background image

Installation of the cables between the junction box and the control panel may or may not 
include the use of conduit. Determine the location in the control panel for entry of the pump 
power cable and the float switch cables. If conduit is used, follow all applicable codes for 
connecting conduit to junction boxes and control panels. 
If conduit is not used, drill the appropriately sized hole, bring the cable into the control panel 
and secure the cable with weather tight cable clamp connectors. 

PUMP POWER CORD

The pump power cable is a 14 AWG, 4-conductor with ratings of 90°C to –40°C and 600 
Volts.  The wires in the pump power cable are colored red, white, black and include a green 
ground wire. The red wire connects to the auxiliary (start) winding in the motor, the white 
wire connects to the main (run) motor winding and the black wire is common to both wind-
ings. The pump power terminal block in the control panel is coded as follows: R – red, W 
– white, and B – black.
Make sure all connections to the pump power terminal block are tight and that no wire strands 
protrude from any terminal. Also, make sure the terminals do not clamp down on any of the 
wire insulation.

FLOAT SWITCH CABLES

In the basin, the bottom float switch is the Off Float, LS-1, the middle float switch is the On 
Float, LS-2, and the top float switch is the Alarm Float, LS-3. The wires of the Off Float LS-1 
are labeled  9  and  10 ; the wires of the On Float LS-2 are labeled  11  and  12 ; the wires 
of the Alarm Float LS-3 are labeled  15  and  16 .

Make sure all connections to the float switch terminal block are tight and that no wire 
strands protrude from any terminal. Also, make sure the terminals do not clamp down on 
any of the wire insulation.

POWER SUPPLY

Using the 230 VAC or 208 VAC power described in the Power Requirements section, bring 
the supply power cable into the control panel and connect the two voltage (hot) lines L1 
and L2 to the control panel circuit breakers. Connect the ground wire to one of the provided 
ground lugs on the back plate.

CAUTION:

 If the incoming electrical feed is from a Delta-Connection Power Supply where a 

High-Leg could be present, caution should be used to ensure the High-Leg is not connected 
to L1 (the voltage between L1 and N should be 115 VAC). Never connect the neutral (N 
terminal) of the incoming power terminal block to a ground wire or a ground lug.
For the 120 VAC control circuitry power, connect the 120 Volt line to the 2 terminal of 

the  terminal block.  Connect the neutral wire to the N of the terminal block.  Connect the 
ground wire to one of the ground lugs on the back plate.  

Remove jumper wire from L1 

to 2 if supplying separate 120 VAC power.

 A separate neutral wire 

MUST

 run from main 

power source.

Make sure all connections to the terminal block are tight and that no strands protrude 
from any terminal. Make sure the terminals do not clamp down on any of the wire 
insulation.

OPERATION OF THE CONTROL PANEL

A. PRE-OPERATION CHECK

  1.  Inspect all wiring and components for damage and check the panel interior for the 

presence of contaminants.  

  2.  Make sure no wires will be pinched when the panel door is closed.

  3.  Check that there is no moisture or debris in the control panel. 

  4.  Verify that the pump is correctly installed in the sump or basin.

  5.  Make sure no person is near the grinder cutters or touching the pump.

  6.  Verify that the source voltages are correct at the panel circuit breakers and the terminal 

block by re-checking the voltage between L1 and L2 and between 2 and N.

B. OPERATION

After the Pre-Operation Check has been completed, the control panel and the grinder pump 
are ready for operation.

  1.  Check that the overload relay is in the factory-set 14 amp position.

  2.  Switch on the circuit breaker for the circuit providing pump power.

  3.  Switch on the control panel circuit breaker.

  4.  Test pump operation by switching the HOA switch to the Hand position. The pump 

should activate and pump water out of the sump or basin. If the pump did not operate 

properly, refer to the Troubleshooting Section at the end of these instructions.  

    TO PREVENT POSSIBLE PUMP DAMAGE, DO NOT OPERATE THE PUMP WITHOUT 

WATER FOR MORE THAN A COUPLE OF SECONDS. 

  5.  Switch the HOA switch to Off, then to Auto to check the float switch operation.

  6.  With the HOA switch in Auto setting, check for automatic operation by activating the 

float switches in the following order: LS-1, LS-2 and LS-3. Then de-activate the float 

2

Figure 3.

Summary of Contents for LittleGIANT MGP-1C18-2

Page 1: ...m operation LOCATING THE CONTROL PANEL The control panel should be mounted in a convenient location preferably close to the pump installation The location should allow clear visibility of the alarm li...

Page 2: ...g could be present caution should be used to ensure the High Leg is not connected to L1 the voltage between L1 and N should be 115 VAC Never connect the neutral N terminal of the incoming power termin...

Page 3: ...endommag Consulter le soutien technique Little Giant 10 Des pr cautions extr mes doivent tre prises durant le per age ou la coupe de trous dans le panneau de commande pour l acc s aux c bles ou aux fi...

Page 4: ...ue la cause d une surcharge soit d termin e et corrig e avant que la pompe soit utilis e de nouveau Apr s la r solution du probl me appuyer bri vement sur le bouton de remise z ro E INTRODUCCION El pa...

Page 5: ...Los cables del interruptor de l mite 1 el Flotador de Apagado LS 1 de flotador de detenci n se etiquetan 9 y 10 los cables del interruptor de l mite 2 de flotador encendido se etiquetan 11 y 12 los c...

Page 6: ...es del foco y aplique una alimentaci n de 120 voltios independiente para determinar si el foco est defectuoso 3 Pump does not operate when HOA switch is in AUTO position La pompe ne fonctionne pas lor...

Page 7: ...mmande d mont e par l utilisateur RETOUR DE PI CES REMPLACER Toute pi ce qui doit tre remplac e conform ment la garantie doit tre retourn e port pay l entreprise Franklin Electric Oklahoma City Oklaho...

Page 8: ...permiten la exclusi n o limitaci n de da os incidentales o emergentes as que la limit aci n o exclusi n arriba indicada puede que no sea aplicable a usted Esta garant a le da a usted derechos legales...

Reviews: