FR200H Special Purpose Inverters for Multi-pumps Constant Pressure Water Supply
- 25 -
pumps
pumps
H00.04
Pressure tolerance for
add pumps
0.0
~
100.0%
0.0%
△
H00.05
Pressure tolerance for
reduce pumps
0.0
~
100.0%
0.0%
△
H00.06
Added pumps delay
0.0
~
300.0s
20.0s
△
H00.07
Reduced pumps delay 0.0
~
300.0s
15.0s
△
Add pumps: running frequency≥H00.02 set value, feedback pressure
<
set pressure-pressure
tolerance, and last the delay time set by H00.06, meet the terms of add pumps, add pump.
Reduce pumps: running frequency≤H00.03 set value, feedback pressure
>
set ppressure
tolerance, and last the delay time set by H00.07, meet the terms of reduce pumps, reduce pump.
H00.08
Time for added pumps
speed arrival max
0.0
~
300.0s
1.0s
△
H00.09
Time for reduced pumps
zero-flow
0.0
~
300.0s
1.0s
△
Time for added pumps speed arrival max: when command for adding pumps being sent, a
delay(H00.08 parameters) been start, which makes the pump arrive at its rated speedbefore start
another pump(avoid shaking).
Time for reduced pumps zero-flow: when command for adding pumps being sent, a delay(H00.09
parameters) been start, which makes the pump can stop effectively before stop another pump(avoid
shaking).
H00.10
Switching time
0.1
~
10.0s
1.0s
×
This function mainly use for protection inverter and AC power supply from short-circuited, which
caused by contactor action delay when a motor switched from variable frequency to power frequency.
Set the shortest time larger than the total of relay action time and contactor action time, generally
the contactor action from connect to disconnect takes longer time than switch from disconnect to
connect, please operate on longer time.
H00.11
Pump status
Unit: No.1 pump status
0:spare
1:start
Decades: No.2 pump status
(same with unit)
Hundreds: No.3 pump status
(same with unit)
Thousands: No.4 pump
status(same with unit)
Myriabit: No.5 pump
status(same with unit)
00011
△
Spare: Control terminals DI1
~
DI7 are multi-functional terminals, which define their functions by
setting the value of F04.00
~
F04.03. Repeat definition is allowed, one of the re-defined
terminals valid, the function valid. 51
~
54 is special functions for constant pressure water
supply, instructions as below: 51
~
54:No.1~No.4 pumps status.
Start: When function of DI1
~
DI7 terminal defined as 51
~
54, terminals valid, then the corresponding
pumps allowed to run, if terminals invalid, and F04.00
~
F04.03 corresponding pumps status
selected to be 1: start, then the pumps allowed to run, if selected to be 0: spare, then the
pumps not allowed to run.
H00.12
Timing rotate or not
0:fixed order
1:start first stop first
2:timing rotate
0
×
0: fixed order: start the pumps from small to large.
1: start first stop first: firstly start the running time shortest one when add pumps, firstly stop the
running time longest one when reduce pumps.
2: timing rotate:
(
1
)
Single variable pump, with assisted pump switched, timing rotate. When 2 pcs or
more than 2 pcs assisted pumps running at the same time, if system meets the term of reduce
pumps, the firstly started pump will stop first; if the one of them keep running more than H00.13
(timing rotate gap), the assisted pump stops, and start the pump with longest stop time. (2) Multi