Technical information | 4
M2250322_en | Installation instructions Wood chip boiler T4e 200-350
23
Regulation (EU) 2015/1189 – emissions in [mg/m³]
1)
Annual space heating emissions of dust (PM)
≤ 30
Annual space heating emissions of gaseous organic compounds
(GOC)
≤ 20
Annual space heating emissions of carbon monoxide (CO)
≤ 380
Annual space heating emissions of nitrogen oxides (NO
x
)
≤ 200
1. The emissions of dust, gaseous organic compounds, carbon monoxide and nitrogen oxides are stated in a standardised form based on dry flue gas with a oxygen content of 10 % and
under standard conditions at 0°C and 1013 millibar
4.4.2 T4e 200 - 250 ESP
Description
T4e 200 - 250 ESP
200
230
250
Nominal heat output
kW
199
230
250
Electrical connection
400 V / 50 Hz / C16A
Weight of boiler (including stoker, without water)
kg
2500
Boiler capacity (water)
l
438
Available feed height of pump
1)
(with ΔT = 20K)
mbar
446
340
273
Max. permitted operating temperature
°C
90
Permitted operating pressure
bar
4
Boiler class as per EN 303-5: 2012
5
Airborne sound level
dB(A)
< 70
Permitted fuel as per EN ISO 17225
2)
Part 2: Wood pellets class A1 / D06
Part 4: Wood chips class A1+A2 / P16S-P31S
Test book number
PB 142
PB 206
PB 143
1. Pump output less water resistance in the boiler
2. Detailed information on the fuel can be found in the operating instructions in the section entitled “Permitted fuels”
Regulation (EU) 2015/1187 – ηs in [%]
Heating space annual rate of use ηs
≥ 78
Additional data for regulation (EU) 2015/1189
Description
T4e 200 – 250 ESP
200
230
250
Heating up mode
automatic
Condensing boiler
No
Solid fuel boiler for combined heat and power
No
Combined heating system
No
Storage tank volume
Characteristics when operated exclusively with the preferred fuel
Useful heat delivered at rated heat output (P
n
)
kW
199
230
250
Useful heat delivered at 30% of rated heat output (P
p
)
59.7
69.0
75.0
Fuel efficiency at rated heat output (η
n
)
%
83.8
83.9
83.9
Fuel efficiency at 30% of rated heat output (η
p
)
83.7
83.7
83.7