background image

11

920-159-02

5) Indoor Air

fl

 ow Data

The Vert-I-Pak A series units must be installed with a free return air 
confi guration.  The table below lists the indoor airfl ow at corresponding 
static pressures.  All units are shipped from the factory and are rated 
at low speed.

To change to high speed replace the low speed lead (blue) with the 
high speed lead (black) on the blower relay.

6) Chassis Installation

NOTE:  Prior to installing the chassis, ensure that the drain pan and 
line are free from debris.

A.  Ensure that the wall ple num is in stalled in ac cor dance with 

the VPAWP1-8/1-14 Installation Manual.

B.  Ensure that the VPDP1 drain pan is installed correctly (see 

page 8). Using the 3/4" plugs supplied with the pan, plug 
the unused condensate drain hole. Connect a drain to the 
condensate exit location.  Be sure to use tefl on tape or 
approved pipe sealant on all drain connections and plugs  
(see page 8).

C.  Place the chassis into the closet with the outdoor side 

facing the wall plenum opening.

D.  Slide the chassis into the wall plenum until the plenum 

divider seal is established and the factory-installed chassis 
to plenum gasket has sealed to the top fl ange of the 
plenum. (See Figure 10)

All values listed are inches 
W.C. with a wet indoor coil 
with fi lter installed.

 

 

2

3

/

8

Chassis to 
plenum gasket

The Vert-I-Pak chassis must be inserted into 
the wall plenum so that the plenum divider 
gas ket makes contact with the condenser 
baffle in the unit. The chassis will fit 
ap prox i mate ly 2

3

/

8

" into the wall plenum.

NOTE:  Prior to installing the chas sis, 
ensure that the drain pan and line are free 
from debris.

Slide-in View / Chassis Installation

Figure 10

VEA/VHA24K

Low

High

.1” ESP

750

815

.2” ESP

725

780

.3” ESP

700

745

.4” ESP

675

700

Summary of Contents for Vert-I-Pak VEA24 Series

Page 1: ...920 159 02 10 06 VERT I PAK A SERIES SINGLE PACKAGE VERTICAL AIR CONDITIONINGSYSTEM 24 000 BTU h INSTALLATION OPERATION GUIDE...

Page 2: ...Thermostat Control 12 10 Low Ambient Protection for Compressor Fan 12 11 Heating Defrost Heat Pump Models only 12 12 Fresh Air Door 13 13 Condensate Disposal System 13 IV Service Maintenance Warranty...

Page 3: ...a clearance of 24 from the outdoor louver should be maintained For major obstructions such as a solid fence wall or other heat rejecting device like a condensing unit a mini mum distance of 72 should...

Page 4: ...llar accepts 10 flex duct Section I General Specifications Vert I Pak Model Identification Guide ELECTRIC HEATER SIZE A Series 25 2 5 KW 34 3 4 KW 50 5 0 KW 75 7 5 KW MODEL NUMBER V E A 09 K 34 RT H E...

Page 5: ...p x 47 1 4 high VPAWP1 8 1 14 Wall Plenum cut out dimensions 24 5 8 wide x 30 7 8 high VPRG4 Access Panel cutout dimensions 27 wide by 55 3 4 high See Figure 8 Page 10 for proper chassis installation...

Page 6: ...side wall plenum Part A Inside Wall Plenum Part B Wall Plenum Outdoor Louver Installation Rough opening dimension 24 5 8 wide x 30 7 8 high Ensure that the bottom of the plenum is 1 1 2 from the floor...

Page 7: ...Sample Nameplate see your chassis nameplate MODEL VHA VEA24K25 VHA VEA24K34 VHA VEA24K50 VHA VEA24K75 Voltage V 230 208 230 208 230 208 230 208 LRA Comp A 68 68 68 68 Cooling Current A 13 7 12 4 13 7...

Page 8: ...branch circuit or general purpose outlet is grounded Wire Sizing Use recommended wire size given in tables and installasinglebranchcircuit Allwiringmustcomply with local and national codes NOTE Use co...

Page 9: ...2 5 KW 3 4 KW HEATER BLACK SEE NOTE 6 PRESSURE WHITE RELAY HEAT RELAY HEAT RELAY HEAT RELAY HEAT BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK RED RED RED RED RED RED RED RED 2 5KW 3 4KW 5 KW...

Page 10: ...ccessories for installation details Return Air Grille Options Figure 9 Field Supplied Return Air Grille Must have a minumum of 250 square inches of free area VPRG4 Return Air Grille with Access Panel...

Page 11: ...n to the condensate exit location Be sure to use teflon tape or approved pipe sealant on all drain connections and plugs see page 8 C Place the chassis into the closet with the outdoor side facing the...

Page 12: ...ticallyswitchestoelectricheatduring defrost Whentheoutdoorambienttemperaturedropsbelowa45 F factory setting the chassis automatically switches to electric heat As outdoor ambient temperatures rise abo...

Page 13: ...can be accomplished easily by referring to the following directions However before performing any maintenance consider these important safety precautions WARNING ElectricalShockHazard Beforeattemptin...

Page 14: ...e Friedrich Air Conditioning Company International Division Any defective part to be replaced must be made available to FRIEDRICH in exchange for the replacement part Reasonable proof must be presente...

Page 15: ...pecial color to match the exterior wall ARCHITECTURAL LOUVER Extruded aluminum louver that attaches to the outdoor section of the wall plenum DIMENSIONS 31 1 16 high x 25 9 16 wide Same as VPAWP1 8 bu...

Page 16: ...tory Certified Parts FRIEDRICH AIR CONDITIONING CO Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 Fax 210 357 4480 www friedrich c...

Reviews: