FR200H Special Purpose Inverters for Multi-pumps Constant Pressure Water Supply   

- 7 - 

Table 1-3 FR200H Description of control circuit terminals 

Type 

Terminal 

Name 

Function Description 

Power supply 

 

+10V-GND 

Ex10 V 

power supply 

P10 V power supply to 
external unit. 
Generally, it provides power supply to 
externalpotentiometer with resistance 
range of 1–5 kΩ. 
Maximum output current: 10 mA 

+24V-COM 

Ex24V 

power 

supply Applying 

to Overvoltage 

Category II 

circuit 

P24 V power supply to 
external unit. 
Generally, it provides power supply to 
DI/Do terminals and external sensors. 
Maximum output current: 200 mA 

PLC 

Input terminal 

of 

external power 

supply 

Connect to +24 V by default. 
When DI1-DI7 need to be driven by 
externalsignal, PLC needs to be 
connected to externalpower supply 
and be disconnected from +24 V. 

Analog input 

 

AI1-GND 

Analog input 1 

Input voltage range: DC 0

10V/0

20mA

decided by toggle switches 

AI1

AI2 on the control board 

Impedance: 250 kΩ (voltage input), 
250 Ω (current input)   

AI2-GND 

Analog input 2 

AI3-GND 

Analog input 3 

Input Voltage Range: DC -10

+10V 

Input impedance: 250kΩ 

Switch input 

DI1- COM 

Switch input 

terminals 1 

Maximum input frequency: 200Hz 
Impedance: 2.4kΩ 
Voltage range for level input: 9V

30V 

DI2- COM 

Switch input 

terminals 2 

DI3- COM 

Switch input 

terminals 3 

DI4- COM 

Switch input 

terminals 4 

DI5- COM 

Switch input 

terminals 5 

DI6- COM 

Switch input 

terminals 6 

DI7/HI-COM 

Switch input 

terminals 7 OR 

High-speed 

pulse input 

Besides features of DI1–DI6, it can be 
used for high-speed pulse input. 
Maximum input frequency: 100 kHz 

Analog 

output 

AO1-GND 

Analog output 

terminal 1 

Output voltage range: DC 0

10V/0

20mA

decided by toggle switches 

AO1

AO2 on the control board 

Impedance requirements≥10kΩ 

AO2-GND 

Analog output 

terminal 2 

Switch output 

Y1-COM 

Open collector 

output 1 

Voltage range: 0

24V 

Current range: 0

50mA 

Y2/HO-COM 

Open collector 

output 2 OR 

High-speed 

pulse output 

Besides features of Y1, it can be used 
forHigh-speed pulse output channels. 
The maximum output frequency: 
100kHz 

Relay output 

 

R1A-R1C 

Normally open   

terminal 

Contact driving capacity:   
AC250V

3A

COSØ=0.4. 

DC 30V

1A 

R1B-R1C 

Normally 

closedterminal 

Summary of Contents for FR200H

Page 1: ...R200 user manual IMPORTANT NOTES To illustrate the details of the products pictures in this manual based on products with outer casing or safety cover being removed When using this product please be s...

Page 2: ...r 1 Product Information 3 1 1 Nameplate information 3 1 2 Information of FR200H Product Model 4 1 3 Terminal Configuration 4 1 4 Configuration Mounting Dimensions and Weight 8 Chapter 2 Debugging Guid...

Page 3: ...011P B Product series code FR200H Input voltage 2 220V 15 30 4 380V 15 30 Input voltage phases S Single phase T Three phase Industry specific series code H special use for multi pumps constant pressur...

Page 4: ...00H 4T 037G 045PB FR200H 4T 045G 055P 69 92 91 45 60 FR200H 4T 045G 055PB FR200H 4T 055G 075P 85 113 112 55 70 FR200H 4T 055G 075PB FR200H 4T 075G 090P 114 157 150 75 100 FR200H 4T 075G 090PB FR200H 4...

Page 5: ...rminals Upload and download interfaces PB RFI Fig 1 4 4 0 18 5kW Schematic of main circuit terminals c 22 30kW Main Circuit Terminals Solution 1 Fig 1 5 22 37kW Main Circuit Terminals Solution 1 Schem...

Page 6: ...s R L1 S L2 T L3 AC power input terminals for connecting to 3 phase AC380V power supply U T1 V T2 W T3 AC output terminals of inverter for connecting to 3 phase induction motor Positive and negative t...

Page 7: ...ge input 250 current input AI2 GND Analog input 2 AI3 GND Analog input 3 Input Voltage Range DC 10 10V Input impedance 250k Switch input DI1 COM Switch input terminals 1 Maximum input frequency 200Hz...

Page 8: ...ed ground Shield PE Shield Ground Ground terminal for shield Auxiliary Interface External operation panel interface Use standard network cable Maximum cable distance 50m UP DOWNLOAD Parameter copy int...

Page 9: ...0H 4T 022G 030PB FR200H 4T 030G 037PB FR200H 4T 037G 045P 270 130 590 572 260 7 27 5 FR200H 4T 045G 055P FR200H 4T 055G 075P 357 230 590 572 260 7 37 FR200H 4T 075G 090P FR200H 4T 090G 110P 430 320 83...

Page 10: ...Given Feedback FWD REV Q5 DI7 R1A R1C R2A R2C KA1 KA2 Y1 Y2 24V M1 M2 M3 M4 M5 L1 L2 L3 220V KM2 KM3 KM4 KM5 R1A R1C R2A R2C KA1 KA2 R S T U V W Inside the dotted line is power frequency pumps can be...

Page 11: ...tore user backup parameters 4 Back up user parameters 5 Restore factory default include motor parameters 6 Clear power dissipation Group F01 Frequency Command F01 01 Master Frequency Command Source 0...

Page 12: ...step frequency terminal 3 16 Multi step frequency terminal 4 17 Accel Decel time determinant 1 18 Accel Decel time determinant 2 19 Accel Decel disabled ramp stop not inclusive 20 Given frequency swi...

Page 13: ...1 output function 00 No output 01 Drive is running 02 Fault output 03 Frequency level detection FDT1 04 Frequency level detection FDT2 05 Drive in 0Hz running 1 no output at stop 06 Drive in 0Hz runni...

Page 14: ...ed as HO 02 Command frequency 1 03 Output current rated current 04 Output voltage rated voltage 05 Output power 06 Bus voltage 07 10V 08 keypad potentiometer 09 AI1 10 AI2 11 AI3 12 HI 100 to 10 00kHz...

Page 15: ...curve V F 10 1 4 power inverse curve V F 11 1 6 power inverse curve V F 12 1 8 power inverse curve V F 13 2 0 power inverse curve V F F09 01 Torque boost 0 0 30 0 0 0 fixed torque boost 0 0 F09 02 Cu...

Page 16: ...Mode 2 Proportion Gain 0 1 100 0 50 0 F11 08 Overvoltage Stall Mode 2 frequency limited 0 00 50 00Hz 5 00Hz F11 10 Protection action 1 Unit s place Bus undervoltage 03330 0 Fault reported and coast t...

Page 17: ...on abnormality F11 15 Backup frequency upon abnormality 0 00 Fmax 0 00Hz F11 17 Motor overload protection time 30 0 300 0s 60 0s F11 18 Overload alarm Unit s place detection option 000 0 Always detect...

Page 18: ...pulse input 6 AI2 7 AI3 F13 01 PID digital setting 0 0 100 0 50 0 F13 02 PID feedback 0 AI1 1 1 AI2 2 Communication 3 AI1 AI2 4 AI1 AI2 5 Max AI1 AI2 6 Min AI1 AI2 7 DI7 HI pulse input 8 AI3 F13 03 PI...

Page 19: ...imit 100 0 PID output frequency upper limit 0 0 F13 24 Detection value of PID feedback loss 0 0 100 0 0 0 Not judging feedback loss 0 0 F13 25 Detection time of PID feedback loss 0 0 30 0s 1 0s F13 26...

Page 20: ...input terminal DI7 DI6 00 U00 14 Status of digital output terminal R2 R1 Y2 Y1 0000 U00 15 AI1 input 0 0 100 0 0 0 U00 16 AI2 input 0 0 100 0 0 0 U00 17 AI3 input 100 0 100 0 0 0 U00 18 Keypad potenti...

Page 21: ...d write fault Err16 Motor auto tuning cancelled Err17 Motor auto tuning fault Err18 Communication overtime error Err19 PID feedback loss Err20 Continuous running time reached Err21 Parameter upload fa...

Page 22: ...d 0 65535h 0h H00 group multi pumps constant pressure water supply H00 00 Special purpose inverter function enable 0 Invalid 0 1 Valid H00 01 Work modes selection 0 fixed variable frequency pumps mode...

Page 23: ...d variable frequency pump mode Inverter 3 phase output control a certain pump as fixed variable frequency pump other pumps power frequency run stop controlled by programmable D0 output max control 1 f...

Page 24: ...the system has too much pressure power frequency pump stops The same moment at most only one pump work as variable frequency pump another one work on power frequency can control 2 variable frequency...

Page 25: ...action time generally the contactor action from connect to disconnect takes longer time than switch from disconnect to connect please operate on longer time H00 11 Pump status Unit No 1 pump status 0...

Page 26: ...le pump H00 13 Gap of timing rotate 1 60000Min 240Min Single variable mode when parts of power frequency motor running water supply system under stable to avoid parts of motor keep running in a long t...

Page 27: ...on time 3 Adjust the manual torque boost or V F curve 4 Adjust the voltage to normal range 5 Select rotational speed tracking restart or start the motor after it stops 6 Remove the added load 7 Select...

Page 28: ...taneous power failure occurs on the input power supply 2 The AC drive s input voltage is not within the allowable range 3 The bus voltage is abnormal 4 The rectifier bridge and buffer resistor are fau...

Page 29: ...tion Err14 Module overheat 1 The ambient temperature is too high 2 The air filter is blocked 3 The fan is damaged 4 The thermally sensitive resistor of the module is damaged 5 The inverter module is d...

Page 30: ...becoming0 The AC drive running current is lower than F11 22 Check that the load is disconnected or the setting F11 22 and F11 23 is correct Err26 With wave current limit fault 1 The load is too heavy...

Page 31: ...ut voltage is too high 2 There is external force drag the motor to run in dece process 3 The deceleration time is too short 4 No installation of braking resistor 1 Adjust the voltage to normal range 2...

Page 32: ...FR200H Special Purpose Inverters for Multi pumps Constant Pressure Water Supply 32...