1-5. OUTDOOR FAN CONTROL
1. Outdoor Fan Motor
Following table shows the fan speed of the outdoor unit.
*
The outdoor fan speed changes in the range mentioned above depending on the compressor
frequency and outdoor temperature.
(When the compressor frequency and outdoor temperature increase, the outdoor fan speed
also changes to the higher speed.
When the compressor frequency and outdoor temperature decrease, the outdoor fan
speed also changes to the lower speed.)
*
It runs at 500rpm for 20 seconds after starting up the outdoor fan.
However, the fan
C
operates at 300rpm when the initial rotation speed is 300rpm or less.
( Table 3 : Fan speed of the outdoor unit )
780/ 680/ 660/ 590/
520/ 450/ 440/ 380/ 300 rpm
680/ 660/ 590/ 520/
450/ 440/ 380/ 300 rpm
680/ 660/ 510/ 400/ 330/ 300 rpm
740/ 680/ 660/ 510/ 400/
330/ 300 rpm
Cooling
Heating
Upper fan
Lower fan
AO*G72LRLA
780/ 730/ 660/ 590/
520/ 450/ 440/ 380/ 300 rpm
780/ 730/ 660/ 590/
520/ 450/ 440/ 380/ 300 rpm
740/ 690/ 660/ 510/ 400/
330/ 300 rpm
740/ 690/ 660/ 510/ 400/
330/ 300 rpm
Upper fan
Lower fan
AO*G90LRLA
After operating the defrost control function on heating mode except economy operation,
its speed becomes 780(Upper) / 740(Lower)(90). 680(Upper) /680(Lower)(72) regardless of the
compressor speed.
However, it returns to the normal speed control when the defrosting operation does not function
for 240 minutes after releasing the defrost operation or when the outdoor temperature sensor
detection value becom
°
es higher than 5 .
*
The compressor and the fan start-up at the same time, and the fan stops after the compressor
stops and 60 seconds has passed.
*
The fan doesn't operates fan 10 seconds after the fan stops.
*