FR500D Series Special Purpose Inverter for Elevator
- 32 -
When emergency signal input, inverters will entry emergency operating mode, the frequency of
H00.12 will be the operation frequency of inverter, and inverter will select accel/decel time 4 as current
accel/decel time.
H00.13
Maintenance Operation
Frequency
0.00
~
50.00Hz
20.00Hz
△
When maintenance signal input, the frequency of H00.13 will be the operation frequency of inverter
H00.14
Emergency Signal
Processing
0: Elevator no run
1
×
1: Elevator Powered on By UPS
And Run
0: 0: Elevator no run
When emergency signal input, inverter no output
1: Elevator Powered on By UPS And Run
When emergency signal input, inverter is powered by UPS and output via emergency operation
frequency
H00.18
Short Floor Function
0:Invalid
0
×
1:Short Floor Function
2:Senior Short Floor Function
0: Invalid
Short floor function is invalid
1: Short floor function
When elevator is running during short floor and when short floor function is triggered, inverter
will continue to run via setting speed of H00.19.
2
:
Senior short floor function
When elevator is running during short floor and when short floor function is triggered, inverter will
calculate remaining running time and maintain current frequency to run till remaining time finished
H00.19
Short Floor Speed
0.0
~
100.0%
60.0%
×
When H00.18=1, inverter run via speed of H00.19 when running in short floor
H00.20
Leveling Jerk
0.0~100.0%
0.0%
×
H00.21
Leveling Jerk Frequency
0.00~1.00
0.20
×
The parameters are used for improving the jerk when elevator stop
H00.22
Motor Mode Slip
0.00~3.00Hz
0.00Hz
×
The parameter used for improving the leveling when elevator is falling. If leveling is good when
elevator is falling with half load but leveling is not good when elevator is falling without load, to
increase the value of H00.02 to improve the leveling.
H00.23
Generator Mode Slip
0.00~3.00Hz
0.00Hz
×
The parameter used for improving the leveling when elevator is rising. If leveling is good when elevator
is rising with half load but leveling is not good when elevator is rising without load, to increase the
value of H00.23 can improve the leveling.
H00.24
Emergency Signal Valid
Time
0.0
~
500.0s
10.0s
×
H00.25
Emergency Signal Invalid
Time
0.0
~
1000.0s
180.0s
×
H00.33
Emergency signal
running invalid time
0.0
~
1000.0s
60.0s
×
When emergency signal is valid, inverter start timing, when timing is over setting value of H00.24,
and when output terminal function (Y1 Y2 R1 R2) selected to be “32” the function of emergency signal
time completed, the terminal output valid signal and last setting time of H00.25(if VFD is running then it
will last H00.33 setting time), then terminal output is invalid.