Part No. 20862 Rev. G February 2015
- 34 -
Chilled Cabinets
Controller Settings
CABINETS
-
SPECIFICATIONS
Changes from
Carel Defaults
The following table specifies the controller settings which differ from the Carel
default values.
Parameters not listed in this table should remain at the default values specified
in the
MPX
PRO
Parameters
listed in the
Servicing
section.
Carel MPX PRO Settings
CABINET MODEL
Parameter
No
IN
– M11C
Regulation Set Point
St
-7
Regulation Differential
rd
6
Assign intake probe (Sr)
/Fc
0
Assign aux probe 1 (Saux1)
/FG
3
Select display main terminal
/t1
1
Max int. between defrosts
dl
2
Defrost end temp
dt1
3
Max defrost duration
dP1
45
Display during defrost
d6
0
Dripping time after defrost
dd
0
Defrost time “Running time”
d10
10
Defrost temp threshold
d11
-10
Config. func. dig. Input DI1
A4
1
Config. func. dig. Input DI2
A5
2
Delay time delayed ext alarm
A7
3
Serial address
H0
5
Configure AUX 3
H7
2