Indoor unit fan operation status
Function setting
External output
Output signal
Command
60—10
CN47
Low → High
Fan run
High → Low
Fan stop
Output signal
Condition
On
The indoor unit fan is operating.
Low → High
Off
The fan is stopped or during cold air prevention.
During thermostat off when in dry mode operation.
High → Low
Fan run
Fan stop
High
Low
CN47
Indoor unit
External heater output
Function setting
External output
Output signal
Command
60—11
CN47
Low → High
Heater on
High → Low
Heater off
Output signal
Condition
Low → High
Heater turns on as shown in diagram of heating temperature
Off → On
High → Low
Heater turns off as shown in diagram of heating temperature
• Other than Heating mode
• Error occurred
On → Off
• Forced thermo off
• Fan stop protection
Specifications of the signal output performance are as shown as follows:
Example:
When set temperature (Ts) is set at 22 °C;
• And room temperature (Tr) increase above 12 °C, signal output is on.
• And Tr increase above 21 °C, signal output is off.
• And Tr decrease below 19 °C, signal output is on.
• And Tr decrease below 10 °C, signal output is off.
Off
Off
On
Tr-Ts
Tr-Ts=-1 °C
Tr-Ts=-10 °C
Tr-Ts=-3 °C
Tr-Ts=-12 °C
The output also turns off in defrost operation.
- 153 -
MULTI TYPE
5, 6 ROOMS TYPE
Summary of Contents for agyg09lvca
Page 8: ......
Page 54: ... Models ASYG18LFCA ASYG24LFCA and ASYG24LFCC 46 MULTI TYPE 5 6 ROOMS TYPE ...
Page 55: ...4 5 Floor Ceiling type Models ABYG14LVTA and ABYG18LVTB 47 MULTI TYPE 5 6 ROOMS TYPE ...
Page 56: ...4 6 Floor type Models AGYG09LVCA AGYG12LVCA and AGYG14LVCA 48 MULTI TYPE 5 6 ROOMS TYPE ...
Page 281: ...Part 2 OUTDOOR UNIT 5 ROOMS TYPE MULTI TYPE AOYG36LBLA5 ...
Page 289: ...5 Wiring diagram 5 1 Model AOYG36LBLA5 281 OUTDOOR UNIT AOYG36LBLA5 ...
Page 352: ... 344 OUTDOOR UNIT AOYG36LBLA5 ...
Page 353: ...Part 3 OUTDOOR UNIT 6 ROOMS TYPE MULTI TYPE AOYG45LBLA6 ...
Page 360: ...5 Wiring diagram 5 1 Model AOYG45LBLA6 352 OUTDOOR UNIT AOYG45LBLA6 ...