11 Technical specifications
11
44
Rittal Liquid Cooling Package
11
Technical specifications
11.1 LCP Rack DX/LCP Inline DX
Technical specifications
Description/Model No.
LCP Rack DX / 3313.290 (1200 mm depth)
Description/Model No.
LCP Inline DX / 3313.390 (1200 mm depth)
Dimensions and weight
Dimensions width x height x depth (W x H x D) [mm]
300 x 2000 x 1200
U height
42
Weight, max. [kg]
239
Electrical connection
Type of electrical connection
Connection clamp
Short-circuit current
10 kA on 3-phase plant
Rated voltage [V, Hz]
380…480 V ±10 %, 3~, N, PE, 50/60 Hz
Rated current [A]
12.4
Startup current [A]
18.2
Pre-fuse T [A]
32
Duty cycle [%]
100
Cooling output
Nominal cooling capacity EN 14511 [kW]
L35 L35 20,0
L35 L30 20,0
Total power input [kW]
L35 L35 7,3
L35 L30 6,0
Energy Efficieny Ratio (EER) L35 L35
2.74
Air throughput, max. [m
3
/h]
4.800
Cooling circuit
Coolant/Fill volume [kg]
R410A/see tab. 22 "Total refrigerant charge"
Max. allowable pressure [bar]
PS HP: 42
PS LP: 30
Connection diameter refrigerant pipes [mm]
See tab. 23 "Refrigerant pipes"
External diameter of coolant lines [mm]
See tab. 23 "Refrigerant pipes" (1mm wall thickness)
Other information
Storage temperatures [°C]
-20…+50
Temperature range [°C]
+15…+35 (indoor)
Relative humidity range [%]
10…90
Max. height above sea level [m]
2500
Tab. 17:
Technical specifications LCP DX