8 Troubleshooting
8
38
Rittal Liquid Cooling Package
8.3
List of error messages and solutions
Alarm code
Display
Possible cause
Possible solution
ALA02
Alarms ALA02
Position: B2
Probe B2 faulty or disconnected
alarm
Sensor failure or sensor not cor-
rectly connected.
Check the connection on the moth-
erboard or replace the sensor.
ALA03
Alarms ALA03
Position: B3
Probe B3 faulty or disconnected
alarm
Sensor failure or sensor not cor-
rectly connected.
Check the connection on the moth-
erboard or replace the sensor.
ALA04
Alarms ALA04
Position: B4
Probe B4 faulty or disconnected
alarm
Sensor failure or sensor not cor-
rectly connected.
Check the connection on the moth-
erboard or replace the sensor.
ALA06
Alarms ALA06
Position: B6
Probe B6 faulty or disconnected
alarm
Sensor failure or sensor not cor-
rectly connected.
Check the connection on the moth-
erboard or replace the sensor.
ALA07
Alarms ALA07
Position: B7
Probe B7 faulty or disconnected
alarm
Sensor failure or sensor not cor-
rectly connected.
Check the connection on the moth-
erboard or replace the sensor.
ALA08
Alarms ALA08
Position: B8
Probe B8 faulty or disconnected
alarm
Sensor failure or sensor not cor-
rectly connected.
Check the connection on the moth-
erboard or replace the sensor.
ALA09
Alarms ALA09
Position: B9
Probe B9 faulty or disconnected
alarm
Sensor failure or sensor not cor-
rectly connected.
Check the connection on the moth-
erboard or replace the sensor.
ALA10
Alarms ALA10
Position: B10
Probe B10 faulty or disconnected
alarm
Sensor failure or sensor not cor-
rectly connected.
Check the connection on the moth-
erboard or replace the sensor.
ALA11
Alarms ALA11
Position: B11
Probe B11 faulty or disconnected
alarm
Sensor failure or sensor not cor-
rectly connected.
Check the connection on the moth-
erboard or replace the sensor.
ALA12
Alarms ALA12
Position: B12
Probe B12 faulty or disconnected
alarm
Sensor failure or sensor not cor-
rectly connected.
Check the connection on the moth-
erboard or replace the sensor.
ALB01
Alarms ALB01
Position: ID3
High pressure
High ambient temperature, incor-
rect coolant filling, defective fan.
Check device limits, check coolant
volume and check correct function-
ing of fan.
ALB02
Alarms ALB02
High pressure compressor 1 by
transducer
High ambient temperature, incor-
rect coolant filling, defective fan.
Check device limits, check coolant
volume and check correct function-
ing of fan.