Rear panel view
2.3. Installation procedure
Choose location
Step 1: UPS input connection
Step 2: UPS output connection
•
•
•
•
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
For 200/208/220/230/240VAC models: The power cord is supplied in the UPS package.
For 100/110/115/120/127VAC models: The power cord is attached to the UPS. The input plug is a NEMA L5-130P.
Install the UPS unit in any protected environment that provides adequate airflow around the unit, and free from excessive
dust, corrosive fumes and conductive contaminants. Do not operate your UPS in an environment where the ambient
temperature or humidity is high. For best performance, keep the indoor temperature between 0° C and 40° C. Place the
UPS unit at least 20 cm away from monitors to avoid interference.
Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords.
For socket-type outputs, there two kinds of outputs: programmable outlets and general outlets. Connect non-critical
devices to the programmable outlets and critical devices to the general outlets. During power failure, you may extend
the backup time to critical devices by setting shorter backup time for non-critical devices.
For terminal-type input or outputs, please follow the steps below for the wiring configuration:
a) Remove the terminal block cover by unscrewing the two screws.
b) We recommend using an AWG 14 or 2.1mm2 power cord, a AWG12-10 or 3.3mm2-5.3mm2 power cord for
the NEMA type.
c) Once the wiring configuration is complete, verify that the wires are securely attached.
d) Finally, replace the terminal cover and secure it using the screws.
Note
: Check if the site wiring fault indicator lights up in LCD panel. It will be illuminated when the UPS is plugged into an
improperly wired utility power outlet (refer to the troubleshooting section). A circuit breaker (40A) must also be provided
between the mains and AC input.
Programmable outlets: connect to non-critical loads.
Output receptacles: connect to high critical loads.
AC input
Input circuit breaker
Network/Fax/Modem surge protection
Emergency power off (EPO) connector
USB communication port
RS-232 communication port
SNMP intelligent slot
Output terminal
Output circuit breaker
Input terminal