( Fig.1 : Limit of Maximum Frequency based on Outdoor Temperature )
1. COOLING OPERATION
1-1 COOLING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is 2°C higher than a set temperature, the compressor operation
frequency will attain to maximum performance.
minimum
frequency
maximum
frequency
maximum
frequency
AO* G30LETL
AO* G36LETL
16rps
72rps
56rps
61rps
Outside air Outside air
temperature drops temperature rises
36°C
A zone
34°C
32°C
B zone
30°C
21°C
C zone
19°C
D zone
Hi
Me
Lo
Quiet
A zone
72rps
72rps
65rps
50rps
50rps
50rps
59rps
59rps
50rps
44rps
44rps
44rps
50rps
50rps
44rps
39rps
39rps
39rps
39rps
39rps
39rps
35rps
35rps
35rps
B zone
C zone
30LETL
36LETL
D zone
E zone
F zone
( Table 1 : Compressor Frequency Range )
When the compressor operates for 30 minutes continuously at over the maximum frequency ,
the maximum frequency is changed from Maximum Frequency to Maximum Frequency .
01-01
E zone
F zone
10°C
0°C
12°C
2°C
* When the room temperature is b2°C to -2.5°C of the setting temperature,
the compressor frequency is controlled within the range shown in Table 1.
However, the maximum frequency is limited in the range shown in Fig. 1 based on the
fan speed mode and the outdoor temperature.
* If the room temperature is some degrees lower than a set temperature,
the compressor will be stopped.
Summary of Contents for AB*G30LRTE series
Page 3: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A Cassette Duct Ceiling type INVERTER ...
Page 26: ......
Page 27: ...2 TROUBLE SHOOTING R410A Cassette Duct Ceiling type INVERTER ...
Page 62: ......
Page 63: ...3 APPENDING DATA R410A Cassette Duct Ceiling type INVERTER ...
Page 71: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Apr 2013 Printed in Japan ...