 2 50 2 50 2 50 2 50 3 5 12 5 14 0 0 8 3 56 4 84 3 51 12 12 12 ...

Page 364: ... 1 44 1 84 1 84 2 46 2 46 2 46 3 5 12 5 14 0 0 8 3 47 4 84 3 60 9 9 9 9 9 9 54 2 08 2 08 2 08 2 08 2 08 2 08 3 5 12 5 14 0 0 8 3 51 4 84 3 56 9 9 9 9 9 12 57 1 97 1 97 1 97 1 97 1 97 2 65 3 5 12 5 14 0 0 8 3 49 4 84 3 58 9 9 9 9 12 12 60 1 88 1 88 1 88 1 88 2 49 2 49 3 5 12 5 14 0 0 8 3 47 4 84 3 60 NOTES 7 7 000 Btu h 9 9 000 Btu h 12 12 000 Btu h 14 14 000 Btu h 18 18 000 Btu h 24 24 000 Btu h V...

Page 365: ...3 5 16 0 0 7 3 70 4 41 3 65 18 18 18 54 4 50 4 50 4 50 3 5 13 5 16 0 0 7 3 72 4 41 3 63 18 18 24 60 4 05 4 05 5 40 3 5 13 5 16 0 0 7 3 71 4 41 3 64 7 7 7 14 35 2 40 2 40 2 40 4 80 3 5 12 0 12 7 0 7 2 98 3 44 4 03 7 7 7 18 39 2 28 2 28 2 28 5 86 3 5 12 7 14 2 0 7 3 35 3 87 3 79 7 7 7 24 45 2 10 2 10 2 10 7 20 3 5 13 5 16 0 0 7 3 61 4 41 3 74 7 7 9 12 35 2 40 2 40 3 09 4 11 3 5 12 0 12 7 0 7 2 98 3 ...

Page 366: ... 7 3 29 3 98 3 89 7 7 7 7 14 42 2 20 2 20 2 20 2 20 4 40 3 5 13 2 15 3 0 7 3 40 4 20 3 88 7 7 7 7 18 46 2 05 2 05 2 05 2 05 5 30 3 5 13 5 16 0 0 7 3 49 4 41 3 87 7 7 7 7 24 52 1 82 1 82 1 82 1 82 6 22 3 5 13 5 16 0 0 7 3 47 4 41 3 89 7 7 7 9 9 39 2 28 2 28 2 28 2 93 2 93 3 5 12 7 14 2 0 7 3 23 3 87 3 93 7 7 7 9 12 42 2 20 2 20 2 20 2 83 3 77 3 5 13 2 15 3 0 7 3 40 4 20 3 88 7 7 7 9 14 44 2 15 2 15...

Page 367: ... 16 0 0 7 3 37 4 41 4 00 7 7 7 7 7 18 53 1 78 1 78 1 78 1 78 1 78 4 60 3 5 13 5 16 0 0 7 3 37 4 41 4 00 7 7 7 7 7 24 59 1 60 1 60 1 60 1 60 1 60 5 50 3 5 13 5 16 0 0 7 3 37 4 41 4 00 7 7 7 7 9 9 46 2 05 2 05 2 05 2 05 2 65 2 65 3 5 13 5 16 0 0 7 3 37 4 41 4 00 7 7 7 7 9 12 49 1 93 1 93 1 93 1 93 2 48 3 30 3 5 13 5 16 0 0 7 3 37 4 41 4 00 7 7 7 7 9 14 51 1 85 1 85 1 85 1 85 2 38 3 72 3 5 13 5 16 0 ...

Page 368: ...tioned in the table are based on the following conditions Power source of specifications 230 V Pipe length 5 m Height difference 0 m Outdoor unit Indoor unit 2 or more indoor units should be connected The total ability of connected a indoor unit is up to 62 000 Btu from 34 000 Btu 360 OUTDOOR UNIT AOYG45LBLA6 ...

Page 369: ...0 4 61 13 08 4 65 14 00 4 70 14 97 4 76 15 43 4 78 35 0 10 98 4 84 12 40 4 92 13 08 4 96 14 00 5 02 14 97 5 08 15 43 5 11 40 0 9 55 4 49 10 79 4 57 11 37 4 61 12 18 4 66 13 02 4 71 13 42 4 74 46 0 8 12 4 15 9 18 4 22 9 67 4 25 10 36 4 30 11 07 4 35 11 41 4 37 59 10 0 10 98 1 77 12 40 1 80 13 08 1 81 14 00 1 83 14 97 1 86 15 43 1 87 5 0 10 98 1 76 12 40 1 79 13 08 1 80 14 00 1 82 14 97 1 85 15 43 1...

Page 370: ...1 95 12 40 1 98 13 08 2 00 14 00 2 02 14 97 2 04 15 43 2 06 10 0 10 98 2 15 12 40 2 19 13 08 2 20 14 00 2 23 14 97 2 25 15 43 2 27 15 0 10 98 2 96 12 40 3 01 13 08 3 03 14 00 3 07 14 97 3 10 15 43 3 12 20 0 10 98 3 77 12 40 3 83 13 08 3 86 14 00 3 91 14 97 3 95 15 43 3 97 25 0 10 98 4 15 12 40 4 22 13 08 4 26 14 00 4 30 14 97 4 35 15 43 4 38 30 0 10 98 4 53 12 40 4 61 13 08 4 65 14 00 4 70 14 97 4...

Page 371: ...1 95 12 40 1 98 13 08 2 00 14 00 2 02 14 97 2 04 15 43 2 06 10 0 10 98 2 15 12 40 2 19 13 08 2 20 14 00 2 23 14 97 2 25 15 43 2 27 15 0 10 98 2 96 12 40 3 01 13 08 3 03 14 00 3 07 14 97 3 10 15 43 3 12 20 0 10 98 3 77 12 40 3 83 13 08 3 86 14 00 3 91 14 97 3 95 15 43 3 97 25 0 10 98 4 15 12 40 4 22 13 08 4 26 14 00 4 30 14 97 4 35 15 43 4 38 30 0 10 98 4 53 12 40 4 61 13 08 4 65 14 00 4 70 14 97 4...

Page 372: ...3 67 1 49 5 0 9 73 1 58 10 99 1 61 11 59 1 62 12 41 1 64 13 27 1 66 13 67 1 67 10 0 9 73 1 74 10 99 1 77 11 59 1 79 12 41 1 81 13 27 1 83 13 67 1 84 15 0 9 73 2 40 10 99 2 44 11 59 2 46 12 41 2 48 13 27 2 51 13 67 2 53 20 0 9 73 3 05 10 99 3 10 11 59 3 13 12 41 3 16 13 27 3 20 13 67 3 22 25 0 9 73 3 36 10 99 3 42 11 59 3 45 12 41 3 49 13 27 3 53 13 67 3 55 30 0 9 73 3 67 10 99 3 74 11 59 3 77 12 4...

Page 373: ...8 1 10 9 58 1 12 10 10 1 12 10 82 1 14 11 56 1 15 11 92 1 16 5 0 8 48 1 09 9 58 1 11 10 10 1 12 10 82 1 13 11 56 1 14 11 92 1 15 0 0 8 48 1 08 9 58 1 10 10 10 1 11 10 82 1 12 11 56 1 14 11 92 1 14 5 0 8 48 1 21 9 58 1 23 10 10 1 24 10 82 1 25 11 56 1 27 11 92 1 27 10 0 8 48 1 33 9 58 1 36 10 10 1 37 10 82 1 38 11 56 1 40 11 92 1 41 15 0 8 48 1 83 9 58 1 87 10 10 1 88 10 82 1 90 11 56 1 92 11 92 1 ...

Page 374: ...30 2 51 1 68 2 68 1 84 2 76 2 10 46 0 1 39 0 68 1 67 0 82 1 89 0 94 2 13 1 21 2 28 1 33 2 35 1 52 MODEL AUYG12LVLB Outdoor temperature Indoor temperature CDB CWB 18 0 12 0 21 0 15 0 23 0 16 0 27 0 19 0 29 0 21 0 32 0 23 0 CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 0 2 50 1 62 3 01 1 98 3 40 2 26 3 84 2 92 4 10 3 19 4 23 3 66 5 0 2 50 1 62 3 01 1 98 3 40 2 26 3 84 2 92 4 10 3 19 4 23 3 66 0 0...

Page 375: ... 6 34 5 04 15 0 3 75 2 24 4 51 2 73 5 09 3 11 5 75 4 03 6 15 4 40 6 34 5 04 20 0 3 75 2 24 4 51 2 73 5 09 3 11 5 75 4 03 6 15 4 40 6 34 5 04 25 0 3 75 2 24 4 51 2 73 5 09 3 11 5 75 4 03 6 15 4 40 6 34 5 04 30 0 3 75 2 24 4 51 2 73 5 09 3 11 5 75 4 03 6 15 4 40 6 34 5 04 35 0 3 75 2 24 4 51 2 73 5 09 3 11 5 75 4 03 6 15 4 40 6 34 5 04 40 0 3 26 1 69 3 92 2 07 4 43 2 35 5 00 3 05 5 35 3 33 5 51 3 82...

Page 376: ...2 51 1 61 2 68 1 76 2 76 2 02 46 0 1 39 0 65 1 67 0 79 1 89 0 90 2 13 1 17 2 28 1 28 2 35 1 46 MODEL ARYG12LSLAP Outdoor temperature Indoor temperature CDB CWB 18 0 12 0 21 0 15 0 23 0 16 0 27 0 19 0 29 0 21 0 32 0 23 0 CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 0 2 50 1 58 3 01 1 93 3 40 2 20 3 84 2 84 4 10 3 11 4 23 3 56 5 0 2 50 1 58 3 01 1 93 3 40 2 20 3 84 2 84 4 10 3 11 4 23 3 56 0 0 2...

Page 377: ...3 6 34 5 19 15 0 3 75 2 30 4 51 2 81 5 09 3 20 5 75 4 14 6 15 4 53 6 34 5 19 20 0 3 75 2 30 4 51 2 81 5 09 3 20 5 75 4 14 6 15 4 53 6 34 5 19 25 0 3 75 2 30 4 51 2 81 5 09 3 20 5 75 4 14 6 15 4 53 6 34 5 19 30 0 3 75 2 30 4 51 2 81 5 09 3 20 5 75 4 14 6 15 4 53 6 34 5 19 35 0 3 75 2 30 4 51 2 81 5 09 3 20 5 75 4 14 6 15 4 53 6 34 5 19 40 0 3 26 1 74 3 92 2 12 4 43 2 42 5 00 3 13 5 35 3 43 5 51 3 9...

Page 378: ...2 51 1 61 2 68 1 76 2 76 2 02 46 0 1 39 0 65 1 67 0 79 1 89 0 90 2 13 1 17 2 28 1 28 2 35 1 46 MODEL ARYG12LLTB Outdoor temperature Indoor temperature CDB CWB 18 0 12 0 21 0 15 0 23 0 16 0 27 0 19 0 29 0 21 0 32 0 23 0 CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 0 2 50 1 58 3 01 1 93 3 40 2 20 3 84 2 84 4 10 3 11 4 23 3 56 5 0 2 50 1 58 3 01 1 93 3 40 2 20 3 84 2 84 4 10 3 11 4 23 3 56 0 0 2 ...

Page 379: ... 6 34 5 19 15 0 3 75 2 30 4 51 2 81 5 09 3 20 5 75 4 14 6 15 4 53 6 34 5 19 20 0 3 75 2 30 4 51 2 81 5 09 3 20 5 75 4 14 6 15 4 53 6 34 5 19 25 0 3 75 2 30 4 51 2 81 5 09 3 20 5 75 4 14 6 15 4 53 6 34 5 19 30 0 3 75 2 30 4 51 2 81 5 09 3 20 5 75 4 14 6 15 4 53 6 34 5 19 35 0 3 75 2 30 4 51 2 81 5 09 3 20 5 75 4 14 6 15 4 53 6 34 5 19 40 0 3 26 1 74 3 92 2 12 4 43 2 42 5 00 3 13 5 35 3 43 5 51 3 93...

Page 380: ... 2 51 1 77 2 68 1 93 2 76 2 21 46 0 1 39 0 71 1 67 0 87 1 89 0 99 2 13 1 28 2 28 1 40 2 35 1 60 MODELS ASYG12LMCA ASYG12LMCE and ASYG12LUCA Outdoor temperature Indoor temperature CDB CWB 18 0 12 0 21 0 15 0 23 0 16 0 27 0 19 0 29 0 21 0 32 0 23 0 CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 0 2 50 1 62 3 01 1 98 3 40 2 26 3 84 2 92 4 10 3 19 4 23 3 66 5 0 2 50 1 62 3 01 1 98 3 40 2 26 3 84 2 9...

Page 381: ...CA and ASYG24LFCC Outdoor temperature Indoor temperature CDB CWB 18 0 12 0 21 0 15 0 23 0 16 0 27 0 19 0 29 0 21 0 32 0 23 0 CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 0 5 00 2 99 6 01 3 64 6 80 4 15 7 67 5 37 8 20 5 87 8 45 6 73 5 0 5 00 2 99 6 01 3 64 6 80 4 15 7 67 5 37 8 20 5 87 8 45 6 73 0 0 5 00 2 99 6 01 3 64 6 80 4 15 7 67 5 37 8 20 5 87 8 45 6 73 5 0 5 00 2 99 6 01 3 64 6 80 4 15 7 ...

Page 382: ...21 MODEL ABYG18LVTB Outdoor temperature Indoor temperature CDB CWB 18 0 12 0 21 0 15 0 23 0 16 0 27 0 19 0 29 0 21 0 32 0 23 0 CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 0 3 75 2 24 4 51 2 73 5 09 3 11 5 75 4 03 6 15 4 12 6 34 5 04 5 0 3 75 2 24 4 51 2 73 5 09 3 11 5 75 4 03 6 15 4 40 6 34 5 04 0 0 3 75 2 24 4 51 2 73 5 09 3 11 5 75 4 03 6 15 4 40 6 34 5 04 5 0 3 75 2 24 4 51 2 73 5 09 3 11 ...

Page 383: ...0 3 11 4 23 3 56 15 0 2 50 1 58 3 01 1 93 3 40 2 20 3 84 2 84 4 10 3 11 4 23 3 56 20 0 2 50 1 58 3 01 1 93 3 40 2 20 3 84 2 84 4 10 3 11 4 23 3 56 25 0 2 50 1 58 3 01 1 93 3 40 2 20 3 84 2 84 4 10 3 11 4 23 3 56 30 0 2 50 1 58 3 01 1 93 3 40 2 20 3 84 2 84 4 10 3 11 4 23 3 56 35 0 2 50 1 58 3 01 1 93 3 40 2 20 3 84 2 84 4 10 3 11 4 23 3 56 40 0 2 18 1 20 2 62 1 46 2 96 1 66 3 34 2 15 3 57 2 35 3 6...

Page 384: ...6 00 4 59 15 26 4 46 14 52 4 33 15 0 10 0 18 34 4 49 17 17 4 40 16 00 4 28 15 32 4 15 14 63 4 02 20 0 15 0 17 37 3 89 16 28 3 81 15 27 3 70 14 68 3 58 14 08 3 47 24 0 18 0 16 35 3 55 15 41 3 48 14 55 3 38 14 30 3 35 14 04 3 31 58 15 0 16 0 10 83 5 10 10 31 5 10 9 90 5 10 9 69 5 09 9 49 5 08 10 0 11 0 12 04 5 10 11 48 5 10 11 10 5 10 10 86 5 09 10 63 5 08 5 0 7 0 13 43 5 10 12 87 5 10 12 40 5 10 12...

Page 385: ...7 5 10 12 40 5 10 12 21 5 09 12 03 5 07 0 0 2 0 15 48 5 10 14 89 5 10 14 30 5 10 13 95 5 07 13 61 5 05 5 0 3 0 17 68 5 10 16 85 5 10 15 60 5 10 15 08 4 95 14 56 4 80 7 0 6 0 18 50 4 77 17 40 4 68 16 00 4 59 15 25 4 36 14 50 4 12 10 0 8 0 18 37 4 77 17 28 4 68 16 00 4 59 15 26 4 46 14 52 4 33 15 0 10 0 18 34 4 49 17 17 4 40 16 00 4 28 15 32 4 15 14 63 4 02 20 0 15 0 17 37 3 89 16 28 3 81 15 27 3 70...

Page 386: ...4 74 11 99 4 74 11 55 4 74 11 38 4 73 11 21 4 72 0 0 2 0 14 43 4 74 13 88 4 74 13 33 4 74 13 00 4 72 12 68 4 69 5 0 3 0 16 48 4 74 15 70 4 74 14 54 4 74 14 05 4 60 13 57 4 46 7 0 6 0 17 24 4 44 16 21 4 35 14 91 4 27 14 21 4 05 13 51 3 83 10 0 8 0 17 12 4 44 16 11 4 35 14 91 4 27 14 22 4 15 13 53 4 03 15 0 10 0 17 09 4 17 16 00 4 09 14 91 3 97 14 27 3 85 13 64 3 73 20 0 15 0 16 19 3 61 15 17 3 54 1...

Page 387: ...3 11 53 3 24 10 0 8 0 14 61 3 76 13 75 3 69 12 73 3 61 12 14 3 51 11 55 3 41 15 0 10 0 14 59 3 54 13 66 3 47 12 73 3 37 12 18 3 26 11 64 3 16 20 0 15 0 13 82 3 06 12 95 3 00 12 15 2 92 11 67 2 82 11 20 2 73 24 0 18 0 13 01 2 80 12 26 2 74 11 58 2 66 11 37 2 64 11 17 2 61 34 15 0 16 0 8 37 3 90 7 97 3 90 7 65 3 90 7 49 3 89 7 33 3 89 10 0 11 0 9 30 3 90 8 87 3 90 8 58 3 90 8 40 3 89 8 21 3 89 5 0 7...

Page 388: ...3 2 72 2 66 2 60 10 0 11 0 3 30 3 15 3 05 2 98 2 92 5 0 7 0 3 68 3 53 3 40 3 35 3 30 0 0 2 0 4 25 4 09 3 92 3 83 3 73 5 0 3 0 4 85 4 62 4 28 4 14 4 00 7 0 6 0 5 08 4 77 4 39 4 18 3 98 10 0 8 0 5 04 4 74 4 39 4 19 3 98 15 0 10 0 5 03 4 71 4 39 4 20 4 02 20 0 15 0 4 77 4 47 4 19 4 03 3 86 24 0 18 0 4 49 4 23 3 99 3 92 3 85 MODEL AUYG14LVLB Outdoor temperature Indoor temperature CDB 16 0 18 0 20 0 22...

Page 389: ...NOTES TC Total Capacity kW Values mentioned in the table are based on the following conditions Pipe length 5 m Height difference 0 m Outdoor unit Indoor unit 381 OUTDOOR UNIT AOYG45LBLA6 ...

Page 390: ... 72 2 66 2 60 10 0 11 0 3 30 3 15 3 05 2 98 2 92 5 0 7 0 3 68 3 53 3 40 3 35 3 30 0 0 2 0 4 25 4 09 3 92 3 83 3 73 5 0 3 0 4 85 4 62 4 28 4 14 4 00 7 0 6 0 5 08 4 77 4 39 4 18 3 98 10 0 8 0 5 04 4 74 4 39 4 19 3 98 15 0 10 0 5 03 4 71 4 39 4 20 4 02 20 0 15 0 4 77 4 47 4 19 4 03 3 86 24 0 18 0 4 49 4 23 3 99 3 92 3 85 MODEL ARYG14LSLAP Outdoor temperature Indoor temperature CDB 16 0 18 0 20 0 22 0...

Page 391: ...NOTES TC Total Capacity kW Values mentioned in the table are based on the following conditions Pipe length 5 m Height difference 0 m Outdoor unit Indoor unit 383 OUTDOOR UNIT AOYG45LBLA6 ...

Page 392: ...72 2 66 2 60 10 0 11 0 3 30 3 15 3 05 2 98 2 92 5 0 7 0 3 68 3 53 3 40 3 35 3 30 0 0 2 0 4 25 4 09 3 92 3 83 3 73 5 0 3 0 4 85 4 62 4 28 4 14 4 00 7 0 6 0 5 08 4 77 4 39 4 18 3 98 10 0 8 0 5 04 4 74 4 39 4 19 3 98 15 0 10 0 5 03 4 71 4 39 4 20 4 02 20 0 15 0 4 77 4 47 4 19 4 03 3 86 24 0 18 0 4 49 4 23 3 99 3 92 3 85 MODEL ARYG14LLTB Outdoor temperature Indoor temperature CDB 16 0 18 0 20 0 22 0 2...

Page 393: ...NOTES TC Total Capacity kW Values mentioned in the table are based on the following conditions Pipe length 5 m Height difference 0 m Outdoor unit Indoor unit 385 OUTDOOR UNIT AOYG45LBLA6 ...

Page 394: ... 3 78 3 54 3 30 3 16 3 02 20 0 15 0 3 58 3 36 3 15 3 03 2 90 24 0 18 0 3 37 3 18 3 00 2 95 2 90 MODELS ASYG12LMCA ASYG12LMCE and ASYG12LUCA Outdoor temperature Indoor temperature CDB 16 0 18 0 20 0 22 0 24 0 CDB CWB TC TC TC TC TC 15 0 16 0 2 97 2 83 2 72 2 66 2 60 10 0 11 0 3 30 3 15 3 05 2 98 2 92 5 0 7 0 3 68 3 53 3 40 3 35 3 30 0 0 2 0 4 25 4 09 3 92 3 83 3 73 5 0 3 0 4 85 4 62 4 28 4 14 4 00 ...

Page 395: ...DELS ASYG24LFCA and ASYG24LFCC Outdoor temperature Indoor temperature CDB 16 0 18 0 20 0 22 0 24 0 CDB CWB TC TC TC TC TC 15 0 16 0 5 91 5 63 5 41 5 30 5 18 10 0 11 0 6 58 6 27 6 06 5 93 5 81 5 0 7 0 7 33 7 03 6 77 6 67 6 57 0 0 2 0 8 46 8 13 7 81 7 62 7 43 5 0 3 0 9 66 9 20 8 52 8 24 7 95 7 0 6 0 10 11 9 50 8 74 8 33 7 92 10 0 8 0 10 03 9 44 8 74 8 34 7 93 15 0 10 0 10 02 9 38 8 74 8 37 7 99 20 0...

Page 396: ...92 4 65 4 57 4 48 MODEL ABYG18LVTB Outdoor temperature Indoor temperature CDB 16 0 18 0 20 0 22 0 24 0 CDB CWB TC TC TC TC TC 15 0 16 0 4 45 4 23 4 07 3 98 3 90 10 0 11 0 4 94 4 71 4 56 4 46 4 36 5 0 7 0 5 51 5 28 5 09 5 02 4 94 0 0 2 0 6 36 6 11 5 87 5 73 5 59 5 0 3 0 7 26 6 92 6 41 6 19 5 98 7 0 6 0 7 60 7 14 6 57 6 26 5 95 10 0 8 0 7 54 7 10 6 57 6 27 5 96 15 0 10 0 7 53 7 05 6 57 6 29 6 01 20 ...

Page 397: ...0 0 2 0 4 25 4 09 3 92 3 83 3 73 5 0 3 0 4 85 4 62 4 28 4 14 4 00 7 0 6 0 5 08 4 77 4 39 4 18 3 98 10 0 8 0 5 04 4 74 4 39 4 19 3 98 15 0 10 0 5 03 4 71 4 39 4 20 4 02 20 0 15 0 4 77 4 47 4 19 4 03 3 86 24 0 18 0 4 49 4 23 3 99 3 92 3 85 MODEL AGYG14LVCA Outdoor temperature Indoor temperature CDB 16 0 18 0 20 0 22 0 24 0 CDB CWB TC TC TC TC TC 15 0 16 0 3 46 3 29 3 16 3 10 3 03 10 0 11 0 3 85 3 67...

Page 398: ...0 935 7 5 0 988 0 980 0 966 0 952 0 939 5 0 992 0 992 0 984 0 970 0 956 0 942 0 1 000 1 000 0 992 0 978 0 964 0 950 Indoor unit is lower than outdoor unit 2 5 1 000 1 000 0 992 0 978 0 964 0 950 7 5 1 000 0 992 0 978 0 964 0 950 10 0 992 0 978 0 964 0 950 15 0 978 0 964 0 950 HEATING Pipe length m 5 7 5 10 15 20 25 Height difference H m Indoor unit is higher than outdoor unit 1 15 0 976 0 957 0 93...

Page 399: ... 934 7 5 0 993 0 986 0 970 0 952 0 932 10 0 983 0 967 0 949 0 930 15 0 962 0 944 0 925 Indoor unit 12 000 Btu COOLING Pipe length m 5 7 5 10 15 20 25 Height difference H m Indoor unit is higher than outdoor unit 1 15 0 937 0 912 0 888 10 0 970 0 944 0 919 0 896 7 5 0 988 0 974 0 948 0 923 0 899 5 0 992 0 992 0 978 0 952 0 927 0 903 0 1 000 1 000 0 986 0 960 0 934 0 910 Indoor unit is lower than ou...

Page 400: ... 914 7 5 0 993 0 985 0 965 0 938 0 912 10 0 982 0 962 0 935 0 910 15 0 957 0 930 0 905 Indoor unit 18 000 Btu COOLING Pipe length m 5 7 5 10 15 20 25 Height difference H m Indoor unit is higher than outdoor unit 1 15 0 968 0 961 0 954 10 0 982 0 976 0 969 0 962 7 5 0 988 0 986 0 980 0 973 0 966 5 0 992 0 992 0 990 0 984 0 977 0 970 0 1 000 1 000 0 998 0 992 0 985 0 978 Indoor unit is lower than ou...

Page 401: ... 002 0 992 0 976 7 5 1 000 1 002 1 002 0 992 0 976 10 1 002 1 002 0 992 0 976 15 1 002 0 992 0 976 HEATING Pipe length m 5 7 5 10 15 20 25 Height difference H m Indoor unit is higher than outdoor unit 1 15 0 964 0 939 0 913 10 0 988 0 964 0 939 0 913 7 5 1 000 0 988 0 964 0 939 0 913 5 1 000 1 000 0 988 0 964 0 939 0 913 0 1 000 1 000 0 988 0 964 0 939 0 913 Indoor unit is lower than outdoor unit ...

Page 402: ...rge calculation 8 1 Model AOYG45LBLA6 Refrigerant type R410 Refrigerant amount g 4 000 Refrigerant charge Total pipe length m 50or less 60 70 80 Max 20 g m Additional charge g 0 200 400 600 394 OUTDOOR UNIT AOYG45LBLA6 ...

Page 403: ...9 Airflow 9 1 Model AOYG45LBLA6 Cooling m3 h 4 200 l s 1 167 CFM 2 472 Heating m3 h 4 200 l s 1 167 CFM 2 472 395 OUTDOOR UNIT AOYG45LBLA6 ...

Page 404: ...35 NC 30 NC 25 NC 20 NC 15 Heating Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 10 2 Sound level check point 1 m Microphone Microphone Rear Airflow Rear view Side view NOTE Detailed shape of the actual outdoor unit might be sligh...

Page 405: ...urrent A 15 7 Wiring spec CKT BKR A 30 Power cable mm2 6 0 Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005 As the regulations of wire size and circuit breaker differ in each country or region select appropriate devices complied to the regional standard CKT BKR Circuit Breaker 397 OUTDOOR UNIT AOYG45LBLA6 ...

Page 406: ...protection Thermal protection program Activate 115 15 C Fan motor stop Reset 70 C Fan motor restart Compressor protection Thermal protection program Compressor temp Activate 108 C Compressor stop Reset 80 C Compressor restart Thermal protection program Discharge temp Activate 110 C Compressor stop Reset After 3 minutes and 110 C less than Compressor restart 398 OUTDOOR UNIT AOYG45LBLA6 ...

Page 407: ...ve prior to performing the local settings Otherwise the compressor may fail Discharge any static electricity from your body before touching the push switches Never touch any terminal or pattern of any parts on the control board The positions of the switches on the outdoor unit control board are shown in the figure below ON 1 2 3 4 ON 1 2 3 4 ON 1 2 3 4 PUMP DOWN 2 W S 1 W S CHECK TEST RUN SET1 SET...

Page 408: ...can be adjusted by changing DIP switches and push switches on the board of the outdoor unit The printed characters for the LED display are shown below DIP switch part ON 1 2 3 4 ON 1 2 3 4 ON 1 2 3 4 PUMP DOWN 2 W S 1 W S CHECK TEST RUN SET1 SET1 1 HEAT COOL SET2 SET3 F E D C MONITOR ERROR B A POWER MODE 1 2 3 SW2 SW1 LED display part 400 OUTDOOR UNIT AOYG45LBLA6 ...

Page 409: ...wn start and stop SW2 Push For when check run function is activated For displaying the check run For resetting the Automatic wiring correction memory SET1 1 DIP For selecting cooling or heating during test operation OFF SET1 2 DIP For switching SW1 operation OFF SET1 3 DIP Prohibited OFF Do not change SET1 4 DIP Prohibited OFF Do not change SET2 1 DIP For selecting outdoor unit low noise operation...

Page 410: ...pacity will de crease When changing the settings explain to the customer beforehand that the capacity de creases 13 3 Changing the current limit function Change the outdoor unit current limit function by using this setting SET2 3 SET2 4 Current Factory setting OFF OFF Full ON OFF 20 5 A OFF ON 16 5 A CAUTION When the current limited function is working cooling and heating capacity will decrease Wh...

Page 411: ...he 3 way valve of the outdoor unit open Gas pipe and liquid pipe 8 Is the power supply connected for more than 12 hours Restrictions applicable when performing the check run When the check run starts all indoor units connected to the outdoor unit will start to run auto matically During the check run you cannot check the operation of the indoor units separately After the check run check the operati...

Page 412: ...r of units places is not the same shut off the power and check whether the indoor and outdoor communication lines are properly connected If there is no operation for 1 minute the LED will return to the original display POWER MODE LED ON Example When 4 indoor units A to D are connected F E D C MONITOR ERROR B A POWER MODE 2 blink 3 Press the CHECK switch for 3 seconds or more again Check run is ini...

Page 413: ...ample When connection of B and C of the 4 units are reversed After the number of connected units are displayed B and C will light up in reverse F E D C MONITOR ERROR B A POWER MODE 7 sec 7 sec 7 sec 7 sec 2 blink NOTES Automatic wiring correction will not be completed if the power supply is disconnected while displaying the results To confirm the automatic wiring correction be sure to carry out st...

Page 414: ...t up in the order that they light up A B C D E F 1 2 3 4 5 6 7 b Based on the results of step a please record as follows Trace the dotted circle with a pen if multiple places light up A B C D E F Write the order from A to D in which the LEDs lit up inside the circle A B C D E F A B C D c Select the correction method Correct the wiring manually 2 Proceed to step 6 Use the Automatic wiring correctio...

Page 415: ...dicating that the automatic wiring correction is completed 2 blink F E D C MONITOR ERROR B A POWER MODE 6 Disconnect the power supply or turn off the breaker and wait 10 minutes then turn the power back on and perform test run NOTE If you do not disconnect the power supply or turn off the breaker normal operation is not possible Notices If an error occurs during check run it will be suspended Corr...

Page 416: ...k run results by referring to the result table in step 4 of Chapter 14 1 3 Operating procedure for check run on page 330 If the automatic wiring correction contents has not been done the POWER MODE LED will blink twice and the MONITOR LED will turn off Automatic wiring correction memory reset CAUTION When relocating the unit reset the memory beforehand or the unit may not function normally 1 Press...

Page 417: ...r supply or turn off the breaker before changing the DIP switch settings 1 Check the 3 way valves both at the liquid side and gas side are opened Confirm that the DIP switch SET1 2 is switched off 2 Set the operation mode to COOL or HEAT When switching the DIP switch SET1 1 between HEAT and COOL disconnect the power supply or turn off the circuit breaker be forehand ON 1 2 3 4 SET1 SET1 1 HEAT COO...

Page 418: ... location and the error code In the event of an error The error LED blink quickly F E D C MONITOR ERROR B A POWER MODE blink High speed Error location display LEDs A to F of MONITOR light up and display the error location In the case of an overall error LEDs A to F of MONITOR do not light up Example Coil error in indoor unit B F E D C MONITOR ERROR B A POWER MODE blink High speed 410 OUTDOOR UNIT ...

Page 419: ...ror cord 9A 1 F E D C MONITOR ERROR B A POWER MODE A 10 1 Blink High speed 9 blink F 1 2 3 4 5 6 7 8 9 A C F J P U E D C For MONITOR A and B Display mode LED on LED off Blink 0 5s Light on 0 5s Light off Number of blinking A 10 Blink C 11 Blink F 12 Blink J 13 Blink P 14 Blink U 15 Blink 411 OUTDOOR UNIT AOYG45LBLA6 ...

Page 420: ...ror 73 2 Heat exchanger middle temp sensor error 73 3 Heat exchanger liquid temp sensor error 74 1 Outdoor temp sensor error 75 1 Suction gas temp sensor error 76 1 Valve sensor error 76 2 77 1 Heat sink temp sensor error 84 1 Current sensor 1 error stoppage permanently 86 1 Discharge pressure sensor error 94 1 Trip detection 95 1 Compressor motor control error stoppage permanently 97 3 Fan motor ...

Page 421: ...re the power supply is disconnected on the breaker is turned off when changing the DIP switch 1 DIP switch SET1 2 ON 1 2 3 4 SET1 3 To start operation press the PUMP DOWN switch 2 for 3 seconds or press after the power has been on for 3 min PUMP DOWN 1 W S TEST RUN 2 Push switch SW1 During pump down the LED POWER MODE will flash 3 times consecutively 3 blink F E D C MONITOR ERROR B A POWER MODE NO...

Page 422: ...ipe valve and then start again from step 3 F E D C MONITOR ERROR B A POWER MODE 3 blink blink High speed In order to interrupt the pump down operation press the PUMP DOWN switch again The LED will return to the original display before starting pump down POWER MODE LED On The pump down may stop before completion due to error To complete the pump down correct the error open the liquid pipe valve and...

Page 423: ... 1 Drain cap 7 Drain pipe 1 Adapter K 12 70 mm 1 2 in 9 52 mm 3 8 in 2 set Cable tie with clip large 2 Adapter L 12 70 mm 1 2 in 15 88 mm 5 8 in 2 set Cable tie with clip small 2 Adapter H 9 52 mm 3 8 in 12 70 mm 1 2 in 1 set Cable tie 1 Grommet edging 1 415 OUTDOOR UNIT AOYG45LBLA6 ...

Page 424: ... 4 way navigation pad Remote controller cable 0 33 mm 22AWG NOTE The remote controller cable supplied with this controller is for indoor use If you require cables for outdoor use purchase locally Material is not specified However it should be selected considering the installing environment temperature humidity and regional regulations RoHS Directive etc 416 OUTDOOR UNIT AOYG45LBLA6 ...

Page 425: ...e following places Condition Contents Countermeasures Reference When installed near adjacent houses Perform installation work so that operating sound does not disturb the neighbors 1 Install a soundproof barrier 2 Change the installation site When there is the possibility of strong wind If the outdoor unit is exposed to strong wind capacity may drop frost may form during heating and operation may ...