Trouble shooting 13
OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
OK
OK
Compressor Thermistor Error
Outdoor unit Main PCB
Compressor temperature thermistor
When Compressor temperature thermistor open or short-circuit
is detected at power ON or while running the compressor.
1. Connector connection failure 2. Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of connector
Check if connector is removed.
Check if connector is erroneous connection.
Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check thermistor resistance value
Thermistor characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
02-15
Refer to error code table.
17.8
26.3
20
40.0
62.5
79.1
100.9
129.8
168.6
Resistance value (k )
15
10
1013.1
-30
531.6
-20
292.9
-10
221.1
-5
5
0
Temperature (°C )
12.3
30
50
40
60
2.0
3.4
4.6
6.3
8.7
Resistance value (k )
120
100
90
80
70
Temperature (°C )
OK
OK
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
BROWN
BROWN
Thermistor
(Discharge pipe)
Thermistor
(Heat exchanger)
Thermistor
(Outdoor temp.)
Thermistor
(Compressor temp.)
3
2
1
3
2
1
CN64
BLUE
BLUE
3
2
1
3
2
1
CN62
BLACK
BLACK
3
2
1
3
2
1
CN65
BROWN
BROWN
3
2
1
3
2
1
CN63
Summary of Contents for AB*G30LRTE series
Page 3: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A Cassette Duct Ceiling type INVERTER ...
Page 26: ......
Page 27: ...2 TROUBLE SHOOTING R410A Cassette Duct Ceiling type INVERTER ...
Page 62: ......
Page 63: ...3 APPENDING DATA R410A Cassette Duct Ceiling type INVERTER ...
Page 71: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Apr 2013 Printed in Japan ...