31
http://www.fsp-group.com.tw/en/product/PVInverter.html
22
Max. charging current
Default 60A, 5~60A
23
Max. AC charging current
Default 60A, 5~60A
24
Bulk charging voltage
Default 56.0V, 50~62V
25
Floating charging voltage
Default 54V, Range 50~62V
26
Stop discharge voltage when
grid unavailable
Default 42V, Range 40~51V
27
Stop discharge voltage when
grid available
Default 48V, Range 40~51V
28
Start discharge voltage when
grid available
Default 54V, Range 42~62V
29
Start discharge voltage when
grid unavailable
Default 54V, Range 42~62V
2A
Max. battery discharging
current in hybrid mode
Default 150A, 20~150A
2B
Generator compatible
Enabled
Disabled (default)
2C
LCD backlight sleep timer
Backlight on
Default 60s, Range 0~100s
2D
Alarm control
Alarm on
(default)
Alarm off
31
Real time setting – Minute
Default 00, Range 00 ~ 59
32
Real time setting – Hour
Default 00, Range 00 ~ 23
33
Real time setting – Date
Default 01, Range 01 ~ 31
34
Real time setting – Month
Default 01, Range 01 ~ 12
35
Real time setting – Year
Default 16, Range 16 ~ 99