9. ELECTRONIC EXPANSION VALVE CONTROL
The most proper opening of the electronic expansion valve is calculated and controlled under the
present operating condition based on the Table 12.
The compressor frequency, the temperatures detected by the discharge temperature sensor, the
indoor heat exchanger sensor, the outdoor heat exchanger sensor,
and the outdoor temperature sensor.
The expansion valve is set at 480 pulses after 120 seconds of stopping compressor.
At the time of supplying the power to the outdoor unit, the initialization of the electronic
expansion valve is operated (528 pulses are input to the closing direction).
10. TEST OPERATION CONTROL
[ Wireless remote controller ]
Under the condition where the air conditioner runs, press the TEST RUN button of the remote control,
and the test operation control mode will appear.
During test running, the operation lamp and timer lamp of the air conditioner body twinkle simultaneously.
[ Wired remote controller ]
If the operation lamp is on, press the START/STOP button to turn it off.
Press the MODE and FAN buttons at the same time for more than two seconds
to start the test operation.
The operation lamp will light up and "o1" will be displayed on the set temperature display.
[ Release ]
Perform the test operation for 60 minutes.
Pressing the START/STOP button will stop the test operation.
The compressor won't enter operation status for 3 minutes after the compressor is stopped,
even if any operation is given.
At the time when the air conditioner is switched from the cooling mode to heating mode, the
compressor is stopped, and the four-way valve is switched in 3 minutes later after
the compressor stopped.
11. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST )
12. FOUR-WAY VALVE EXTENSION SELECT
01-14
( Table 12 : The pulse range of the electronic expansion valve control )
Cooling / Dry mode
Heating mode
AO*G30LETL
AO*G36LETL
Operation mode
Pulse range
between 53 to 480 pulses.
between 40 to 480 pulses.
Summary of Contents for AB*G30LRTE series
Page 3: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A Cassette Duct Ceiling type INVERTER ...
Page 26: ......
Page 27: ...2 TROUBLE SHOOTING R410A Cassette Duct Ceiling type INVERTER ...
Page 62: ......
Page 63: ...3 APPENDING DATA R410A Cassette Duct Ceiling type INVERTER ...
Page 71: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Apr 2013 Printed in Japan ...