Command "OL" can be used to switch the optional measured values to any of the remaining
5 analogue outputs; see Command "OL".
Scaling of certain measured values to the voltage output is also possible. Wind direction, direction
of brightness and precipitation status are fixed values, which are not scalable.
By default, the analog channels are linked always in the same way. Measuring values, missing by
partial configuration level, and erroneous measuring values are treated acc. to the command "EI"
(Error Inversion).
The following table lists the selectable parameters and factory-set scaling:
Parameter
Measured value
Scaling
Analogue output
AB80106
Air pressure
800...1060hPa
0...10V
AH00100
Relative humidity
0...100%
0...10V
AL00120
Brightness
0...120klux
0...10V
AP00100
Precipitation intensity
0...100mm/h
0...10V
AQ00100
Daily sum of precipitation 0...100mm/d
0...10V
AP00000
Präzipitation Status
0 / 1
0 / 10V
AT14060
Air temperature
-40...+60°C
0...10V
AR00060
Wind speed
0...60m/s
0...10V
Fixed scale
Wind direction
0°…360°
0...10V
Fixed scale
Brightness direction
0°…360°
0...10V
Table 6: Factory-set Scaling of analogue outputs
7.2.1 North correction
The command NC can be used to shift the angle measured for wind direction by an angle offset in
a positive direction. The device adds the value input to the angle measured for the wind direction. If
the resulting value is greater than 360°, 360° is subtracted from the corrected angle value. This
setting is used whenever it is not possible to align the WEATHER STATION exactly to north and
this angle needs to be electronically corrected afterwards.
See also
If a wind speed < 0.1m/s is calculated, the wind direction is set to zero. The wind direction 0° is
reserved for no wind.
In contrast to no wind, the precise wind direction north, i.e. 0°, is output as 360° with wind speeds >
0.1m/s.