3-1. FUNCTION SETTING
Follow the instructions in the Local Setup Procedure, which is supplied with the remote control,
in accordance with the installed condition.
After the power is turned on, perform the Function Setting on the remote control.
The settings may be selected between the following two: Function Number or Setting Value.
Settings will not be changed if invalid numbers or setting values are selected.
3-1-1 INDOOR UNIT ( For AR type)
Filter sign
estimated amount of dust in the air of the room.
If the indication is not required, select “No indication” (03).
Setting Description
Function Number
Setting Value
Standard (400 hours)
Long interval (1000 hours)
Short interval (200 hours)
No indication
11
26
00
01
02
03
( Factory setting)
Setting Description
Function Number
Setting Value
Standard
Slightly lower control
Lower control
Warmar control
30
00
01
02
03
( Factory setting)
Setting Description
Function Number
Setting Value
Standard
Slightly warmer control
Lower control
Warmar control
21
00
01
02
03
( Factory setting)
Setting Value
00
01
02
03
04
05
06
07
08
09
31
( Factory setting)
Static pressure (AR*G18LLLA)
Select the appropriate static pressure according to the installation conditions.
Select appropriate intervals for displaying the filter sign on the indoor unit according to the
25Pa (Standard)
0Pa
20Pa
30Pa
50Pa
40Pa
60Pa
70Pa
80Pa
90Pa
10Pa
Setting Description
Function Number
03-01
Static pressure (AR*G22/24LMLA, AR*GARYG30/36LMLE)
Select appropriate static pressure according to the installation conditions.
Cooler room temperature correction
Depending on the insralled environment, the room temperature sensor may require a correction.
The settings may be selected as shown in the table below.
Determine the wind volume in each mode i.e. applicable range of static pressure,
referring "8.3. Static pressure characteristics."(The unit is factory-set to "00")