INSTALLATION

Electrical Connections

4

High Water Level Switch Connection

1.

High Water Level Switch

2. NC terminal. Connect here to activate an external alarm or relay.
3. NO terminal. Connect here to shut off the condensing unit of the heating/cooling system.
4. Motor Cover and Screw
5. Thermostat
6. Air Conditioner/Furnace
7. High Water Level Switch wiring leads
There are two options for connecting the high level switch:
1.

The switch is factory wired to the NO and COM terminals. This configuration will open (break) an elec

-

trical circuit when the switch is activated by a high water level in the reservoir, which can be used to 
stop the condensing unit(s) of the heating/cooling system. 
Refer to the thermostat and heating/cooling unit’s Operating Manual for expected switch operation and 
wiring connections. Connect the switch leads (7) in series with the low voltage thermostat circuit as 
specified in the heating/cooling unit’s operating manual.

2. The installer can reconfigure this switch to the NC terminal to close a low voltage circuit in the event of 

high water level, which could activate an external alarm or relay (purchased separately). Use the fol

-

lowing procedure if an NC configuration is required:

Remove the pump’s motor cover (4).

Support the switch and carefully change the lead wire from the NO(3) terminal to the NC terminal 
(2).

Re-install the motor cover.

Connect the switch leads in series with the low voltage external component as specified in the 
component’s manual.

Place the “Attention Service Technician” label included with the pump on the outside of the access panel 
in a visible location.

Risk of bodily injury or property damage.

In applications where property damage and/or personal injury might result from an inoperative or 
leaking pump due to power outages, discharge line blockage, or any other reason, a backup sys

-

tem(s) (e.g. auxiliary switch) and/or alarm should be used and monitored.

The high level switch should be connected to a Class II Low Voltage circuit. The two switch wires are 
black. Do not confuse these wires with the line voltage power conductors.

The high level switch is placed in an orientation that reverses the normal function of normally open 
and normally closed terminals. Pay close attention to the following instructions.

Summary of Contents for Little Giant VCC-20S

Page 1: ...be installed and serviced by technically qualified personnel who are familiar with the correct selection and use of appropriate tools equipment and procedures Failure to comply with national and loca...

Page 2: ...only be used with liquids compatible with pump component materials If the pump is used with liquids incompatible with the pump components theliquid can cause failure to the electrical insulation syst...

Page 3: ...c head capacity of the pump 5 From the high point slope discharge line down slightly to a point above the drain area Then turn down and route to a suitable drain at a point below or approximately leve...

Page 4: ...rcuit in the event of high water level which could activate an external alarm or relay purchased separately Use the fol lowing procedure if an NC configuration is required Remove the pump s motor cove...

Page 5: ...p MAINTENANCE To inspect and clean the tank and other components follow these steps 1 Disconnect the pump from the power source 2 Remove tank cover assembly from the tank Remove four screws that secur...

Page 6: ...erate correctly Check valve stuck or plugged Remove check valve and inspect for proper operation Outlet flow is blocked Check outlet tubing to ensure that it is not kinked or blocked Clear blocked tub...

Page 7: ...Antes de empezar La instalaci n y el mantenimiento de este equipo deben estar a cargo de personal con capacitaci n t cnica que est familiarizado con la correcta elecci n y uso de las herramientas equ...

Page 8: ...bomba solo se debe utilizar con l quidos compatibles con los materiales que componen la bomba Si la bomba se utiliza con l quidos incompatibles con los componentes de la bomba el l quido puede causar...

Page 9: ...que un 75 la capacidad de la carga gal h de la bomba 5 Desde el punto alto baje la l nea de descarga ligeramente hasta un punto encima del rea del drenaje Luego volt ela y ori n tela hasta un drenaje...

Page 10: ...e podr a activar un rel o una alarma externa que se compran por separado Utilice el siguiente procedimiento si se requiere una configuraci n NC Retire la cubierta del motor de la bomba 4 Sostenga el i...

Page 11: ...8 Encienda la alimentaci n el ctrica a la bomba MANTENIMIENTO Para inspeccionar y limpiar el tanque y otros componentes siga los pasos que se detallan a continuaci n 1 Desconecte la bomba de la fuente...

Page 12: ...est bloqueado Verifique la tuber a de salida para asegurarse de que no est retorcida ni bloqueada Despeje la tuber a bloqueada de lodo y residuos Limpie la tuber a de entrada y de salida El impulsor d...

Page 13: ...alifi s capables de choisir et d utiliser les outils les quipements et les proc dures appropri s Le non respect des codes lectriques et codes de plomberie local et national et des recommandations de L...

Page 14: ...s e avec des liquides incompatibles avec les composants de la pompe le liquide peut provoquer une d faillance du syst me d isolation lectrique entra nant un choc lectrique Risque de blessure de choc l...

Page 15: ...e la pompe 5 partir du point le plus haut inclinez l g rement le tuyau de refoulement vers le bas jusqu un point au dessus de la zone d coulement Ensuite tournez vers le bas et acheminez vers un sipho...

Page 16: ...elais externe vendus s par ment Utilisez la proc dure suivante si une configuration NC est requise Retirer le couvercle du moteur de la pompe 4 Soutenir l interrupteur et passer soigneusement le fil d...

Page 17: ...oteur devrait d marrer avant que le flotteur de l inter rupteur ne touche le dessous du couvercle du r servoir 5 Tester l interrupteur auxiliaire pour niveau lev en faisant monter le flotteur de cet i...

Page 18: ...op ration au dessus d un vier 6 Nettoyer le r servoir l eau chaude avec un savon doux 7 Rincer le r servoir avec de l eau Cela permet de s assurer que le condensat r siduel ne cr e pas de poches d ac...

Page 19: ...le n est pas cou d e ou obstru e Nettoyez la boue et les d bris de tout tuyau obstru Net toyez la tuyauterie d entr e et de sortie La roue de la pompe ne tourne pas Nettoyez toute obstruction dans le...

Page 20: ...ic Co Inc Oklahoma City OK 73157 2010 800 701 7894 littlegiant com Pour l aide technique entrez s il vous pla t en contact Form 993554 R v 001 07 19 Droits d auteur 2019 Franklin Electric Co Inc Tous...

Reviews: