Fig. 6-14
F05.14
Consecutive running time
Range:0.0
~
6000.0Min
Default: 0.0Min
This parameter should be set with digital output terminal “Consecutive running time attained".
When current running time attains the value of F05.14, corresponding terminal outputs ON. Current
running time is cleared when stop. When this parameter value is set to 0.0, this function is invalid.
F05.15
Accumulative power-on time
Range:0
~
65535h
Default: 0h
This parameter should be set with digital output terminal “Accumulative power-on time attained".
When accumulative power-on time attains the value of F05.15, corresponding terminal outputs ON.
Accumulative power-on time is maintained when stop. When this parameter value is set to 0, this
function is invalid.
F05.16
Accumulative running time
Range:0
~
65535h
Default: 0h
This parameter should be set with digital output terminal “Accumulative running time attained".
When accumulative running time attains the value of F05.16, corresponding terminal outputs ON.
Accumulative running time is maintained when stop. When this parameter value is set to 0, this
function is invalid.
F05.17
Brake control selection
Range: 0
~
1
Default value: 0
0: Disabled
1: Enabled
F05.18
Brake open frequency
Range: 0.00
~
20.00Hz
Default value: 2.50Hz
F05.19
Brake open current
Range: 0.0
~
200.0%
Default value: 0.0%
F05.20
Brake open waiting time
Range: 0.00
~
10.00s
Default value: 0.00s
F05.21
Brake open operating time
Range: 0.00
~
10.00s
Default value: 0.50s
F05.22
Brake closed frequency
Range: 0.00
~
20.00Hz
Default value: 2.00Hz
F05.23
Brake close waiting time
Range: 0.00
~
10.00s
Default value: 0.00s
F05.24
Brake close operating time
Range: 0.00
~
10.00s
Default value: 0.50s
Scheme of brake control process: