FR500D Series Special Purpose Inverter for Elevator
- 31 -
(Falling)
H00.08
Brake Release
Frequency (Falling)
0.00
~
10.00Hz
0.20Hz
×
H00.09
Brake Open Current
0.0
~
100.0%
40.0%
△
H00.10
Brake Open Frequency
Holding Time
0.00
~
10.00s
0.30s
×
H00.15
Running Contactor
Release Delay
0.00~10.00s
0.20s
×
H00.16
Running Contactor Open
Delay
0.00~10.00s
0.10s
×
H00.17
Stop DC Injection Time ,
0.00~10.00s
0.50s
×
Setting function code H00.01~H00.10 and H00.15~H00.17 can improve the comfort when
elevator start star/stop, DC brake current when braking to stop can be adjusted by F02.14, every
function code shown as below:
FWD/REV
Run
Brake
H00.0
1
H00.1
0
H00.05
H00.02
H00.0
3
H00.06
H00.1
7
Multi-Speed
Current
H00.09
Motor Contactor
H00.1
5
H00.1
6
H00.0
4
DC injection
Figure 3.1 Elevator Operation Logic
H00.05(Brake Open Frequency (Rising)),H00.06(Brake Release Frequency (Rising)) and
H00.07(Brake Open Frequency (Falling)),H00.08(Brake Release Frequency (Falling)) are same
meanings, rising group use for frequency adjusting on FWD, falling group use for frequency adjusting
on REV.
H00.11
Brake Open Type
0: Open according to frequency
0
×
1: Open according to frequency &
current
0
:
Open according to frequency
Criteria for judging the brake opening is inverters output reach to the setting frequency of H00.05
(rising) or H00.07 (falling), and then open the brake by setting time of H00.01 (Brake Open Delay).
1: Open according to frequency and current
Criteria for judging the brake opening is inverters output reach to the setting frequency of H00.05
(rising) or H00.07 (falling), meanwhile, inverter current reach H00.09 (brake open current) setting
value.
H00.12
Emergency Operation
Frequency
0.00
~
50.00Hz
20.00Hz
△