FPI P36D Zero Clearance Direct Vent Gas Fireplace

31

Diagram 4

6) The arrow on the vent cap should be

pointing up. Insure that the 1-1/2" clear-
ances to combustible materials are main-
tained (Diagram 4). Install the termination
cap.

NOTE: For Snorkel terminations  in ABOVE

grade installations, follow nation-
al or local code requirements.

Below Grade Installation

If the Snorkel Termination must be installed
below grade, i.e. basement application, proper
drainage must be provided to prevent water
from entering the Snorkel Termination. Refer to
Diagram 4. Do not attempt to enclose the Snor-
kel within the wall, or any other type of enclo-
sure.

*Diagrams 3 & 4: As specified in CGA B149
Installation Code. Local codes or regula-
tions may require different clearances.

HORIZONTAL

INSTALLATIONS

Install the vent system according to the
manufacturer's instructions included
with the components.

1) Set the unit in its desired location. Check to

determine if wall studs or roof rafters are in
the way when the venting system is at-
tached. If this is the case, you may want to
adjust the location of the unit. Rough in the
gas preferably on the right side of the unit
and the electrical (junction block is on the left
side) on the left.

2) Direct Vent pipe and fittings are designed

with special twist-lock connections to con-
nect the venting system to the appliance flue
outlet. A twist-lock appliance adaptor is an
available option that must be used in con-
junction with the Simpson Dura-Vent Direct
Vent GS system.

3) Put a bead of silicone inside the outer section

of the adapter and a bead of Mill Pac on the
inner collar. Slip the adapter over the exist-
ing inner and outer flue collar and fasten to
the outer collar only with the 3 supplied
screws (drilling pilot holes will make this
easier). Level the fireplace and fasten it to
the framing using nails or screws through
the nailing strips.

4) Assemble the desired combination of pipe

and elbows to the appliance adaptor and
twist-lock for a solid connection.

Note:

a) Twist-lock procedure: Four indentations,

located on  the female ends of pipes and
fittings, are designed to  slide straight
onto the male ends of adjacent pipes and
fittings, by orienting the four pipe inden-
tations so they match and slide in to the
four entry slots on the male ends, Dia-
gram 1. Push the pipe sections com-
pletely  together, then twist-lock one
section clockwise approximately one-
quarter turn, until the two sections are
fully locked. The female locking lugs will
not be visible from the outside, on the
Black Pipe or fittings. They may be locat-
ed by examining the inside of the female
ends.

Diagram 1

b) Horizontal runs of vent must be sup-

ported every three feet. Wall straps are
available for this  purpose.

5) Mark the wall for a 10" x 10"  square hole.

The center of the square hole should line up
with the centerline of the horizontal pipe.
Cut and frame the 10 inch square hole in the
exterior wall where the vent will be termi-
nated. If the wall being penetrated is con-
structed of non-combustible material, i.e.
masonry block or concrete, a 7"(178mm)
dia. (7-1/2"(191mm) dia. for flex) hole is
acceptable.

Diagram 2

Note:

a) The horizontal run of vent must be level,

or have a 1/4 inch rise for every 1 foot
of run towards the termination. Never
allow the vent to run downward. This
could cause high temperatures and may
present the possibility of a fire.

b) The location of the horizontal vent termi-

nation on an exterior wall must meet all
local and national building codes, and
must not be blocked or obstructed.  For
External Vent Terminal Locations, see
diagram on page 20.

c) Snorkel Terminations:

For installations requiring a vertical rise
on the exterior of the
building, 14-inch and
36-inch tall Snorkel
Terminations  are avail-
able, as well as the
standard Riser
Vent. Follow the
same instal-
lation pro-
cedures as
used for
s t a n d a r d
Horizontal
T e r m i n a -
tion. NEV-
ER install
the snor-
kel upside
down.

Diagram 3

Diagram 3a

Note: Riser Vent
is only for use
in above grade
terminations.

Note: Apply sealant "Mill-Pac" to inner

pipe and high temperature sili-
cone sealant to outer pipe on eve-
ry twist-lock joint.

Note:  With
D u r a - V e n t ,
the mini-
mum height
is achieved
by installing
a 90

o

 elbow

directly to
the rigid
pipe adaptor.

INSTALLATION

Summary of Contents for P36D-LP

Page 1: ...llowed exactly a fire or explosion may result causing property damage personal injury or loss of life FORYOURSAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity o...

Page 2: ...me Construction and Safety Standard Title 24 CFR Part 3280 or the current Standard of Fire Safety Criteria for Manufactured Home Installations Sites and Communities ANSI NFPA 501A and with CAN CSA Z24...

Page 3: ...nds 42 Lighting Plate Instructions 43 SAFETY LABEL Safety Label 5 INSTALLATION Unit Dimensions 6 Before You Start 7 General Safety Information 7 Installation Checklist 7 Locating Your Gas Fireplace 8...

Page 4: ...h Glass Replacement 44 Bay Glass Replacement 44 Removing Valve 45 Installing Valve 45 REGENCY FLUSH BAY DOOR OPTIONS Flush Trim 47 Louvers Flush 47 Double Screen Door 47 Bay Front 48 Bay Trim 48 Louve...

Page 5: ...OTE FPI unitsareconstantlybeingimproved Check the label on the unit and if there is a difference the label on the unit is the correct one SAFETY LABEL Copy of Safety Decal for P36D For the State of Ma...

Page 6: ...FPI P36D Zero Clearance Direct Vent Gas Fireplace 6 UNIT DIMENSIONS...

Page 7: ...rstothisappliance should be done by a qualified service per son A professional service person should be called to inspect this appliance annually Make it a practice to have all of your gas appliances...

Page 8: ...ce is Listed for bedroom instal lations when used with a Listed Millivolt Thermostat Some areas may have further requirements check local codes before installation 6 The P36D Direct Vent Gas Fireplace...

Page 9: ...urface of the carpeting tile etc Minimum Clearance from Top of Unit to Ceiling from top of unit 32 1016mm Side Wall Clearances Bay or Flush Front 6 152mm Barcelona Trim 6 152mm Cast Faceplate 6 152mm...

Page 10: ...10 INSTALLATION Clearances for Bay or Flush Front Clearances for Barcelona Trim REGENCY CLEARANCES PALACE SERIES CLEARANCES Clearances for The Balmoral The Westminster Front Clearances for The Kensing...

Page 11: ...L CLEARANCES These drawings are to scale at 1 6 one inch 6 inches Mantel can be installed anywhere in shaded area or higher using the above scale Note Ensure the paint that is used on the mantel and t...

Page 12: ...t are shown in the diagram below Note A non combustible mantel may be installed at a lower height if the framing is made of metal studs covered with a non combustible board These drawings are to scale...

Page 13: ...the mantel and the facing is heat resistant or the paint may discolour HAMPTON COMBUSTIBLE MANTEL CLEARANCES Because of the extreme heat this fireplace emits the mantel clearances are critical Combust...

Page 14: ...mantel and the facing is heat resistant or the paint may discolour PALACE SERIES COMBUSTIBLE MANTEL CLEARANCES Because of the extreme heat this fireplace emits the mantel clearances are critical Comb...

Page 15: ...leg clearances as per diagram Maximum 1 1 2 projection at 2 minimum clearance PALACE SERIES MANTEL LEG CLEARANCES Combustible mantel leg clearances as per diagram Maximum 1 1 2 projection at 2 minimu...

Page 16: ...6mmhighx921mmwidex441mmdeep Framing Dimensions A B C D 36 1 4 37 1 4 17 3 8 46 1 2 921mm 946mm 441mm 1181mm D isMinimumheighttocombustiblematerials including the Minimum 2 1 2 64mm Top clearance to th...

Page 17: ...r Palace Series a non combustible material 12 305mm above the unit and 6 153mm on each side must be used See diagram 1 The Barcelona Front and Palace Series also requires steel stud framing above and...

Page 18: ...ptional Arch Door Series a non combustible material 12 305mm above the unit and 6 153mm on each side must be used See diagram 2 The Arch Door Series also requires steel stud framing above and on each...

Page 19: ...epending on your facing depth VENTING INTRODUCTION The P36D uses the balanced flue technology Co Axial system The inner liner vents products of combustion to the outside while the outer liner draws ou...

Page 20: ...ce to inside corner with AstroCap Termination Cap min 6 15cm with Dura Vent Termination Cap 12 30cm H Not to be installed above a meter regulator assembly within 3 90cm horizontally from the centerlin...

Page 21: ...le liner 4 ft length 2 4 dia flexible liner 4 ft length 3 spring spacers 4 4 thimble 2 5 AstroCap termination cap 1 6 screws 12 7 tube of Mill Pac 1 8 plated screws 8 9 screws 8 x 1 1 2 Drill Point St...

Page 22: ...gth 7 Galvinized N A N A 4D7A Adjustable Length 7 Black N A N A 4D7AB Adjustable Length 12 Galvinized N A N A 4D12A Adjustable Length 12 Black N A N A 4D12AB 45O Elbow Galvinized 945 4DT EL45 4D45L 45...

Page 23: ...inches Alternate Horizontal Termination Caps Flat Wall Installation Wall Thickness Vent Length inches Required inches 4 5 1 2 6 7 8 1 2 9 10 11 1 2 12 9 14 1 2 11 14 5 8 Adj Pipe 15 23 1 2 17 24 Adj...

Page 24: ...7 8 inner diameter Maintain clearances to combustibles Horizontal vent must be supported every 3 feet Firestops are required at each floor level and whenever passing through a wall NOTE If you are ins...

Page 25: ...rances to combustibles Note Must use optional rigid pipe adaptor when using rigid pipe vent systems Part 510 994 VENTING ARRANGEMENTS VERTICAL TERMINATIONS RIGID PIPE SYSTEM Propane Natural Gas The sh...

Page 26: ...diagram 1 The shaded area in the diagram 1 shows all allowable combinations of straight vertical and offset to vertical terminations with rigid pipe vent systems for Propane and Natural Gas Maximum tw...

Page 27: ...s is required Horizontal Venting with Three 3 90o Elbows Option V H V V1 H H1 A 0 Min 1 Max 1 Min 2 Max B 1 Min 2 Max 3 Min 3 Max C 2 Min 2 Max 5 Min 4 Max D 3 Min 2 Max 7 Min 5 Max E 4 Min 3Max 9 Min...

Page 28: ...x 3 Min C 2 Min 3 Max 4 Min D 3 Min 4 Max 6 Min E 4 Min 5 Max 7 Min F 5 Min 6 Max 8 Min G 6 Min 7 Max 9 Min H 7 Min 8 Max 10 Min With these options max total pipe length is 30 feet with min of 10 feet...

Page 29: ...of the termination cap Required Parts Part Description 946 529 Co linear DV Vertical TerminationCap 948 305 3 Flex 35 ft 946 563 Co Axial to Co Linear Adapter Kit which contains the following Co line...

Page 30: ...Gas Fireplace 30 INSTALLATION Venting Arrangements Vertical Terminations with Co linear Flex System for both Residential Manufactured Homes into Masonry Fireplaces The shaded area in the diagrams show...

Page 31: ...ocedure Fourindentations located on the female ends of pipes and fittings are designed to slide straight ontothemaleendsofadjacentpipesand fittings by orienting the four pipe inden tations so they mat...

Page 32: ...his point Next drop a plumb bob from the roof to the hole previously drilled in the ceiling and mark the spot where the vent will penetratetheroof Determineifceilingjoists roof rafters or other frami...

Page 33: ...nt System Flex 1 Locate the unit in the framing rough in the gas preferably on the right side of the unit and the electrical Junction block is on the left side on the left Locate the centerline of the...

Page 34: ...oming into proper contact with the rear burner or thermopile or thermocouple it is always best to consult with your local authorities and the CAN CGA B149 installation code For USA installations follo...

Page 35: ...6 Pull off the pilot cap to expose the pilot orifice Burner Orifice 7 Unscrew the pilot orifice with the allen key and replace with the LP pilot orifice in the kit and replace pilot cap 9 Reinstall n...

Page 36: ...al Brick Panels install the Brick Pan els prior to installing the logs 1 Carefully remove the logs from the box and unwrap them The logs are fragile handle with care do not force into position 3 Place...

Page 37: ...right end sits behind the rear grate tab Front Brackets Notch 02 50 02 55 02 53 02 50 02 55 02 53 9 Sit Log 02 50 on the front left side of the burner Push the back of the log against the 2 front bra...

Page 38: ...flush door comes with a black frame To install the frame simply hook the top door flange onto the top of the unit and swing the door towards the unit see diagram 1 Be careful that the glass gasket doe...

Page 39: ...ntrol kit comes with a hand held transmitter a receiver and a wall mounting plate 1 Choose a convenient location on the wall to install the receiver and the receptacle box protection from extreme heat...

Page 40: ...o bring power to the receptacle box provided with the unit in case the fan is installed at a later date CAUTION Label all wires prior to disconnectionwhenservicingcon trols Wiring errors can cause im...

Page 41: ...approximately 4 from the control box Ensure that there is no interference with the wires when the louver is closed and that no wire will touch the hot metal surfaces or sharp edges 13 Plug the fan pow...

Page 42: ...rst time before you use it with the fan on When first operated the unit will release an odour caused by the curing of the paint the burning off of any oils remaining from manufac turing Smoke detector...

Page 43: ...abel 1 Push in gas control knob slightly and turn clockwise to OFF Knob cannot be turned from PI LOT to OFF unless knob is pushed in slightly Do not force 2 Wait five 5 minutes to clear out any gas If...

Page 44: ...lacement you must use the proper replacementlog Thepositionoftheselogsmust be as shown in the diagrams under Log Instal lation Note Improper positioning of logs may create carbon build up and will sev...

Page 45: ...appliance performance 9 Reinstall the 10 hold down screws 10 Hook up the 2 TP and 2 TH wires to the appropriate connections on the valve 11 Reinstall the bottom brick panel and the front log stand 12...

Page 46: ...FPI P36D Zero Clearance Direct Vent Gas Fireplace 46 FLUSH BAY DOOR OPTIONS...

Page 47: ...of the bottom louver Push down to lock into place Tighten the screws Screws on louver bracket Burner ON OFF control box attached to bottom flush louver Burner ON OFF control box FLUSH TRIM Attach the...

Page 48: ...andard flush door and glass must remain on the unit 1 Slide the Bay Deflector into the 2 Bay Deflector brackets in the top of the unit 2 Hook the top of the bay door over the flush door flange and swi...

Page 49: ...e the inner cut outs to secure the base of the Frame using the 2 x Hex Head Drill Point Screws provided Backside of Full Screen Door Frame Shown Inside Top of Outer Frame Hinge Bracket Inner Hinge Bra...

Page 50: ...Install the Left and Right Side Screen Doors in the fully open position by placing over top of the hinges on the Full Screen Door Frame NOTE Failuretoinstallthedoorsinthefullyopenpositioncouldresult...

Page 51: ...terial has to go on after the unit is set 1 Remove Glass Door Refer to P36 Manual 2 Remove 2 screws and bracket as indicated 3 Install On Off switch 4 Place bracket under the Flange Secure with 2 scre...

Page 52: ...nding hole on the Top Support Frame then secure with 1 screw b Repeat step on the other side Diagram 2 10 Change in Logo Replace existing logo with Regency logo a Mount Side Support Frame to unit as s...

Page 53: ...FPI P36D Zero Clearance Direct Vent Gas Fireplace 53 CAST FACEPLATE...

Page 54: ...f faceplate with screw 4 Repeat step 3 for the right side faceplate Secure bottom of faceplate with screw 5 Slide top piece of faceplate into side faceplates by fitting mounting plates into brackets 6...

Page 55: ...emoved in step 3 5 Install hinge to bracket then secure with screw New hinge bracket Left side shown 6 Place something underneath bottom grill to prevent scratching 7 Line up hinge holes in bottom gri...

Page 56: ...FPI P36D Zero Clearance Direct Vent Gas Fireplace 56 The Westminster Front INSTALLATION The Kensington Front The Balmoral Front...

Page 57: ...on the inside top of the firebox Bracket inside top of firebox Kensington Front frame 4 Remove existing control switch box from under firebox by discon necting wires connected to the valve at TH TH T...

Page 58: ...eft and right side of the firebox Slide frame in place and secure Left Side Shown Hinge bracket on bottom of firebox 4 Slide tabs into louver brackets located on the inside top of the firebox Westmins...

Page 59: ...and secure Left Side Shown Hinge bracket on bottom of firebox 4 Remove existing control switch box from under firebox by discon necting wires connected to the valve at TH TH TP terminals and discard...

Page 60: ...er 3 Connect new fan control box wires to the existing fan plug wires red to red black to black Disconnect Wires Fan Control Box Fan Control Box Vertical Hinge Bracket Discard Fan Cover with Wires New...

Page 61: ...s 1 Install sub frame by hooking top over glass door push in bottom of frame and secure with 2 screws Sub Frame 2 Mount 2 panel door frame to flange on sub frame ensuring to line up holes Secure using...

Page 62: ...FPI P36D Zero Clearance Direct Vent Gas Fireplace 62 REPLACEMENT PARTS LIST...

Page 63: ...241 Switch Burner ON OFF 3 way 910 899 Wire Harness Valve to Burner 432 917 Fan Speed Control Assy 120 Volts Optional 42 910 331 P Fan Motor 432 966 Fan Switch Assy 120 Volts Optional 43 910 813 Powe...

Page 64: ...P 57 910 378 Valve S I T Natural Gas 910 380 Valve S I T Propane 58 Valve Bracket 65 Pilot Bracket 66 910 038 Pilot Assy S I T 3 Flame NG 910 039 Pilot Assy S I T 3 Flame LP 67 PilotHolder 68 W840470...

Page 65: ...rick Panel Standard Brown 780 906 Bay Brick Panel Standard Red 780 938 Bay Front Trim Set Brass 780 936 Bay Front Trim Set Steel 112 Bay Front Trim Top Bottom 780 934 Bay Front Trim Set Gold 113 Bay F...

Page 66: ...Set Steel Black 138 Flush Louver Assy Top 139 Flush Louver Assy Btm 146 Barcelona Assy Black 148 Barcelona Louver Assy Black 510 934 Flush Glass Trim Set Brass 510 947 Flush Glass Trim Set Steel 152...

Page 67: ...LY Part Description 513 971 Cast Faceplate Set 201 Cast Faceplate Right 202 Cast Faceplate Top 203 Cast Faceplate Left 513 981 Cast Grills Set 204 Top Grill 205 BottomGrill Not available as a replacem...

Page 68: ...______________________________________________________ ______________________________________________________ _______________________________________________________________ __________________________...

Page 69: ...______________________________________________________ ______________________________________________________ _______________________________________________________________ __________________________...

Page 70: ...______________________________________________________ ______________________________________________________ _______________________________________________________________ __________________________...

Page 71: ...ed and inspected by an authorized dealer within three days of installation Reported damage after this time will be subject to rejection It is the general practice of FPI to charge for larger higher pr...

Page 72: ...pton and Panorama are trademarks of FPI Fireplace Products International Ltd FPI fireplaces are designed with reliability and simplicity in mind In addition our internal Quality Assurance Team careful...

Reviews: