FPI P36D Zero Clearance Direct Vent Gas Fireplace
24
INSTALLATION
VENTING ARRANGEMENTS - HORIZONTAL TERMINATIONS
RIGID PIPE and FPI DIRECT VENT SYSTEM (FLEX)
(Propane & Natural Gas)
The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90
o
elbow (two 45
o
elbows equal one 90
o
elbow).
Note: Must use optional rigid pipe adaptor (Part # 510-994) when using Rigid Pipe venting systems.
All Rigid Pipe Systems
4" inner diameter
6-5/8" outer diameter
FPI Flex Vent
4" inner diameter
6-7/8" inner diameter
•
Maintain clearances to combustibles.
•
Horizontal vent must be supported every 3 feet.
•
Firestops are required at each floor level and whenever passing through a wall.
NOTE: If you are installing the P36D into a FPI cabinet Mantel Kit, use the minimum horizontal vent height
(centre-line of 40-1/2"). Remember to include the mantel base (3" in height) in your calculations and to maintain the 2"
clearance from the top with rigid or flex pipe systems to the underside of the mantel top.
A vent guard should be used when-
ever the termination is lower than the
specified minimum or as per local
codes.
Note: FPI Direct Vent System
(Flex ) Part #'s 946-515 and
946-516 is only approved
for horizontal termina-
tions.
Summary of Contents for P36D-LP
Page 6: ...FPI P36D Zero Clearance Direct Vent Gas Fireplace 6 UNIT DIMENSIONS...
Page 46: ...FPI P36D Zero Clearance Direct Vent Gas Fireplace 46 FLUSH BAY DOOR OPTIONS...
Page 53: ...FPI P36D Zero Clearance Direct Vent Gas Fireplace 53 CAST FACEPLATE...
Page 62: ...FPI P36D Zero Clearance Direct Vent Gas Fireplace 62 REPLACEMENT PARTS LIST...