WLA200 Rev140407

7

Pressure/Vacuum Foam Tank Vent

The pressure/vacuum foam tank vent is supplied for use on sealed foam tanks. 

The vent compensates for changes in tank pressure due to thermal expansion or when 

withdrawing foam concentrate from the tank. Internal passageways provide a path 

for air to move between the tank and a center cavity in the vent. These passageways 

are self-draining and designed to prevent splashing foam from entering the center 

cavity and clogging the pressure and vacuum valves. The pressure and vacuum valves 

are easily accessed and disassembled for periodic cleaning or inspections. (Refer to 

Maintenance section.)

Note:

 The vent can compensate for a maximum foam concentrate flow rate 

of 60 GPM. If the flow rate of foam concentrate from the tank will exceed 

60 GPM, two (2) vents will be required. 

MaxVision LED Tank Display (Optional)

The LED display is waterproof and has dimensions of 14 3/8 inches high by 1 7/8 

inches wide by 7/8 inch deep. It has 96 RGB LEDs and built in LED drivers. A signal 

from the primary display module is output on a two wire datalink and input to the LED 

light to show the volume of liquid in the tank.

The display shows the level in 1/8 tank increments. It has a photo sensor that adjust 

brightness for day or night operations. The LEDs are programmable for two modes of 

display and ten brightness levels:

Ultra - All LEDs are one color and change at each 1/4 tank increment.
Typical - LEDs show four colors for 1/4 tank increments.

Remote Light Driver (Optional)

The remote light driver is waterproof and has dimensions of 4 inches high by 2.75 

inches wide by 1 inch deep. An output signal from the primary display module is input 

to the remote light driver. This provides the option to power four (4) 60 watt remote 

lights that show the volume of liquid in the tank. The lights will show full, 3/4, 1/2, 

and 1/4 tank levels.

Buzzer (Optional)

The buzzer provides an audio alarm when the tank volume drops to 25%. The 

buzzer resets when the tank volume goes above 25%.

Note:

 When the TankVision primary is used to control a Foam Fill FFA100 

or Auto Tank ATA400 system, pin 5 does not provide a ground for the 

buzzer. The primary display is programmed from the factory with a control 

output on display connector pin 5 for each of these special systems. These 

displays are not interchangeable.

Summary of Contents for TankVision WLA200

Page 1: ...70 CLASS B FOAM CONCENTRATE TANKS Document Number XE WLA2PM R0A PRIMARY and REMOTE DISPLAYS HORIZONTAL OPTION MAXVISION LED TANK DISPLAY CAB MINIATURES FIRE RESEARCH CORPORATION www fireresearch com 2...

Page 2: ...re Vacuum Foam Tank Vent 12 Install MaxVision LED Tank Display 14 Program MaxVision LED Tank Display 14 Install Remote Light Driver 16 Install Buzzer 16 OPERATION 17 Options 17 CALIBRATION 18 Overview...

Page 3: ...gure 5 MaxVision LED Display Mounting Dimensions 15 Figure 6 Remote Light Driver 16 Figure 7 Diagnostics Faults 22 Figure 7 Diagnostics Warnings 23 Figure 8 Primary Display Wiring 24 Figure 9 Remote C...

Page 4: ...ly read from all line of sight angles for a full 180 degrees The pressure vacuum foam tank vent is supplied for use on foam concentrate storage tanks These tanks should remain closed to the atmosphere...

Page 5: ...mic Diaphragm Pressure Range 0 5 PSI Maximum Tank Height 10 Feet Excitation Voltage 5 VDC Pressure Vacuum Foam Tank Vent Material PVC and Aluminum with Delrin Valves Relief Pressure 0 01 PSI Maximum F...

Page 6: ...Foam Fill FFA100 and Auto Tank ATA400 systems These require special programs for the correct controlling output on display connector pin 5 Cab Miniature Display Optional The cab miniature display has...

Page 7: ...ut on a two wire datalink and input to the LED light to show the volume of liquid in the tank The display shows the level in 1 8 tank increments It has a photo sensor that adjust brightness for day or...

Page 8: ...re there is clearance behind the panel for the display and cables before cutting holes Refer to Figure 1 for layout and dimensions 2 Cut out a 4 by 2 1 8 inch hole and drill four 4 holes clearance or...

Page 9: ...Dimensions 5 8 1 1 2 1 3 16 1 9 16 Drill a clearance hole for 3 8 threads 2 3 4 3 4 Figure 2 Cab Miniature Display Mounting Dimensions 2 2 1 2 2 1 2 1 1 2 4 3 8 2 1 2 3 3 1 2 2 1 8 1 3 4 3 1 2 4 1 1...

Page 10: ...rance for sensor and cable before drilling hole Refer to Figure 3 for dimensions 2 Drill and tap a 1 4 NPT hole 3 Apply sealant around base and threads of pressure sensor 4 Screw sensor into hole 5 Co...

Page 11: ...ical Pressure Sensor Location Typical Tank 1 2 NPS 2 Mount sensor approximately 2 from bottom of tank Note The sensor can be mounted vertically on a 90 fitting in cold areas to help prevent water free...

Page 12: ...he tank vent must be in a vertical position and can not be immersed in foam 1 Measure and mark mounting location for vent Make sure there is clearance for the valve before drilling hole Refer to Figur...

Page 13: ...lts 3 4 Dia 2 5 8 Figure 4 Pressure Vacuum Foam Tank Vent Note The tank vent must be mounted in a vertical position The vent can not be immersed in foam If there is no fill tower mount the vent at the...

Page 14: ...datalink requires two terminating resistors a TankVision display always has one One TankVision with one or two LED displays Install resistor at farthest light Two TankVision displays Do not install t...

Page 15: ...4 6 5 8 6 5 8 7 8 7 8 7 8 1 7 8 Front View Side View Rear View Three locations are available for the wires to exit the rubber gasket Drain Notch Figure 5 MaxVision LED Display Mounting Dimensions Mou...

Page 16: ...d cable before drilling holes Refer to Figure 5 for dimensions 2 Drill and tap two 10 32 holes 3 Secure remote light driver with two screws 4 Connect cable and wires Refer to Wiring section Install Bu...

Page 17: ...r display Cab Miniature Display All 5 LEDs is on when the tank is full The LEDs will show full 3 4 1 2 1 4 and empty tank MaxVision LED Display The LED display repeats exactly what is shown on the mas...

Page 18: ...used for any shape or size tank This procedure must to be used for irregular shape tanks e g T shape oval elliptical tank with through hole etc The program compares the pressure in the tank as the tan...

Page 19: ...e display module 3 Swipe the magnet three times to enter the calibration mode Result Top three display LEDs flash on and off Note Once the calibration process is activated the flow rate of liquid into...

Page 20: ...the calibration program terminates no program data is changed 1 Fill the tank Do not fill up into the fill tower 2 Apply power to the display module Note Once the calibration program is activated the...

Page 21: ...op eight display LEDs go on the calibration program terminates no program data is changed 1 Fill the tank Do not fill up into the fill tower 2 Apply power to the display module Note Once the calibrati...

Page 22: ...ressure Sensor high output voltage voltage 4 6V Shorted wire on sensor cable Pressure Sensor or Primary Display Failure Checksum Error Primary Display Failure Top 2 3 Bottom 2 3 LEDs Alternately Flash...

Page 23: ...ltage from the Pressure Sensor is more than 0 5V above calibrated full tank voltage Top 2 and Bottom 2 LEDs Blink ON and OFF Top and Bottom LEDs Blink ON and OFF The difference in voltage from the Pre...

Page 24: ...ch Plug DTM06 8S Primary Display Module To Pressure Sensor Power Figure 8 Primary Display Wiring Note When the TankVision primary is used to control a remote valve Foam Fill or Auto Tank system pin 5...

Page 25: ...nnector and a butt connector on the other to connect to customer provided wire is provided with the Cab Miniature Display Wires can be routed from top middle or bottom feed through The datalink requir...

Page 26: ...ied together The maximum current is 20 AMPS 12VDC 10 AMPS 24 VDC 1 4 5 8 Figure 10 Remote Light Driver Wiring Light Driver Connector Pin Signal Description 1 Ground 2 Signal Input 3 Remote Light Power...

Page 27: ...An unlimited number of remote displays can be connected Any remote display can become a primary by disconnecting the sensor from the primary and connecting it to the remote To Other Miniature Displays...

Page 28: ...sure and vacuum valves are easily accessed and disassembled for periodic cleaning or inspections Unscrew the cap from the main body and lift the valves out of the center cavity Clean all parts with wa...

Page 29: ...splay Module Class B Foam 2 XE WL200S CXXA Primary Display Cable XX Length 3 XE WL200R CXXA Remote Display Cable XX Length 4 XE WLPT4 S Pressure Sensor 5 XE WL20A A Thin Wall Adapter Kit 6 XE WL400 A...

Page 30: ...WLA200 Rev140407 30 NOTES...

Page 31: ...WLA200 Rev140407 31 NOTES...

Page 32: ...WLA200 Rev140407 32...

Reviews: