Trouble shooting 3
INDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause:
Check Point 2 : Check Wired Remote Controller and Controller PCB
Check Point 1 : Check the connection of terminal
OK
Wired Remote Controller
Communication Error
Indoor unit Controller PCB
Wired Remote Controller
1. Connection failure 2. Wired Remote Controller failure 3. Controller PCB failure
Check & correct the followings.
Check the connection of terminal berween Wired Remote Controller and indoor unit,
and check if there is a disconnection of the cable.
When the indoor unit cannot properly receive the signal from
Wired Remote Controller for 1 minute or more.
>> If it is DC13V, Remote Control is failure. (Controller PCB is normal) >> Replace Remote Control
>> If it is DC 0V, Controller PCB is failure. (Check Remote Control once again) >> Replace Controller PCB
Ceck Voltage at CN14 of Controller PCB. (terminal 1-3)
(Power supply to Remote Control)
Indicate or Display:
Outdoor unit :
POWER
MODE
ERROR
2
5
(L1)
(L2)
(L6)
(L5)
(L4)
(L3)
15
PUMP
DOWN
LOW
NOISE
PEAK
CUT
02-08
Economy lamp : Continuous flash.
ERROR CODE : [E : 12]
Indoor Unit : Operation lamp: 1 time Flash,
Timer lamp: 2 time Flash