7 Operation
7
32
Rittal Liquid Cooling Package
If DHCP is not used in your network: Activate the
bootswitch parameters (see section 7.2.2 "Switching
off the LCP DX and the external condenser").
Open the browser and enter the IP address of the
pCO Web card in the address line, together with the
suffix "/config".
Example of a static IP address:
http://172.16.0.1/config
The following dialogue will appear for logging on to
the Web server.
Fig. 35:
Authentication on the pCO Web card
Enter
admin
as the user and
fadmin
as the pass-
word.
Once you have successfully logged in, the homepage of
the pCO Web card will launch.
Fig. 36:
Homepage of the pCO Web card
7.13.3 Configure the network interface
Network settings are made under the menu point
Con-
figuration
>
Network
. Here, you can assign an
IP address and up to three aliases to the network inter-
face. The aliases do not have their own gateway ad-
dress.
Fig. 37:
Network configuration
Enter the fixed IP address via which you wish to ac-
cess the network interface under
Eth0
in the
IP Ad-
dress main
field.
Alternatively, you may leave this field blank or enter
DHCP
if you would like an IP address to be automat-
ically assigned to the network interface via DHCP.
If applicable, enter the corresponding alias addresses
in the
IP Alias 1
,
IP Alias 2
and
IP Alias 3
fields.
Transfer these changes to the controller by clicking on
the
Submit
button.
Reboot to activate the changes.
7.13.4 E-mail configuration
The parameters listed in the supervisory table (see
section 7.13.5 "LCP DX supervisory table") can be used
to configure various events for notification by e-mail.
The procedure for configuration is described in the
original user instructions for the pCO Web card from
Carel.
These instructions can be found at the following ad-
dress:
http://www.carel.com/carelcom/web/eng/catalogo/
prodotto_dett.jsp?id_gamma=39&id_prodot-
to=350&id_mercato=4
Caution! Risk of malfunction or damage!
Double-clicking on a variable will open
the variables window.
Every variable represented by the pCO
Web controller can be edited, provided
you have write permission. Editing these
variables could result in an LCP DX mal-
function. Download the list of data points
from the website shown in the Foreword,
and use this list to check the meaning of
the variables and their minimum and max-
imum values.