6. OUTDOOR FAN CONTROL
01-08
* The outdoor fan speed mentioned above depends on the compressor frequency.
(When the compressor frequency increases, the outdoor fan speed also changes to the higher
speed. When the compressor frequency decreases, the outdoor fan speed also changes to the
lower speed.)
* After the defrost control is operated on the heating mode, the fan speed keeps at the higher speed
as Table8 without relating to the compressor frequency.
( Table8 : Outdoor fan speed after the defrost )
1. Outdoor Fan Motor
2. Fan Speed
AC Motor
DC Motor
AO*G30/ 36LETL
The Table 6 shows the type of the outdoor fan motor. The control method is different
between AC motor and DC motor.
( Table 6 : Type of Motor )
900rpm
( Fig.7 : Outside air temperature zone selection )
12°C
0°C
Outside air
temperature
Outside air
temperature
F zone
D zone
G zone
H zone
2°C
- 8°C
10°C
- 10°C
( Table 7 : Outdoor fan speed )
Cooling
Heating
AO* G30LETL
AO* G36LETL
AO* G30LETL
AO* G36LETL
D
F
Zone
850/ 800/ 620/ 500/ 400
900/ 850/ 800/ 620/ 550/ 450
Refer to Fig. 7
(rpm)
500/ 320/ 250
G
300/ 250/ 200
H
D
F
G
H
300/ 250/ 200
Dry
550/ 450
500/ 320/ 250
300/ 250/ 200
300/ 250/ 200
900/ 800/ 620/ 500/ 400
900/ 800/ 620/ 550/ 450
500/ 320/ 250
300/ 250/ 200
300/ 250/ 200
550/ 450
500/ 320/ 250
300/ 250/ 200
300/ 250/ 200
Summary of Contents for AB*G30LRTE series
Page 3: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A Cassette Duct Ceiling type INVERTER ...
Page 26: ......
Page 27: ...2 TROUBLE SHOOTING R410A Cassette Duct Ceiling type INVERTER ...
Page 62: ......
Page 63: ...3 APPENDING DATA R410A Cassette Duct Ceiling type INVERTER ...
Page 71: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Apr 2013 Printed in Japan ...