Every 2 months
-
If present: clean the coolant return filter on the outside of the unit and replace the
filter element if necessary
Every 6 months
-
Gas purge the cooler
Every 6 months in 3-shift operation with ethanol-based coolant
-
Gas purge the cooler
-
Change the coolant
Every 12 months in single-shift operation with ethanol-based coolant
-
Change the ethanol-based coolant
Every 12 months in 3-shift operation with FCL 10/20 coolant
-
Change the coolant
-
CU1200i Pro /MC only: clean the coolant pre-filter in the interior of the unit and re-
place the filter insert if necessary
Every 24 months in single-shift operation with FCL 10/20 coolant
-
Change the coolant
Cleaning the
coolant return fil-
ter on the outside
of the unit
WARNING!
Danger from welding current and accidental ignition of an arc.
This can result in serious injury and damage to property.
▶
Disconnect the ground earth connection between the welding system and the work-
piece.
▶
Remove the wire electrode from the welding torch being used.
▶
Depending on the system, remove the wirespool or the basket-type spool from the
power source or the wirefeeder.
1
57
EN
Summary of Contents for CU 1100i
Page 2: ......
Page 16: ...16...
Page 17: ...General information 17...
Page 18: ...18...
Page 26: ...26...
Page 27: ...Connections and mechanical com ponents 27...
Page 28: ...28...
Page 31: ...Installation and commissioning 31...
Page 32: ...32...
Page 45: ...Close the cover on the cooling unit connection 3 45 EN...
Page 46: ...46...
Page 47: ...Troubleshooting 47...
Page 48: ...48...
Page 53: ...Care maintenance and disposal 53...
Page 54: ...54...
Page 70: ...70...
Page 71: ...Technical data 71...
Page 72: ...72...
Page 82: ...82...
Page 83: ...83 EN...