5

920-159-02

electrical 

entrance

control box

Fig ure  4

Top View

II.  Installation

1)  Utility Closet Dimensions

Recommended utility closet dimensions and a typical indoor installation are illustrated in Figure 1.  Three inches minimum clearance on 
three sides of the unit must be allowed for return airfl ow, installation access and service access.  See Figures 1 & 2 for clear anc es and 
ref er ence di men sions.

NOTE: Drain pan must be installed in closet prior to chassis 
insertion into plenum. See Figure 7 (page 8) for drain pan 
installation details.

•  Vert-I-Pak Chassis 2-ton dimensions:  

23" wide x 23" deep x 47 1/4" high.

•  VPAWP1-8/1-14  Wall Plenum cut-out 

dimensions 24 5/8" wide x 30 7/8" high.

•  VPRG4 Access Panel cutout dimensions: 

27" wide by 55 3/4" high.

•  See Figure 8 (Page 10) for proper 

chassis installation.

Fig ure  3

Typical Utility Closet

Chassis Shown in Closet, on Optional Platform

Exterior Wall

Flexi

b

le Ductwork

Rigid Ductwork

VPAWP1-8/1-14 Wall Plenum

Plenum 

VPDP1 drain pan 

b

eneath unit is 

required on all 
VEA/VHA24 units. 
Drain pan must 

b

installed prior to 
chassis installation 

Chassis is 
shipped with 
vi

b

ration 

isolators 
installed

3" Clearance on all 

three sides minimum for 

service and installation

Optional Platform

Field-supplied 
Filter (25" x 20")

58"

29"

Optional field 

installed drain pan 

(refer to local codes)

VPRG4 Access Panel & 
Return Air Filter Grille

Power 
Disconnect

Outside Wall

Summary of Contents for Vert-I-Pak VEA24 Series

Page 1: ...920 159 02 10 06 VERT I PAK A SERIES SINGLE PACKAGE VERTICAL AIR CONDITIONINGSYSTEM 24 000 BTU h INSTALLATION OPERATION GUIDE...

Page 2: ...Thermostat Control 12 10 Low Ambient Protection for Compressor Fan 12 11 Heating Defrost Heat Pump Models only 12 12 Fresh Air Door 13 13 Condensate Disposal System 13 IV Service Maintenance Warranty...

Page 3: ...a clearance of 24 from the outdoor louver should be maintained For major obstructions such as a solid fence wall or other heat rejecting device like a condensing unit a mini mum distance of 72 should...

Page 4: ...llar accepts 10 flex duct Section I General Specifications Vert I Pak Model Identification Guide ELECTRIC HEATER SIZE A Series 25 2 5 KW 34 3 4 KW 50 5 0 KW 75 7 5 KW MODEL NUMBER V E A 09 K 34 RT H E...

Page 5: ...p x 47 1 4 high VPAWP1 8 1 14 Wall Plenum cut out dimensions 24 5 8 wide x 30 7 8 high VPRG4 Access Panel cutout dimensions 27 wide by 55 3 4 high See Figure 8 Page 10 for proper chassis installation...

Page 6: ...side wall plenum Part A Inside Wall Plenum Part B Wall Plenum Outdoor Louver Installation Rough opening dimension 24 5 8 wide x 30 7 8 high Ensure that the bottom of the plenum is 1 1 2 from the floor...

Page 7: ...Sample Nameplate see your chassis nameplate MODEL VHA VEA24K25 VHA VEA24K34 VHA VEA24K50 VHA VEA24K75 Voltage V 230 208 230 208 230 208 230 208 LRA Comp A 68 68 68 68 Cooling Current A 13 7 12 4 13 7...

Page 8: ...branch circuit or general purpose outlet is grounded Wire Sizing Use recommended wire size given in tables and installasinglebranchcircuit Allwiringmustcomply with local and national codes NOTE Use co...

Page 9: ...2 5 KW 3 4 KW HEATER BLACK SEE NOTE 6 PRESSURE WHITE RELAY HEAT RELAY HEAT RELAY HEAT RELAY HEAT BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK RED RED RED RED RED RED RED RED 2 5KW 3 4KW 5 KW...

Page 10: ...ccessories for installation details Return Air Grille Options Figure 9 Field Supplied Return Air Grille Must have a minumum of 250 square inches of free area VPRG4 Return Air Grille with Access Panel...

Page 11: ...n to the condensate exit location Be sure to use teflon tape or approved pipe sealant on all drain connections and plugs see page 8 C Place the chassis into the closet with the outdoor side facing the...

Page 12: ...ticallyswitchestoelectricheatduring defrost Whentheoutdoorambienttemperaturedropsbelowa45 F factory setting the chassis automatically switches to electric heat As outdoor ambient temperatures rise abo...

Page 13: ...can be accomplished easily by referring to the following directions However before performing any maintenance consider these important safety precautions WARNING ElectricalShockHazard Beforeattemptin...

Page 14: ...e Friedrich Air Conditioning Company International Division Any defective part to be replaced must be made available to FRIEDRICH in exchange for the replacement part Reasonable proof must be presente...

Page 15: ...pecial color to match the exterior wall ARCHITECTURAL LOUVER Extruded aluminum louver that attaches to the outdoor section of the wall plenum DIMENSIONS 31 1 16 high x 25 9 16 wide Same as VPAWP1 8 bu...

Page 16: ...tory Certified Parts FRIEDRICH AIR CONDITIONING CO Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 Fax 210 357 4480 www friedrich c...

Reviews: