31
5.4 (18) Analog output check
Description
Check the analog output circuit.
Check to make sure that the output values at -20% to 120% are 0.8mA to 23.2mA.
Connect an ammeter to the Iout terminal as shown below.
Operation (example) Check of analog output of 4mA, 8mA, 12mA, 16mA, 20mA
Key operation
FUNC SYSTEM
or
0 , ENTER
2 5 , ENTER
5 0 , ENTER
7 5 , ENTER
1 0 0 , ENTER
ESC ESC
Description
Select “Analog output check”.
Enter “0” with ten keys.
[0% (4mA) check]
Enter “25” with ten keys.
[25% (8mA) check]
Enter “50” with ten keys.
[50% (12mA) check]
Enter “75” with ten keys.
[75% (16mA) check]
Enter “100” with ten keys.
[100% (20mA) check]
Press the key twice.
OUTPUT CHECK
0 %
(Measurement display)
Display
OUTPUT CHECK
0 %
Iout
Ammeter
TRout 1
1
2
3
4
OUTPUT CHECK
25 %
OUTPUT CHECK
50 %
OUTPUT CHECK
75 %
OUTPUT CHECK
100 %