50 - 70
71130/11E/0318
Example: OL=12789 means:
output 4 (PIN:N) = relative humidity
output 5 (PIN:C) = air pressure
output 6 (PIN:B) = brightness
output 7 (PIN:A) = direction of brightness
output 8 (PIN:P) = precipitation intensity
Note:
The first 3 measured values have fixed linking to the
analogue outputs, cannot be changed and are linked as follows:
output 1 (PIN:T) = wind speed
output 2 (PIN:S) = wind direction
output 3 (PIN:O) = temperature / virtual temperature
Value range:
0...99999
Initial value:
12789
Command OP
<id>OP<para5>
Possible parameter for the output of calculated values (Optional Param.)
Access:
Configuration mode (ADMIN).
Description:
By means of this parameter, it is possible to output additionally to each telegram
–
excepted the NMEA telegram (TR5/TT5) the parameters stated below. The output is
carried out always after the measuring values, and before date/time resp. before the
checksum, see parameter DT. The order is defined by the position from left to right in
the parameter.
When the parameter OP=14, first, the value „absolute humidity“ is
added to
the measuring values, and then the value “heat index temperature”.
Parameter description:
0:
No additional values in the output telegram (off).
1:
Output of the calculated absolute humidity.
2:
Output dew point temperature.
3:
Output of wind-chill temperature (valid if the air temperature <10°C).
4:
Output of heat index temperature (valid if the air temperature >26°C
and rel. humidity >40%).
5:
Output of direction of magnetic compass (optional).
Value range:
00000...55555
Initial value:
0 (see factory setting: supplement sheet)
Command OR
<id>OR<para5>
Telegram output interval (Output Rate).
Access:
Configuration mode (ADMIN).
Description:
When the telegram output is autonomous, the time distance between the telegrams is
specified by means of this parameter. The selection is carried out in increments of
milliseconds. If the output rate is higher than the data transmission speed, the
upcoming output is rejected. If the output repetition rate is several times faster than the
measuring value acquisition, the available measuring values are double- or multiple-
output.
Parameter description:
10..60000
Specifies the output interval in milliseconds.
Value range:
0..60000 [ms]
Initial value:
1000 (see factory setting: supplement sheet).