11 Technical specifications
11
48
Rittal Liquid Cooling Package
11.5 Total refrigerant charge
11.6 Refrigerant pipes
Connection diameter LCP DX 20 kW: 12 mm/12 mm
System: LCP DX + con winter kit mod-
ule (in case of it)
Fill volume up to a line length
of 5 m [kg]
Fill volume per metre above
5 m [kg]
System with standard condenser
5.0
0.05
System with low temperature condenser and winter
kit module
6.0
0.05
System with high temperature condenser
5.7
0.05
Tab. 22:
Total refrigerant charge
Type of
condenser
Connection diameter condenser
liquid line/hot gas line
[mm]
Equivalent
length
External diameter of coolant lines
liquid line/hot gas line
[mm]
Standard
22/22
Up to 20 m
12/16
20 m to 45 m
16/16
Low temperature
22/22
Up to 20 m
12/16
20 m to 45 m
16/16
High temperature
28/28
Up to 20 m
12/16
20 m to 45 m
16/16
Tab. 23:
Refrigerant pipes