![Frecon FR500-4T-0.7G/1.5PB User Manual Download Page 70](http://html1.mh-extra.com/html/frecon/fr500-4t-0-7g-1-5pb/fr500-4t-0-7g-1-5pb_user-manual_2329263070.webp)
FR500A&FR510A Series Vector Control Inverter
- 70 -
F18.22
Find encoder origin at
beginning (FR510A only)
0: Not find
1: Find
1
×
F18.23
Encoder line number
(FR510A only)
0
~
10000
1024
×
F18.24
Encoder type
(FR510A only)
0: ABZ encoder
1: UVW encoder
2: Rotary encoder
3: ECN1313
4: Sine-cosine encoder
0
×
F18.25
AB Phase Sequence of
ABZ Incremental
Encoder (FR510A only)
0: Positive
1: Negative
0
×
F18.26
Speed feedback PG
disconnection detection
time (FR510A only)
0.0
:
Invalid
0.1
~
10.0s
0.0s
×
F18.27
Speed Ratio of Motor to
Encoder (FR510A only)
0.001
~
60.000
1.000
×
F18.28
Pole pairs of rotary
encoder
(FR510A only)
1
~
100
1
×
F18.30
Autotuning of motor 2
0: No autotuning
0
×
1: Static autotuning of motor
2: Rotary autotuning of motor
Group F19 V/f Control Parameters of Motor 2
F19.00
V/f curve setting
00: Linear V/F
0
×
01: Multi-stage V/F
02: 1.2nd power V/F
03: 1.4nd power V/F
04: 1.6nd power V/F
05: 1.8nd power V/F
06: 2.0nd power V/F
07: V/F complete separation
08: V/F half separation
09: 1.2 power inverse curve V/F
10: 1.4 power inverse curve V/F
11: 1.6 power inverse curve V/F
12: 1.8 power inverse curve V/F
13: 2.0 power inverse curve V/F
F19.01
Torque boost
0.1%–30.0% 0.0% (fixed torque
boost)
0.0%
△
F19.02
Cut-off frequency of
torque boost
0.00
~
Fmax
50.00Hz
△
F19.03
Multi-point V/F frequency
1(F1)
0.00
~
F19.05
0.00Hz
△
F19.04
Multi-point V/F voltage 1
(V1)
0.0
~
100.0
5.0%
△
F19.05
Multi-point V/F frequency
2(F2)
F19.03
~
F19.05
5.00Hz
△
F19.06
Multi-point V/F voltage 2
(V2)
0.0
~
100.0
14.0%
△
F19.07
Multi-point V/F frequency
3(F3)
F19.05
~
F19.09
25.00Hz
△
F19.08
Multi-point V/F voltage 3
(V3)
0.0
~
100.0
50.0%
△
F19.09
Multi-point V/F frequency
4(F4)
F19.07
~
rated motor frequency
50.00Hz
△
F19.10
Multi-point V/F voltage 4
(V4)
0.0
~
100.0
Ue=100.0%
100.0%
△