background image

4

920-159-02

Vert-I-Pak

®

 Chassis Speci

fi

 cations

MODEL: V(E,H)A24

Voltage (V)

230/208

Refrigerant

R-22

Chassis Width

23.125

Chassis Depth

23.125

Chassis Height **

47.25

Supply Duct Collar ***

10"

Drain Connection

3/4" FPT

Min. Circuit Amps

See Nameplate

CFM Indoor

See chart, pg. 11

Max. Duct ESP

.4 in. water

NOTES:  
**   Height includes 2" duct collar & isolators under unit.
*** Factory collar accepts 10" fl ex duct. 

 

 
 

   

 

   

Section I.  General Speci

fi

 cations

Vert-I-Pak

®

 Model Identi

fi

 cation Guide

ELECTRIC HEATER SIZE

A Series
25  =   2.5 KW
34  =   3.4 KW
50  =   5.0 KW*
75  =   7.5 KW**

MODEL NUMBER 

V  E  A  09  K  34  RT  H

EN GI NEER ING CODE

OPTIONS

RT = Stan dard Re mote Op er a tion

*  Not available on 9000 BTU models.
** 24000 BTU only. 

VOLTAGE

K = 208/230V-1Ph-60Hz

 NOMINAL CAPACITY

A Series (Btu/h)
09 =   9,000
12 = 12,000

DESIGN SERIES

A = 32"/47" Cabinet

SERIES

V=Vertical Series

18 = 18,000
24 = 24,000

 E =Cooling with electric heat
 H =Heat Pump

Refer to electrical data chart for heater/unit compatibility.

Summary of Contents for Vert-I-Pak VEA24 Series

Page 1: ...920 159 02 10 06 VERT I PAK A SERIES SINGLE PACKAGE VERTICAL AIR CONDITIONINGSYSTEM 24 000 BTU h INSTALLATION OPERATION GUIDE...

Page 2: ...Thermostat Control 12 10 Low Ambient Protection for Compressor Fan 12 11 Heating Defrost Heat Pump Models only 12 12 Fresh Air Door 13 13 Condensate Disposal System 13 IV Service Maintenance Warranty...

Page 3: ...a clearance of 24 from the outdoor louver should be maintained For major obstructions such as a solid fence wall or other heat rejecting device like a condensing unit a mini mum distance of 72 should...

Page 4: ...llar accepts 10 flex duct Section I General Specifications Vert I Pak Model Identification Guide ELECTRIC HEATER SIZE A Series 25 2 5 KW 34 3 4 KW 50 5 0 KW 75 7 5 KW MODEL NUMBER V E A 09 K 34 RT H E...

Page 5: ...p x 47 1 4 high VPAWP1 8 1 14 Wall Plenum cut out dimensions 24 5 8 wide x 30 7 8 high VPRG4 Access Panel cutout dimensions 27 wide by 55 3 4 high See Figure 8 Page 10 for proper chassis installation...

Page 6: ...side wall plenum Part A Inside Wall Plenum Part B Wall Plenum Outdoor Louver Installation Rough opening dimension 24 5 8 wide x 30 7 8 high Ensure that the bottom of the plenum is 1 1 2 from the floor...

Page 7: ...Sample Nameplate see your chassis nameplate MODEL VHA VEA24K25 VHA VEA24K34 VHA VEA24K50 VHA VEA24K75 Voltage V 230 208 230 208 230 208 230 208 LRA Comp A 68 68 68 68 Cooling Current A 13 7 12 4 13 7...

Page 8: ...branch circuit or general purpose outlet is grounded Wire Sizing Use recommended wire size given in tables and installasinglebranchcircuit Allwiringmustcomply with local and national codes NOTE Use co...

Page 9: ...2 5 KW 3 4 KW HEATER BLACK SEE NOTE 6 PRESSURE WHITE RELAY HEAT RELAY HEAT RELAY HEAT RELAY HEAT BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK RED RED RED RED RED RED RED RED 2 5KW 3 4KW 5 KW...

Page 10: ...ccessories for installation details Return Air Grille Options Figure 9 Field Supplied Return Air Grille Must have a minumum of 250 square inches of free area VPRG4 Return Air Grille with Access Panel...

Page 11: ...n to the condensate exit location Be sure to use teflon tape or approved pipe sealant on all drain connections and plugs see page 8 C Place the chassis into the closet with the outdoor side facing the...

Page 12: ...ticallyswitchestoelectricheatduring defrost Whentheoutdoorambienttemperaturedropsbelowa45 F factory setting the chassis automatically switches to electric heat As outdoor ambient temperatures rise abo...

Page 13: ...can be accomplished easily by referring to the following directions However before performing any maintenance consider these important safety precautions WARNING ElectricalShockHazard Beforeattemptin...

Page 14: ...e Friedrich Air Conditioning Company International Division Any defective part to be replaced must be made available to FRIEDRICH in exchange for the replacement part Reasonable proof must be presente...

Page 15: ...pecial color to match the exterior wall ARCHITECTURAL LOUVER Extruded aluminum louver that attaches to the outdoor section of the wall plenum DIMENSIONS 31 1 16 high x 25 9 16 wide Same as VPAWP1 8 bu...

Page 16: ...tory Certified Parts FRIEDRICH AIR CONDITIONING CO Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 Fax 210 357 4480 www friedrich c...

Reviews: