FR500D Series Special Purpose Inverter for Elevator
- 35 -
H00.37
Err41 overload reset time
timing
0s
⊙
H00.38
Err41 overload times
0
⊙
When Err41 overload fault, system will record Err41 overload fault times which is displayed in
H00.38. When fault reset, if no again Err41 within setting time (H00.35), zero clearance in H00.38; If
again Err41 within setting time H00.35, the value will be accumulated in H00.38, when the value
H00.38 is bigger than the value H00.34, system will forbid Err41 reset, only after setting time H00.36
can reset Err41. H00.37 FOR reset time timing.
F03.11
S curve Time 1
0.00
~
600.00s
1.00s
×
F03.15
S curve Time 2
0.00
~
600.00s
1.00s
×
F03.16
S curve Time 3
0.00
~
600.00s
1.00s
×
F03.17
S curve Time 4
0.00
~
600.00s
1.00s
×
H00.39
S curve Time 5
0.00
~
60.00s
1.00s
△
H00.40
S curve Time 6
0.00
~
60.00s
0.50s
△
S curve time setting:
H00.05
High
Speed
DC injection
Leveling
Speed
F03.11
F03.15
F03.16
F03.17
H00.39
H00.40
Hz
H00.41
Coefficient of S curve
time when short floor
function is enabled
0.00
~
1.00
0.7
△
When short floor function is enabled and triggered, deceleration time will multiple this coefficient
set by H00.41.
H00.42
Percentage of torque
boost when leveling
0.0
~
120.0%
0.0%
×
H00.43
Torque boost Kp when
leveling
0.000
~
1.000
0.100
△
H00.44
Torque boost Ki when
leveling
0.000
~
1.000
0.300
△
H00.45
Duration for torque boost
0.0
~
10.0s
1.0s
△
This Four function codes are used to increase the torque when leveling.