FR200H Special Purpose Inverters for Multi-pumps Constant Pressure Water Supply
- 26 -
variable pump, with assisted pump, with timing rotate. Start current variable pump, when the
running frequency higher than frequency for add pumps, start H00.06 delay, if the frequency
still higher than frequency for add pumps after the delay, then start the other assisted pump.
When variable pump keep running within a certain time, no need to start assisted pumps, if the
time ,more than timing rotate time set by H00.12, then stop the current variable pump, switch
the assisted pump to variable pump.
H00.13
Gap of timing rotate
1
~
60000Min
240Min
×
Single variable mode:
when parts of power-frequency motor running, water supply system under
stable, to avoid parts of motor keep running in a long time, timing rotate time set for limit the longest
running time.
Multi variable mode:
when only variable pumps running, and keep running time more than set timing
rotate time, then stop the current running pump and switch to another variable pump.
H00.14
Inverter action selection
when adding or reducing
pump in single-variable
pump mode
0: Inverter stop
0
×
1: Inverter not stop
0:Inverter stop
In single-varialble pump mode, when adding or reducing pump , inverter will stop.
1: inverter not stop
In single-varialble pump mode, when adding or reducing pump , inverter will not stop.